Minimum – Maximum Operating Conditions

25

35

50

75

100 / 125

150

Min.-Max. Inlet Air Pressure (compressed air at inlet to dryer)

30 psig (2.1 kgf/cm

2

) - 250 psig (17.6 kgf/cm

2

)

Max. Inlet Air Temp. (compressed air at inlet to dryer)

120

°

F (49

°

C)

Min.-Max. Ambient Temperature

Air-cooled 45

°

F (7

°

C) - 110

°

F (43

°

C)  Water-cooled 45

°

F (7

°

C) - 130

°

F (54

°

C)

Refrigeration System Data

Compressor Type

Hermetic - Resistance Start, Induction Run - Non-Cycling

Refrigeration Compressor Horsepower

1/6

1/5

1/4

1/3

1/2

3/4

BTU/HR – Refrigeration Only

@ 35

°

F Evaporator & 100

°

F Ambient                               

60 Hz / 50 Hz

1010 / 842

1380 / 1150

2160 / 1800

2780 / 2317

4430 / 3692

6020 / 5017

Refrigerant Type

 R-134a

R-134a

R-134a

R-134a

R-134a

R-134a

Refrigerant Charge

              See dryer serial number tag

Suction Pressure Setting (controlled by hot gas by-pass valve)

31.5 psig

31.5 psig

31.5 psig

31.5 psig

31.5 psig

31.5 psig

Condenser Fan Switch Setting (in-out) (psig)

NA

NA

NA

NA

NA

110-70

Air Flow Across Condenser (cfm)                                     

 60 Hz / 50 Hz

 105 / 98

235 / 196

275 / 229

220 / 183

350 / 292

530 / 440

Condenser Cooling Water Requirements (gpm @ 85

°

F)

NA

NA

NA

NA

NA

2.2 / 1.8

(water-cooled models only) (40 psig min. pressure)

Electrical

Nominal Voltages

115/1/60

Max.- Min. Voltage

127-104

127-104

127-104

127-104

127-104

127-104

Rated Load Amps

3.4

3.9

5.9

7.4

10.3

14.7

Locked Rotor Amps

18.0

22.0

28.0

35.0

48.0

66.3

Minimum Circuit Ampacity

4.0

4.7

7.3

9.1

12.4

18.3

Branch Circuit Fuse Size (amps)

15

15

15

15

20

25

Watts @ 35

°

F Evaporator & 100

°

F Ambient

280

290

465

600

815

1060

Resistance (ohms)                                Single phase                 Start C/S

---

---

---

---

---

3.15

                                                                                                  Run C/R

---

---

---

---

---

0.416

    Overload

                    Thermal & Current (Auto reset)

Nominal Voltages

208-230/1/60

Max.-Min. Voltage

253-187

253-187

253-187

253-198

253-187

253-198

Rated Load Amps

1.8

2.1

3.0

4.1

5.1

8.3

Locked Rotor Amps

8.5

13.7

14.4

19.0

23.0

33.5

Minimum Circuit Ampacity

2.2

2.6

3.7

5.1

5.2

10.5

Branch Circuit Fuse Size (amps)

15

15

15

15

15

15

Watts @ 35

°

F Evaporator & 100

°

F Ambient

280

290

470

600

815

1060

Resistance (ohms)                                Single phase                 Start C/S

---

---

---

---

---

7.92

                                                                                                  Run C/R

---

---

---

---

---

1.55

Overload

                    Thermal & Current (Auto reset)

Nominal Voltages

220-240/1/50

Max.-Min. Voltage

264-198

264-198

264-198

264-198

264-198

264-198

Rated Load Amps

1.6

1.8

2.6

3.5

4.2

7.6

Locked Rotor Amps

8.7

10.7

14.5

15.2

21.0

53.0

Minimum Circuit Ampacity

2.0

2.2

3.2

4.4

5.2

9.9

Branch Circuit Fuse Size (amps)

15

15

15

15

15

15

Watts @ 35

°

F Evaporator & 100

°

F Ambient

223

257

395

507

669

930

Resistance (ohms)                                Single phase                 Start C/S

---

---

---

---

---

10.49

                                                                                                      Run C/R

---

---

---

---

---

1.8

Overload

                    Thermal & Current (Auto reset)

ENGINEERING DATA

Summary of Contents for 9VXRD025

Page 1: ...9VXRD035 9VXRD050 9VXRD075 9VXRD100 9VXRD125 9VXRD150 CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 4 3 0 MAINTENANCE 7 SIZING 7 ENGINEERING DATA...

Page 2: ...and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the deliv...

Page 3: ...designed to operate in ambients from 45 to 110 F 7 to 43 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is in...

Page 4: ...cool the air with an aftercooler B Air Outlet Connect air outlet to downstream air lines C By pass piping If servicing the dryer without interrupting the air supply is desired piping should include in...

Page 5: ...ed models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 45 F 7 C On Off Switch Power On Light Dewpoint Indicator Green 2 2 Start up Energize compressor by positioning the on...

Page 6: ...lly To facilitate service maintenance kits are available 3 0 Maintenance Sizing Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at var...

Page 7: ...nal Voltages 115 1 60 Max Min Voltage 127 104 127 104 127 104 127 104 127 104 127 104 Rated Load Amps 3 4 3 9 5 9 7 4 10 3 14 7 Locked Rotor Amps 18 0 22 0 28 0 35 0 48 0 66 3 Minimum Circuit Ampacity...

Page 8: ...l 50 208 230V 60Hz Model 75 208 230V 60 Hz 220 240V 50 Hz Models 100 125 All Voltages Model 150 230V 60 Hz Legend PBS Push button switch 1LT Power on light SR Start Relay CAP Start Capacitor MTR Compr...

Page 9: ...16 1 13 16 1 15 16 1 15 16 1 15 16 2 3 16 2 3 16 E 4 4 5 5 5 5 5 F 15 16 15 16 15 16 15 16 15 16 15 16 15 16 G 1 7 8 1 7 8 1 7 8 1 7 8 1 7 8 1 7 8 1 7 8 H 3 3 3 3 3 3 3 I 1 3 16 1 3 16 1 3 16 1 3 16...

Page 10: ...ture a Power failure b Line disconnect switch open c Blown fuses open breaker d Faulty wiring loose terminals a High or low ambient conditions b Air cooled models Dirty clogged condenser fins obstruct...

Page 11: ...31 735 5 Contactor G5910 134 11 Maintenance Kit 9VXMK4 9VXMK4 9VXMK4 9VXMK5 9VXMK5 9VXMK5 Element GE9 24 GE9 24 GE9 24 GE9 28 GE9 28 GE9 28 Drain G4460 151 10 G4460 151 10 G4460 151 10 G4460 151 10 G4...

Page 12: ...NUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE...

Reviews: