INSTALLATION OF STANDALONE GTB WALLBOX
4. Set dip switch CC1 SW1 to the max Ampere (A) that the
Twinbox can supply according to the rating label, i e GTB11kW=
16+16A = 32A. SW1 position: see
picture
7.
5. You can by setting Dip switch SW2 on both CC1 and CC2
reduce the charging current for left or right hand side if needed.
Normally, this is normally not necessary. Available range is 6-32A
(picture 8). Dip switch 2 location See picture 7.
• It is allowed to set different values on left and right hand side.
• CC1 SW2 controls left hand side outlet/cable CC2 SW2
controls right hand side outlet/cable
Note! Max allowed (A) for each side according to table 2.
(picture 7)
(table 2)
GTB 3,7 kW = MAX 16 A
GTB 7,4 kW = MAX 32 A
GTB 11 kW = MAX 16 A
GTB 22 kW = MAX 32 A
SW2 MAX Ampere
SW1
SW2
ON OFF
ON OFF
3
3=OFF
16A
3
3=OFF
6A
2
2=OFF
2
2=OFF
1
1=ON
1
1=ON
3
3=OFF
20A
3
3=OFF
10A
2
2=ON
2
2=ON
1
1=OFF
1
1=OFF
3
3=OFF
25A
3
3=OFF
13A
2
2=ON
2
2=ON
1
1=ON
1
1=ON
3
3=ON
32A
3
3=ON
16A
2
2=OFF
2
2=OFF
1
1=OFF
1
1=OFF
3
3=ON
40A
3
3=ON
20A
2
2=OFF
2
2=OFF
1
1=ON
1
1=ON
3
3=ON
50A
3
3=ON
25A
2
2=ON
2
2=ON
1
1=OFF
1
1=OFF
3
3=ON
63A
3
3=OFF
29A
2
2=ON
2
2=OFF
1
1=ON
1
1=OFF
3
3=ON
32A
2
2=ON
1
1=ON
(picture 8)
7