20
Dryer Set Point Table
DIP Switch Settings
DIP Switch
Description
On
Off
1
Evaporator Outlet Temperature Sensor
Disabled
Enabled
2
Status Menu Scrolling
Disabled
Enabled
3
Reserved
N/A
N/A
4
Reserved
N/A
N/A
Dryer Configuration
Description
Units
Lower
Upper
Increment
Default
Service Interval
Hours
0
9999
1
4000
Energy Cost
Decimal
0.00
0.99
0.01
0.13
Total Hours
Hours
0
999999
1
0
Proportional Gain
Gain
0.0
100.0
0.1
3.0
Integral Time
Seconds
0.0
200.0
0.1
100.0
Derivative Time
Seconds
0.0
200.0
0.1
20.0
Set Value
Celsius
0.0°C (32.0°F)
15.0°C (59.0°F)
0.1°C (0.2°F)
3.3°C (37.9°F)
Time On
Minutes
0.0
10.0
0.1
3.0
Time Off
Minutes
0.0
10.0
0.1
3.0
Modbus Device Address
Integer
1
247
1
1
Full Load Power
Watts
0
29999
10
0