background image

11

• No high or low temperature* alarms

*If the compressor is on, then the process control tem-
perature must drop below the process control tempera-
ture set point before the compressor will turn off.  If the
compressor is off, then the process control tempera-
ture must rise above the set point before the compres-
sor will turn on.

Percent Savings LED

Calculation of savings realized with energy saver design
compared to direct expansion design. These savings are
expressed in percent of compressor on time to dryer on
time. This mode is display only. No adjustments can be
made.

High Pressure “HiP” Alarm

A high pressure alarm occurs if the high pressure switch
opens and the display shows “HiP.” During this condition,
the compressor will shut down. The dryer cannot be re-
started until this switch is manually reset.

To reset the high pressure switch:

1.

Shutdown the dryer per the Shutdown procedure on
page 1-11.

2.

Remove the dryer front panel.

3.

Press the “Manual Reset” switch near the electrical
enclosure.

4.

Replace the dryer front panel.

5.

Restart the dryer according to the Start-up proce-
dure.

If this alarm cannot be reset or occurs frequently, consult
your local Deltech representative before servicing the dryer.

AUTOMATIC DRAIN VALVES (ADVs)

Energy Saving Cycling dryers are equipped with an elec-
tronic-timer controlled drain valve (ADV) that automatically
discharges condensate from the dryer. Controls for the dryer
drain valve are on the Controller Membrane Panel.

All models are equipped with a strainer/isolation valve ahead
of the drain valve on the separator. The strainer prevents
large particles from entering the valve. The isolation valve
allows servicing of the strainer and valve without shutting
the dryer down.

The ADV has two LED indicators and a test button to help
verify operation. Pushing the test button causes the drain
port to click open. One LED indicates that power is sup-
plied to the ADV; the other LED indicates that the drain port
is open. The power indicator turns off when the drain port
opens. If either LED fails to turn on at the proper time, refer
to the Maintenance section of this manual. If the dryer is
under warranty, call your local distributor for authorization
before servicing.

To minimize air losses, set the timer so that only air dis-
charges at the end of the open period. Recommended ini-
tial settings are a 3-second drain on time and a 4-minute
drain off time. If air discharges for more than one second,
set the timer for a longer cycle or a shorter opening. If liq-
uid discharges as the port is closing, set the timer for a
shorter cycle or a longer opening.

START-UP

Once the dryer has been installed according to instructions,
it is ready to be operated. The system is fully automatic
and does not require any auxiliary controls. It is designed
to run continuously.

Dryers with Energy Management Controller

To start the dryer:

Do not start dryer with compressed air flow through the
dryer. Close dryer isolation valves until start-up procedure
is complete.

1.

Supply power to the dryer and disengage Emergency
Stop button. The Power On LED will light indicating
power to the controller. The crankcase heater warmup
will begin (the display will show the number of minutes
remaining in the warmup period). This warmup period
is essential to allow the compressor oil to warm and
boil off liquid refrigerant, preventing compressor fail-
ure. The warmup will be skipped only if the dryer was
started previously and supply power has been off for
less than 60 minutes.

  NOTE

The Dryer On LED will blink if the START button is
pressed before the end of the warm-up period.

2.

During the warm-up period, review the INSTALLA-
TION instructions to make sure the dryer has been
properly installed.

3.

If the dryer is water-cooled, open water supply lines.

4.

After the warm-up period, push the START button.
The Start button energizes the controller for normal
operation.

Immediately after pushing the START button, the Dryer
On LED will light, the condensate drain valve will open,
and the Drain Open LED will turn on.

If the dryer does not operate normally as indicated
above:

• Verify power is supplied to the dryer.

• Verify voltage supplied to the dryer matches the volt-

age stamped on the dryer data plate.

• Check customer-supplied circuit breakers for fuses.

Replace as required.

Summary of Contents for RCD800

Page 1: ...050414 CONTENTS INTRODUCTION 2 SAFETY 2 SAFETY INSTRUCTIONS 3 RECEIVING AND INSPECTION 3 INSTALLATION 3 HOW IT WORKS 5 ENERGY MANAGEMENT CONTROLLER EMC 7 EMC MEMBRANE PANEL 8 AUTOMATIC DRAIN VALVES AD...

Page 2: ...der pressure within the dryer can cause severe injury or death 4 High voltage in the motor and control box is danger ous The dryer must be installed in accordance with recognized electrical codes Befo...

Page 3: ...m filing and processing is your responsibility Handling The dryer is mounted on a base to facilitate moving the dryer with a forklift Forks should extend all the way through the forklift channels prov...

Page 4: ...cause a rise in dew point unless the dryer inlet air flow is reduced The refrigerant discharge pressure control will shut down the refrigerant compressor if cooling water is inadequate Table 2 COOLING...

Page 5: ...es CAUTION Operation of dryers with improper line voltage con stitutes abuse and could affect the dryer warranty Standard dryer enclosures and controls are designed to meet NEMA Type 1 electrical stan...

Page 6: ...CUT OUT SWITCH AMBIENT AIRFLOW CONDENSER DISCHARGE COMPRESSOR SUCTION SERVICE ACCESS VALVE HPS GLYCOL TANK GLYCOL MIXTURE SEPARATOR DRAIN SUCTION COMPRESSOR DISCHARGE CONDENSER WATER OUT WATER IN WAT...

Page 7: ...l e D r e y r D e t u n i m 1 o t 0 s d n o c e s 0 6 s e t u n i m 0 6 o t 1 y a l e d o N s t r a t s e r r e y r d y l e t a i d e m m i s r u o h 4 o t 1 s r u o h 4 o t 1 p u m r a w l l i w r e...

Page 8: ...he dryer i e the Dryer On LED is off Up and Down Buttons Used to change the display for the right hand column of LEDs when the DISPLAY SELECT button is pressed These buttons are also used to select th...

Page 9: ...setting the drain open times Drain Closed LED Indicates when the automatic drain valve is closed See Set Auto Drain Off Time Min for information on setting the drain closed times Fahrenheit LED Indic...

Page 10: ...ff time Press the DISPLAY SELECT button until the Set Auto Drain Off Time Min LED is lit The display will show the current drain off time setting in minutes Press the up or down button to increase or...

Page 11: ...rn on at the proper time refer to the Maintenance section of this manual If the dryer is under warranty call your local distributor for authorization before servicing To minimize air losses set the ti...

Page 12: ...equire little maintenance for satisfactory operation Good dryer performance can be ex pected if the following routine maintenance steps are taken DANGER Dismantling or working on any component of the...

Page 13: ...or blow out debris with compressed air from an OSHA approved air nozzle that limits its discharge pressure to 30 psig 12 Check that small port in diaphragm assembly is clear and solenoid coil moves fr...

Page 14: ...I e g r a h e r d n a r i a p e r k a e l e t a c o L y r o t c a f t l u s n o c d e c a l p e r n o i t c u s t n a r e g i r f e R n a h t r e h g i h e r u t a r e p m e t l a m r o n F 0 2 1 n a...

Page 15: ...ype Valve Aids in Disconnecting Compressor from the System PRESSURE GUAGE THERMOMETER DRIP LEG MANOMETER DIFFERENTIAL PRESSURE INDICATOR AUTOMATIC DRAIN VALVE FALSE LOADER Blows Off Air Outside of Com...

Page 16: ...7 2 1 7 0 1 4 6 5 1 2 2 2 3 5 9 7 0 1 2 0 0 2 1 3 7 8 1 5 7 3 7 0 1 8 1 5 2 1 7 8 7 9 5 8 3 5 7 7 1 9 8 9 6 2 7 2 1 7 0 1 8 5 5 6 9 1 2 6 0 0 1 3 2 2 2 NOTE Dimensions and weights are for reference o...

Page 17: ...oltage 460 3 60 Max Min voltage 506 414 Rated Load Amps 7 69 9 62 9 94 Locked Rotor Amps 42 67 80 Minimum Circuit Ampacity 11 69 14 21 14 82 Branch Circuit Fuse Size amps 17 5 20 20 Watts 35 F Evapora...

Page 18: ...18 REPLACEMENT PARTS Air Cooled Models 800 1200 scfm 1 6 7D 7C 9 3 4 5 7A 7B 6 8 2 7A 7B REAR VIEW TOP VIEW FRONT VIEW LEFT SIDE VIEW...

Page 19: ...G 4 0 5 9 9 0 3 G 0 8 5 8 6 0 3 G r o t i c a p a C n u R r o t o M n a F 1 9 0 1 5 0 3 G 1 9 0 1 5 0 3 G 8 5 9 2 6 0 3 G 6 0 6 3 0 6 4 r o s s e r p m o C 0 5 2 6 3 1 3 G 0 4 6 0 1 1 3 G 9 7 1 9 9 0...

Page 20: ...20 REPLACEMENT PARTS Water Cooled Models 800 1200 scfm FRONT VIEW TOP VIEW LEFT SIDE VIEW REAR VIEW 3 1 2 9 5 8 6 4 7D 7C 7A 7B 7A 7B...

Page 21: ...3 G r o t c a t n o C r o s s e r p m o C 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G 9 2 6 6 3 1 3 G t i K r e m r o f s n a r T 4 9 3 4 9 0 3 G G 0 8 2 5 6 0 3 9 8 9 0 1 1 3 G y l b m e s s A w o l F r i A A 7...

Page 22: ...SIC TMR 1 2 3 POWER 21 J5 22 20 J4 NO ALARM CONTACTS NO NC GND EMERGENCY STOP SWITCH COMPRESSOR FAN1 1 2 3 HIGH PRESSURE CUT OUT WITH MANUAL RESET HPS M 32 RC DRAIN VALVE RATING 5A 115 VAC 5A 24 VDC 1...

Page 23: ...ER 2 1 IDP DIP SWITCHES 1 2 3 SEE NOTE 14 6 5 8 7 COMPRESSOR 1 1 2 CUTOUT SW J8 2 DRAIN VALVE J7 1 2 3 4 1 2 3 J6 ALARM J5 C OPTION DRAIN VALVE 1 TMR 20 20 3TS 21 2SOL POWER J4 CHASSIS GROUND 5A 24 VD...

Page 24: ...2 2 1 1 2 CONTROLLER 2 1 IDP DIP SWITCHES 1 2 3 SEE NOTE 14 6 5 8 7 COMPRESSOR 1 1 2 CUTOUT SW J8 2 DRAIN VALVE J7 1 2 3 4 1 2 3 J6 ALARM J5 DRAIN VALVE 1 TMR 20 20 3TS 21 2SOL POWER J4 CHASSIS GROUN...

Page 25: ...1 2 4 1 5 3 1 2 4 1 12 12 12 12 6 6 6 4 ENCLOSURE COVER 3091860 8 1 13 T 16 15 14 16 15 14 13 11 17 18 19 20 6 21 21 6 5 9 21 9 11 16 15 14 13 8 2FU2FB 3TS 16 15 14 13 17 18 19 20 6 21 9 23 24 0020244...

Page 26: ...y a l p s i D e t a D e m i T y B n i a r D o t u A e v l a V l i O p m o C l e v e L n O r e w o P h g i H e r u t a r e p m e T m r a l A w o L e r u t a r e p m e T m r a l A s s e c o r P s l o r...

Page 27: ...27 NOTES...

Page 28: ...SLY IN LIEU OF THE IMPLIED WARRANTY OF MERCHANTABILITY AND THE IMPLIED WAR RANTY OF FITNESS FOR A PARTICULAR PURPOSE THE MANUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAM AGE BY REASON OF STRICT LIABIL...

Reviews: