13-18-612 Page 60
6-5
To increase water flow (e.g., decrease exiting cooling water temperature) turn the adjusting screw
from right to left, decreasing spring tension. (The groove at the lower edge of the adjusting screw is
an index line for use with the index scale 0 to 8 in obtaining a desired setting).
Care must be used when handling the capillary tube; a kink or break in the tubing or connections will
make the valve inoperative. Never attempt to change capillary length. Excess capillary tube should be
carefully coiled and placed so that damage will not occur with normal maintenance or traffic past the unit.
If a leak develops through the packing, tighten the packing gland nut firmly with a wrench to reseat the
packing around the valve stem, back off the nut until loose and finally retighten the nut finger tight.
Tightening the packing nut too tight may cause erratic operation. An occasional drop of oil on the valve
stem at the packing nut will prolong packing life.
If the valve malfunctions, check for a bend or binding in the capillary tube, paint or corrosion on valve
stem, foreign material in valve, erosion or thermal system (capillary) failure.
WATER FLOW SHUTOFF VALVE -
This device completely shuts off the flow of cooling water when the
compressors are not operating. Its normally closed state prevents the waste of cooling water even in the
case of power failure. It is a common companion to the water flow regulating valve.
The water flow regulating valve and the water shutoff valve are factory-installed options. If the presence
of foreign material or scale formation in the cooling water is likely, the use of a strainer in the inlet water
line is recommended.
OPTIONAL WATER SEPARATOR AND DRAIN
– These devices separate and drain the water
(condensed by the air cooler) mixed with the compressed air delivered by the compressor package. The
optional water separator assembly is shipped loose and must be field-installed by the end user:
Figure 6- 4
– WATER SEPARATOR AND DRAIN
Summary of Contents for AirSmart VS80-110B
Page 33: ...13 18 612 Page 32 4 7 300CGE546 04 Ref Drawing Page 2 of 4...
Page 34: ...13 18 612 Page 33 4 8 300CGE546 04 Ref Drawing Page 3 of 4...
Page 35: ...13 18 612 Page 34 4 9 300CGE546 04 Ref Drawing Page 4 of 4...
Page 37: ...13 18 612 Page 36 4 11 301CGE546 B Ref Drawing Page 2 of 4...
Page 38: ...13 18 612 Page 37 4 12 301CGE546 B Ref Drawing Page 3 of 4...
Page 39: ...13 18 612 Page 38 4 13 301CGE546 B Ref Drawing Page 4 of 4...
Page 41: ...13 18 612 Page 40 4 15 302CGE546 05 Ref Drawing Page 2 of 4...
Page 42: ...13 18 612 Page 41 4 16 302CGE546 05 Ref Drawing Page 3 of 4...
Page 43: ...13 18 612 Page 42 4 17 302CGE546 05 Ref Drawing Page 4 of 4...
Page 45: ...13 18 612 Page 44 4 19 303CGE546 B Ref Drawing Page 2 of 4...
Page 46: ...13 18 612 Page 45 4 20 303CGE546 B Ref Drawing Page 3 of 4...
Page 47: ...13 18 612 Page 46 4 21 303CGE546 B Ref Drawing Page 4 of 4...
Page 70: ...13 18 612 Page 69 9 2 Figure 9 1 MINIMUM DISCHARGE PRESSURE CHECK VALVE...
Page 86: ...NOTES...
Page 87: ...NOTES...