hyst

CAP indicates the elevator maximum capacity. To view the current value press

AL 1 is the load value to trigger Alarm Relay 1. To view the current value press

AL 2 is the load value to trigger Alarm Relay 2. To view the current value press

An internal sounder beeps when an overload alarm is triggered or when the keypad is pressed.

To change the setting, press

and use

To toggle beteween On and OFF.

Op on for turning the display on or off when the li is moving, the door close signal

ac vates. To change the setting, press

and use

To toggle between On and OFF.

The filter value determines the update rate and damping factor. The available settings are:

0 = 0.4sec, 1 = 0.8sec, 2 = 1.2sec, 3 = 1.6sec.

Defines the time from the control signal input is activated and the car load is stored.

Default =2, the available settings are: 0 = 0sec, 1 = 0.5sec, .....7 = 3.5sec.

Defines the value by which the load in the lift has to drop to reset the instrument,

once the alarm has been triggered.

AL 3 is similar to Alarms 1 & 2 but allows negative values to be entered. When editing the

most significant digit, instead of rolling over from 9 to 0 it included the minus sign option.

dLy

FIL

bEEP

5rES

AL 1

AL 2

AL 3

Op on to turn the systems reset func on on or off. Leave OFF during system set up and zero and

load calibra on. Select ON a er calibra on and before entering the li into service.

To change the setting, press

and use

To toggle beteween On and OFF.

Select the required Analog output . Refer to page 4 for available outputs

CAL

SYST

EWS-102 CONTROL UNIT - MULTI ANALOG

SYSTEM SETUP

Select the first menu item.

When a value is displayed, use

to select the digit to

edit selected digit ashes and use

to step through the

values for that digit.

Press

to save a change. The system will revert to the

opera onal display a er approx. 10 seconds. Alterna vely,

return to the opera onal display by pressing

twice

Edi ng Values

To begin the system
setup, press the

and

buttons together.

Enter the system setup menu.

Un l a sensor is connected, the EWS will display

Err6

preven ng access to the system setup and calibra on

menus

To calibrate the EWS 102, a link must be

ed to the

control signal input terminals

Calibra on and set up can be carried out on any oor,

but the EWS 102 must be re-zeroed at the lowest oor

to nalise the Analog output calibra on.

Notes

Use the

bu on to step through the menu items.

Press

to view the menu item

www.garan.co.uk

The system setup menu allows you to set and ad ust various

system parameters.

Naviga on

AL 1

OUT

1

2

Firmware 5.5 Rev 1 s

e

a era i

Summary of Contents for EWS-102

Page 1: ...5sec Defines the value by which the load in the lift has to drop to reset the instrument once the alarm has been triggered AL 3 is similar to Alarms 1 2 but allows negative values to be entered When e...

Page 2: ...www garan co uk EWS 102 CONTROL UNIT C LI R TION ERO Page 2 Firmware 2 5 rev 1 subje a era i www garan co uk...

Page 3: ...www garan co uk EWS 102 CONTROL UNIT C LI R TION LO www garan co uk Page 3 Firmware 2 5 rev 1 subje a era i...

Page 4: ...ion Error Contact aran Sensor Offset Too igh Positive Installation Error Contact aran Sensor Offset Too igh Negative Installation Error Contact aran Trying to calibrate without Control Signal link Sen...

Page 5: ...ES AL 1 AL 2 AL 3 Op on to turn the systems reset func on on or off Leave OFF during system set up and zero and load calibra on Select ON a er calibra on and before entering the li into service To cha...

Page 6: ...Page 2 www garan co uk Firmware 5 5 Rev 1 s e a era i See Note 3 After the EWS 102 calibration and setup has been completed place the the lift at the lowest floor level and re ero following the proce...

Page 7: ...www garan co uk EWS 102 CONTROL UNIT MULTI ANALOG CALI RATION LOAD www garan co uk Page 3 See note 3 to finalise Analog calibration Firmware 5 5 Rev 1 s e a era i...

Page 8: ...5V 0V no load 5V full load Output type 5V 5V no load 0v half load 5V full load Output type 10V 10V no load 0v half load 10V full load Sensor Signal Input Negative Reverse connection of sensor signal l...

Reviews: