13-17-621 Page 28
If the alarm icon in the Alarm column is an outline, as shown in Figure 26, the alarm is no longer active
and may be reset. If the alarm icon is solid (
), the fault is still active and the condition must be
resolved before it can be cleared.
Once all faults have been resolved, press the
Reset All
button, which will move the alarms to the Alarm
History screen. Once all faults have been reset, return to the Home screen.
3.8 Jogging the Motors
If this is the first time that the machine has been started after being connected to power, the motors must
be jogged to verify correct rotation. To do this, you must be logged in as a Technician. After logging in,
navigate to Diagnostics -> Jog Motors. The Jog Motors screen is shown in Figure 27.
Figure 27: Jog Motors Screen
Select the desired jog duration and select Compressor Motor or Fan Motor from the dropdown as shown.
You will need to jog both individually to verify correct rotation. The Jog Delay field allows you to delay the
start of the jog from the time that you press the
Start Jog
button. This is to allow you time to get into a
position to view the rotation before the motor is started. Note that the controller will only allow one jog
every 10 seconds and will disable the
Start Jog
button during this time period.
After correct rotation has been verified, return to the Home screen and proceed to operate the
compressor.
3.9 Operating the Compressor
The compressor is now ready to operate. This section gives a basic overview of how to operate the
machine.
3
.
9.1 Starting
From the home screen, the Message Status Bar
should display “Ready to Start” as shown in Figure 28.