e.bloxx A9-1
SPECIFICATIONS
HB_EBLOXX-A9_E_V13.doc
27
Gantner Instruments Test & Measurement GmbH
Output
Function
process-, host controlled
Type of output
Open Collector
Output voltage
max. 30 V
Output current
max. 100 mA
6.4. Communication Interface
Standard
RS 485, 2-wire
Data format
8E1
Protocols
ASCII, Modbus-RTU, Profibus-DP, Local-Bus
Baud rates
ASCII and Modbus-RTU 19.2, 38.4, 57.6, 93.75, 115.2 kbit/s
Profibus-DP
19.2, 93.75, 187.5, 500, 1500 kbit/s
Local-Bus
19.2, 38.4, 57.6, 93.75, 115.2, 187.5, 500, 1500 kbit/s
Connectable devices
up to 32 without repeater
up to 127 with repeater
Galvanic isolation
500 V
6.5. Power Supply
Power supply
10 V to 30 VDC
overvoltage and overload protection
Power consumption
approx. 2.3 W
Influence of voltage
0.001%/V
6.6. Mechanical
Case
Aluminium and ABS
Dimensions (W x H x D)
45 x 90 x 83 mm (1.8 x 3.5 x 3.3 inch), 160 g
and weight
Protective system
IP 20
Mounting
DIN EN-Rail
6.7. Connection
Plug-in screw terminals
wire cross-section up to 1.5 mm²
Rapidbus connector
4-pin plug in ABS-housing
6.8. Environmental Conditions
Operating temperature
-20 °C to +60 °C (-4 °F to +140 °F)
Storage temperature
-30 °C to +85 °C (-22 °F to +185 °F)
Relative humidity
0% to 95% at +50 °C (+122 °F), non-condensing