13-17-613 Page 64
Table 5-4: Oil Control Parameter Definitions
Injection
Delta T
Parameter A
VC Low Oil Temp
Valve Max CMD
Parameter B
V1 High Oil Temp
Valve Min CMD
Parameter C
V2 Low Oil Temp
Valve PID Gain
Parameter D
V2 High Oil Temp
Valve PID Int Time
Parameter E
Full Flow Start Time
Valve PID Diff Rate
Parameter F
State Mach Step Period
Valve PID Dead Band
Parameter G
Not Used
Valve B Pressure
5.4.9.3 Aftercooler Temp Rise
Accessibility
Maintenance
Distributor
Factory
The
Aftercooler Temp Rise
defines the target temperature rise across the air aftercooler.
5.4.9.4 Target Temperature Adjust
Accessibility
Maintenance
Distributor
Factory
The
Target temperature Adjust
is a factory parameter used to change the scale for the target
temperature calculation on machines using the delta T oil control method.
5.4.10 Control Pressure
The
Control Pressure
menu allows configuration of the control and restart pressure settings on the
machine.
Note:
These settings are machine-specific and should not be adjusted unless directed by Gardner
Denver.
The
Control Pressure
menu structure is organized as follows:
5.4.10.1 Control Pressure
Accessibility
Maintenance
Distributor
Factory
The
Control Pressure
setting is the minimum pressure that must be achieved in the air/oil reservoir
before the controller will switch from the starting sequence to the
loaded
state at which modulation
occurs.