![Gantner e. Series Manual Download Page 15](http://html1.mh-extra.com/html/gantner/e-series/e-series_manual_3411591015.webp)
e.bloxx A9-1
MOUNTING e.bloxx AND CONNECTING WIRES
HB_EBLOXX-A9_E_V13.doc
13
Gantner Instruments Test & Measurement GmbH
Picture 3.1.
- Power Supply of the e.bloxx A9-1
3.4. Bus Connection
Only the connection of the e.bloxx modules to the bus is described in here. A detailed description of the bus and the
communication of the modules can be found in the Communication Guide of the e.bloxx/e.gate modules.
The e.bloxx modules have an RS-485 bus interface for connection to the serial fieldbus. The bus has to be terminated
on both sides with characteristic impedance. The maximum line length depends on the transmission speed (refer to the
Communication Guide for details) and can never be higher than 1.2 km per bus segment or 4.8 km via a physical bus
string by using 3 repeaters. A maximum of 32 devices are possible with each bus segment and up to 127 devices via a
physical bus string.
Wiring
In general, the e.bloxx is connected to the bus by connecting both signal leads A and B of the incoming bus cable and
A' and B' of the outgoing bus cable together to one terminal on the module (Figure 3.2). Alternatively, the bus can also
be connected by a "stub cable" (Figure 3.3). This guarantees that the bus connection to other modules remains in place,
even if one module has to be exchanged, due to the removable terminal strip.