background image

”Longpress” both left and right touch area to bypass the password. The blinking ”0” will stop to blink after 2 seconds

!

!

!

Rx

!

2

!

!

!

Rx

!

!

1.  Click left touch area until ”SYStEn” is visible. 

If you need to change the current System setting, follow below instructions:
2. Longpress center touch area and PrG is visible.
3. Click left or right touch area until wanted value is visible. Confirm by longpress center touch area.

!

!

!

Rx

3

1P   = N
2P   = N (3-wire)
3P   = 3phase        (3-wire)
3Pn = N (4-wire)

EN

6

System setting

Summary of Contents for GNM3T-LP RS485 N

Page 1: ...GARO AB GARO GNM3T LP RS485 N as DLM meter Box 203 SE 335 25 Gnosj info garo se garo se Manual 380253 DLM Dynamic Loadbalancing Meter Installation and Programming Manual EN...

Page 2: ...ICAL CONNECTION POWER CABLES 4 2P 4 3Pn 4 3P 4 DLM METER SETTINGS 5 Touch area 5 System setting 6 CT Ratio setting 7 UT Ratio setting 8 Modbus address information 9 Set the Modbus Adress 10 Set verify...

Page 3: ...orized electrician MODBUS CONNECTION Install the DLM meter in the mains cabinet you want to monitor Use shielded twisted pair cable between the DLM meter and the wallbox Suitable cables CAT5 FTP CAT5e...

Page 4: ...CONNECTION POWER CABLES N 1 2 3 section 4 mm torque 0 6 Nm 4 17 section 1 5 mm torque 0 4 Nm EN 4 L N F 16 17 Rx L1 L2 L3 N F N 1 2 8 4 7 9 3 5 6 L1 L2 N F N 1 2 4 7 5 6 L1 L2 L3 F 1 2 8 4 7 9 3 5 6...

Page 5: ...DLM METER SETTINGS Rx Rx 5 EN Rx Rx Rx Touch area 1 Longpress center touch area until you see PASS...

Page 6: ...a until SYStEn is visible If you need to change the current System setting follow below instructions 2 Longpress center touch area and PrG is visible 3 Click left or right touch area until wanted valu...

Page 7: ...is visible Confirm by longpress center touch area and next figure starts to blink 4 Repeat step 3 until the complete value is correct Rx 7 EN CT Ratio setting CT Ratio values depending on the CT you...

Page 8: ...area and PrG is visible 3 Click left or right touch area until wanted value is visible Confirm by longpress center touch area and next figure starts to blink 4 Repeat step 3 until the complete value i...

Page 9: ...grid use address 100 DLM settings in the webinterface are required Address 100 require an installed wifi module in the Master Wallbox Note When use of Adress 100 the wallbox will not paus the chargin...

Page 10: ...blink 2 Click left or right touch area to modify the figure 3 Longpress center touch area to change to next figure and repeat step 2 Rx Rx 4 When the adress is correct longpress center touch area to c...

Page 11: ...OTE Correct Value Baudrate 9 6 Rx Click left touch area until PArIty is visible Default is no and this is correct If you need to change the parity longpress center touch area and click left or right t...

Page 12: ...Confirm settings 1 Click left touch area until End is visible 2 Longpress center touch area when End is visible and the setting is confirmed 3 The square is blinking when DLM meter have communication...

Reviews: