Universal dimmer actuators GDA2K-400 KNX / GDA4K-400 KNX
pdated: Mai-17 (Subject to changes) Page 11 of 63
Continuation:
No.
Object name
Function
Length
Flags
C R W T
13
Channel C1
Reset service
1 bit
1.001
✓
✓
✓
-
Reset operating hours
1 bit
1.001
✓
✓
✓
-
14
Channel C1
General error message
1 bit
1.001
✓
✓
-
✓
15
Channel C1
Short circuit message
1 bit
1.001
✓
✓
-
✓
16
Channel C1
Excess temperature message
1 bit
1.001
✓
✓
-
✓
17
Channel C1
Mains power failure
1 bit
1.001
✓
✓
-
✓
18
Channel C1
Load type message (R, C/L)
1 bit
1.001
✓
✓
-
✓
30
Channel C2
Switching ON/OFF
1 bit
1.001
✓
✓
✓
-
31
Channel C2
Brighter/darker
4 bit
3.007
✓
✓
✓
-
32
Channel C2
Dimming value
1 byte
5.001
✓
-
✓
-
33
Channel C2
Soft switching
1 bit
1.001
✓
✓
✓
-
34
Channel C2
Block
1 bit
1.001
✓
✓
✓
-
35
Channel C2
Call up/save scenes
1 byte
17.001
✓
✓
✓
-
36
Channel C2
Enable scenes = 1
1 bit
1.001
✓
✓
✓
-
Block scenes = 1
1 bit
1.001
✓
✓
✓
-
37
Channel C2
Force = 0
1 bit
1.001
✓
✓
✓
-
Force = 1
1 bit
1.001
✓
✓
✓
-
Dimming value with force
1 byte
5.001
✓
✓
✓
-
Force
2 bit
2.001
✓
✓
✓
-
38
Channel C2
Dimming value limit
1 byte
5.001
✓
✓
✓
-
39
Channel C2
Feedback On/Off
1 bit
1.001
✓
✓
-
✓
40
Channel C2
Feedback in %
1 byte
5.001
✓
✓
-
✓