background image

3. Safety regulations 

13 

Maintenance/rectification of faults  

The employer has to inform the employee of the 
dangers possibly arising during the repair and 
maintenance of the machine/unit as well as on how to 
avoid them; the employee has to observe all measures 
for safety at work. Safety equipment for the prevention 
or elimination of danger has to be maintained regularly 
and functionally checked at least once a year. Faults 
observed have to be immediately rectified and/or 
reported to the responsible person.  

Use only original spare parts.  

Only carry out maintenance and repair work when the 
system is not in operation and the power supply 
disconnected. Ensure that the power unit cannot be 
switched on inadvertently.  

Before removing or opening pressurized components, 
positively isolate any source of pressure and 
depressurize the entire system.  

Never weld near oil systems or carry out any other work 
requiring heat. Pressure reservoirs or components and 
pipes containing oil have to be drained completely and 
cleaned, for example by means of a steam jet, before 
beginning such work.  

Never weld any pressure reservoir or change it in any 
way.  

If work which produces heat, flames or sparks has to be 
carried out on a machine, the adjacent components 
have to be protected by means of non inflammable 
material.  

Before releasing the power unit for operation after 
maintenance or overhaul, check that the operating 
pressures, temperatures and time settings are correct 
and that the regulating and shut-down equipment 
function properly. 

Motor, air filter, electrical components and regulating 
equipment have to protected from the ingress of 
humidity, e.g. when cleaning the system by means of a 
steam jet. 

Under no circumstance must the sound-proofing 
material be removed or modified. 

Never use etching solvents which could attack the 
materials used. 

If indicated or if there is any suspicion that an internal 
part of the machine has run hot, the machine has to be 
shut down. 

In order to avoid an increase in the operating 
temperature, check and clean the heat transfer surfaces 
(cooling fins, intermediate cooler, water cooling jackets, 
etc.) at regular intervals. Prepare a plan of the most 
favourable cleaning intervals for each machine. 

Avoid damage to the safety valves and other pressure 
reducing components. Check in particular for clogging 
caused by paint, oil carbon or the accumulation of dust, 
which could deteriorate the effectiveness of these 
components. 

Insulation or protective shielding, the temperature of 
which may exceed 70 °C/158 °F and which could be 
erroneously touched by the personnel, must not be 
removed before these parts have cooled down to room 
temperature.  

Check the accuracy of pressure and temperature 
indicators at regular intervals. If the admissible 
tolerance limits have been exceeded, these devices 
have to be replaced.  

Before removing or overhauling a compressor, a motor 
or another machine, ensure that all moveable parts of a 
mass of more than 15 kg cannot move or roll away. 

After completion of repair work, always verify that no 
tools, loose parts or cloths have been left in or on the 
machine, drive motor or drive equipment. Machines 
performing a back and forward main movement have to 
be cycled at least once, rotating machines have to be 
cycled several times in order to ensure that there are no 
mechanical faults in the machine or the drive member. 
Check the direction of rotation of the electric motors 
during first commissioning and after each modification 
of the electrical connections in order to prevent the 
compressor from being damaged. 

The fastening of loads and the instructing of crane 
operators should be entrusted to experienced persons 
only. The person giving the instructions must be within 
sight or voice contact with the operator. 

For carrying out overhead assembly work always use 
specially designed or otherwise safety-orientated 
ladders and working platforms. Never use machine 
parts as a climbing aid. Wear a safety harness when 
carrying out maintenance work at greater heights. 

Keep all steps, handles, handrails, platforms, landings 
and ladders free from dirt, snow and ice! Clean the 
machine, especially connections and threaded unions, 
of any traces of oil, fuel or preservatives before carrying 
out maintenance or repair work! Never use aggressive 
detergents! Use lint-free cleaning rags!  

Before cleaning the machine with water or steam jet 
(high pressure cleaner) or other cleaning agents, 
cover/mask all openings which have to be protected 
from the ingress of water, steam or detergents for 
safety and/or functional reasons, in particular electric 
motors and switch cabinets.  

After cleaning, remove the covers/masking completely !  

Check all hydraulic oil lines for leakage, loose fittings, 
abrasion and damage after cleaning. Any defect must 
be rectified immediately!  

Always re-tighten screwed connections which have  
been loosened for maintenance and repair work.  

Summary of Contents for ESM 30

Page 1: ...Original User Manual Screw Air Compressor ESM 30 ESM 50 GB CDN USA Id no ZS1064358 00 January 2010...

Page 2: ......

Page 3: ...er is advised to contact the local Gardner Denver Company or Distributor who is supplied with revised and up dated information In any communication concerning the compressor it is essential to quote t...

Page 4: ...e Address ______________________________________________________________________________________ ______________________________________________________________________________________ ________________...

Page 5: ...in the operating manual and complying with the inspection and maintenance directives 1 3 Maintenance Carefully performed maintenance is imperative this ensures that your screw compressor can meet all...

Page 6: ...ot be accepted in the case of Operating errors Incorrect maintenance Wrong auxiliary materials Use of spare parts other than Gardner Denver genuine spare parts Modifications and changes to the install...

Page 7: ...tion 27 5 1 Transport 27 5 2 Installation 28 6 Preparations for commissioning 29 6 1 Cooling air volume minimum cross 29 6 2 Compressed air connection 30 6 3 Electrical connection 30 6 3 1 Electrical...

Page 8: ...echnical Data 49 10 1 1 EUROPE version ESM 30 ESM 37 49 10 1 2 EUROPE version ESM 45 ESM 50 50 10 1 3 North America version ESM 30 ESM 37 51 10 1 4 North America version ESM 45 ESM 50 52 10 2 Layout p...

Page 9: ...esponsibility and duty of notification for taking into account in plant factors for example regarding work organization sequences of operations personnel assigned to certain tasks are to be added to t...

Page 10: ...accessories This applies also to the installation and setting of safety equipment and valves as well as to welding on structural or pressurized parts 3 4 Installation and normal operation Installatio...

Page 11: ...possible and where the temperatures never rise above or fall below the respective limit values as indicated in the operating instructions If required the cooling air is to be taken from a cleaner coo...

Page 12: ...l operations or maintenance work Appoint a person to supervise the activities Maintenance and repair work may only be carried out under the supervision of a person who is qualified for this work Oil l...

Page 13: ...oil carbon or the accumulation of dust which could deteriorate the effectiveness of these components Insulation or protective shielding the temperature of which may exceed 70 C 158 F and which could...

Page 14: ...ust and other inflammable substances and make sure that the premises are adequately ventilated risk of explosion Adhere to the regulations valid for the place of operation Observe any existing nationa...

Page 15: ...tions must be taken Compressors which are to be shut down for a lengthy period must also be protected from corrosion Since corrosion occurs more quickly in damp atmospheres than in dry conditions it i...

Page 16: ...8 Symbols and explanations Carefully read the operating manual before commissioning or servicing this compressor Never breathe in compressed air from this system Never operate the unit with open door...

Page 17: ...3 Safety regulations 17 Warning Hot surface Warning Pressurized part or system Warning This system can start up by means of a remote control or automatically after a power failure...

Page 18: ...3 Safety regulations 18 Warning The system continues to run for 30 seconds after pressing the O key Warning Danger of electric shock Attention Lifting point...

Page 19: ...egulations 19 Attention Check and if required re tighten connection terminals For further details see the operating instructions Attention Opening pressure safety valve xx bar value xx see sticker on...

Page 20: ...ir inlet filter mat 19 Compressed air outlet 20 Base frame 21 Control keypad 22 EMERGENCY OFF push button 23 Control cabinet 24 Supply cable gland 25 Final compression temperature sensor 26 Network pr...

Page 21: ...ball valve 9 Safety valve 10 Oil filter monitor S5 11 Oil filter 12 Oil cooler 13 Throttle 14 Check valve 15 Pressure holding and check valve 16 Compressed air after cooler 18 Final compression pressu...

Page 22: ...ottle 14 Check valve 15 Pressure holding and check valve 16 Compressed air after cooler 18 Final compression pressure sensor B2 19 Control valve Y1 20 Control blow off valve Y4 21 Blow off valve 22 Oi...

Page 23: ...sequent fine separation by the separator element 7 Fig 3 the compressed air with a low oil content is fed via the minimum pressure valve 15 Fig 3 and the air cooler 16 Fig 3 into the consumer network...

Page 24: ...g instructions for the compressor control GD Pilot MK Danger The lower control area of the operating cylinder 2 1 is generally pressurised even when the system is at a standstill Before working on the...

Page 25: ...trol area is bled via the solenoid valve 20 Y4 The oil separator vessel 6 is released to the idle pressure residual pressure The screw compressor is now running in the offload mode The cooling air ven...

Page 26: ...he operating cylinder The suction regulator valve opens the lower control area is bled through the pipe 22 by the solenoid valve 7 Y1 Fig 4 Idling mode As soon as mains pressure has been attained both...

Page 27: ...e proper lifting of the load according to the operating instructions of the load suspension device has to be ensured Important Never lift or lash the compressor and its hood via the enclosure The scre...

Page 28: ...perating instructions Important The operator has to provide adequate ventilation for the compressor station The screw compressor unit has to be levelled A minimum distance from walls other machines et...

Page 29: ...nd a minimum duct cross section of approx 0 55 m2 6 ft2 Important The stated minimum cross section refers to a maximum duct length of 5 m 16 4 ft and a maximum of one bend In the event of differing va...

Page 30: ...wer electric components any kind of operation outside of the stated limits of EN60204 1 IEC60204 1 is inadmissible The customer has to connect a main switch in the incoming line of the compressor unit...

Page 31: ...example Fig 13 Danger When carrying out adjustment work on the control power transformer the unit must be electrically isolated and locked off Work on the control cabinet may only be carried out by el...

Page 32: ...3x70PE35 4G35 4G35 ESM 45 ESM 50 230V 380V 460V 45 200 125 100 3x95PE50 4G50 4G35 Notes on the table We do not know the cable type used by you its length and the installation conditions temperatures g...

Page 33: ...the control power transformer output voltages during under load operation and if required re set Several tapping points are provided for this purpose see circuit diagram Fig 13 Danger When carrying ou...

Page 34: ...connect switch or circuit breaker so that electrical power may be disconnected while the unit is being serviced The fuse line disconnect should be located and moun ted in accordance with all state loc...

Page 35: ...reservoir sight glass see also chapters 8 4 and 8 13 Check the oil level as follows Stop the compressor with the stop button Wait at least 5 minutes for the oil to settle and for the air to disperse...

Page 36: ...OSS must be acknowledged before the unit can be started To this end press the acknowledgement pushbutton 4 Fig 16 After the acknowledgement the message READY TO START appears on the display unless ano...

Page 37: ...ction of rotation for compressor direction of rotation may deviate from this representation Note For switching the compressor off normally use only the stop push button 3 Fig 16 but not the EMERGENCY...

Page 38: ...SS must be acknowledged before the unit can be started To this end press the acknowledgement push button 4 Fig 16 After the acknowledgement the message READY TO START appears on the display unless ano...

Page 39: ...crew compressor unit comprises the Maintenance and inspection manual for Gardner Denver compressors in which you can list your performed maintenance work at the specified intervals You can also have t...

Page 40: ...oil change intervals and cleaning intervals in the event of heavy soiling For order numbers see the spare parts list Due at x service hours 3 000 h 6 000 h 9 000 h 12 000 h 15 000 h 18 000 h At the l...

Page 41: ...e of the new oil fill considerably Do not mix lubricating oils of different makes When changing over to a new oil type the oil in the oil circuit must be drained completely For the oil change interval...

Page 42: ...kage Check oil level see chapter 6 4 If required top up oil Changing intervals for oil filter cartridge The operating conditions e g coolant temperatures the operating modes and the quality of the int...

Page 43: ...Remove used oil fine separator 1 Fig 19 a Clean sealing faces and if required remove and clean O rings Install new oil fine separator Swivel reservoir cover back to the initial position Turn cheese he...

Page 44: ...air filter cartridge The operating conditions e g coolant temperatures the operating modes and the quality of the intake air e g content of dust content of gaseous foreign matter such as SO2 solvent...

Page 45: ...tructions Blow off the screw compressor unit with compressed air at the specified intervals never direct compressed air towards persons paying particular attention to Regulating elements Fittings Comp...

Page 46: ...ommendations Please note that proper lubrication will considerably increase the service life of your compressor unit According to regulations relating to the prevention of accidents use lubricants the...

Page 47: ...ower switch set point 8 Wait until the mains pressure has fallen below the lower switch set poin Unit stops during the start up phase 1 Intake regulator only closes partly pressure builds up too quick...

Page 48: ...in the compressed air 1 Oil fine separator defective 1 Replace oil fine separator cartridge 2 Oil foams 2 Change oil 3 Oil level too high 3 Drain off oil 4 Minimum pressure valve defective 4 Check mi...

Page 49: ...air delivery connections male screwed thread EN 10226 R 1 1 2 DIN 2999 R 1 1 2 Weight kg 923 966 Dimensions L x W x H mm 1722 x 920 x 1659 ESM 30 ESM 37 Technical Data 60Hz 7 5 9 13 7 5 9 13 Maximum...

Page 50: ...nnections male screwed thread EN 10226 R 1 1 2 DIN 2999 R 1 1 2 Weight kg 988 1055 Dimensions L x W x H mm 1722 x 920 x1659 ESM 45 ESM 50 Technical Data 60Hz 7 5 9 13 7 5 9 Maximum operating pressure...

Page 51: ...00V 230V 460V 575V Amps 143 124 63 50 170 148 75 59 Standard drive motor detail TEFC IP55 EPACT Drive motor speed rpm 3600 Fan motor rating hp kW 1 2 0 86 IP 54 Suggested cable size 200V 230V 460V 575...

Page 52: ...rrent max IP55 200V 230V 460V 575V Amps 207 180 90 73 Standard drive motor detail TEFC IP55 EPACT Drive motor speed rpm 3600 Fan motor rating hp kW 2 0 1 5 IP 54 Suggested cable size 200V 230V 460V 57...

Page 53: ...ondensate connection only for dryer option or for integrated water separator option outer 10 for polyamide pipe PA11 12 C Water inlet cold only for integrated heat recovery option D Water outlet hot o...

Page 54: ...10 Annex 54 Fig 24 all dimensions in mm...

Page 55: ...ant provisions 2009 105 EG 97 23 EG 2004 108 EG 2006 42 EG 3 If the machine is modified in a way not agreed upon with us this statement will be void 4 Harmonised standards applied particularly EN 1012...

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ...essor Division 1800 Gardner Expressway Quincy Illinois 62305 Telephone 800 682 9868 Fax 217 224 7814 Gardner Denver Deutschland GmbH Argenthaler Str 11 55469 Simmern Deutschland Tel 49 0 6761 832 0 Fa...

Reviews: