background image

4

1.4  Electrical connections

A.   Dryer is designed to operate on the voltage, phase,

and frequency listed on the serial number tag.

B.   Dryer is supplied with a cord and plug. Install in a

receptacle  of proper voltage.

NOTE:
Refrigeration condensing unit is designed to run continu-
ously and should NOT be wired to cycle on/off with the air
compressor.

NOTE:
Models 150 (115V only)—install plug in receptacle rated
for  20 amps.

1.3  Piping connections

A.   Air Inlet—Connect compressed air line from air

source to air inlet.

WARNING:

 Refer to Serial Number Tag for maximum

working pressure.  Do not exceed dryer’s Maximum
Working Pressure.

NOTE:
Install dryer in air system at highest pressure possible
(e.g. before pressure reducing valves).

NOTE:
Install dryer at coolest compressed air temperature
possible. Maximum inlet compressed air temperature:
120

°

F (49

°

C). If inlet air exceeds this temperature, precool

the air with an aftercooler.

B.   Air Outlet—Connect air outlet to downstream

air lines.

C.   By-pass piping—

If servicing the dryer without interrupting the
air supply is desired, piping should include
inlet and outlet valves and an air by-pass valve.

D.   Water cooled models—cooling water inlet and

outlet

1.   Connect cooling water supply to cooling water

inlet.

2.   Connect cooling water return line to cooling

water outlet connection.

NOTE:
Strainer and water regulating valve are supplied on water
cooled models.

Air Inlet

Air Outlet

1.5 Moisture separator

A.   Separator has an internal drain which automatically

discharges collected condensate. It may be desirable
to pipe the condensate from the Automatic Drain
outlet to a suitable drain.

NOTE:
Discharge is at system pressure. Drain line should be
anchored.

NOTE:
Condensate may contain oil. Comply with applicable laws
concerning proper disposal.

B.   Separator has a knurled fitting with flexible  drain

tubing attached. Be sure knurled fitting is tightened
by turning it counter-clockwise before operating
dryer.

TO CLOSE

TURN COUNTERCLOCKWISE

Summary of Contents for 9VXRD025

Page 1: ...9VXRD035 9VXRD050 9VXRD075 9VXRD100 9VXRD125 9VXRD150 CONTENTS GENERAL SAFETY INFORMATION 2 RECEIVING MOVING UNPACKING 2 1 0 INSTALLATION 3 2 0 OPERATION 4 3 0 MAINTENANCE 7 SIZING 7 ENGINEERING DATA...

Page 2: ...and was so acknowledged Check for Visible Loss or Damage If this shipment shows evidence of loss or damage at time of delivery to you insist that a notation of this loss or damage be made on the deliv...

Page 3: ...designed to operate in ambients from 45 to 110 F 7 to 43 C E Installations in altitudes above 4500 feet 1370 meters Dryer is adjusted to operate in altitudes up to 4500 feet 1370 meters If dryer is in...

Page 4: ...cool the air with an aftercooler B Air Outlet Connect air outlet to downstream air lines C By pass piping If servicing the dryer without interrupting the air supply is desired piping should include in...

Page 5: ...ed models 110 F 43 C Water cooled models 130 F 54 C E Minimum ambient temperature 45 F 7 C On Off Switch Power On Light Dewpoint Indicator Green 2 2 Start up Energize compressor by positioning the on...

Page 6: ...lly To facilitate service maintenance kits are available 3 0 Maintenance Sizing Determining dryer capacity at actual operating conditions To determine the maximum inlet flow capacity of a dryer at var...

Page 7: ...nal Voltages 115 1 60 Max Min Voltage 127 104 127 104 127 104 127 104 127 104 127 104 Rated Load Amps 3 4 3 9 5 9 7 4 10 3 14 7 Locked Rotor Amps 18 0 22 0 28 0 35 0 48 0 66 3 Minimum Circuit Ampacity...

Page 8: ...l 50 208 230V 60Hz Model 75 208 230V 60 Hz 220 240V 50 Hz Models 100 125 All Voltages Model 150 230V 60 Hz Legend PBS Push button switch 1LT Power on light SR Start Relay CAP Start Capacitor MTR Compr...

Page 9: ...16 1 13 16 1 15 16 1 15 16 1 15 16 2 3 16 2 3 16 E 4 4 5 5 5 5 5 F 15 16 15 16 15 16 15 16 15 16 15 16 15 16 G 1 7 8 1 7 8 1 7 8 1 7 8 1 7 8 1 7 8 1 7 8 H 3 3 3 3 3 3 3 I 1 3 16 1 3 16 1 3 16 1 3 16...

Page 10: ...ture a Power failure b Line disconnect switch open c Blown fuses open breaker d Faulty wiring loose terminals a High or low ambient conditions b Air cooled models Dirty clogged condenser fins obstruct...

Page 11: ...31 735 5 Contactor G5910 134 11 Maintenance Kit 9VXMK4 9VXMK4 9VXMK4 9VXMK5 9VXMK5 9VXMK5 Element GE9 24 GE9 24 GE9 24 GE9 28 GE9 28 GE9 28 Drain G4460 151 10 G4460 151 10 G4460 151 10 G4460 151 10 G4...

Page 12: ...NUFACTURER SHALL NOT BE LIABLE FOR LOSS OR DAMAGE BY REASON OF STRICT LIABILITY IN TORT OR ITS NEGLIGENCE IN WHATEVER MANNER INCLUDING DESIGN MANUFACTURE OR INSPECTION OF THE EQUIPMENT OR ITS FAILURE...

Reviews: