7100 Series Installation/Operating Manual —
P/N 9000-0447:J 08/28/08
31
Notification Appliance Circuits
Basic System Module (BSM)
1(+)
2(-)
EOL
1 (+)
2 (-)
- +
- +
BSM
CAOM
DOTTED LINES INDICATE CLASS A,
STYLE Z WIRING. REMOVE EOL
FOR CLASS A, STYLE Z
OPERATION
3.3 Notification Appliance Circuits
The 7100 Series provides two (2), 24 VDC Class B,
Style Y notification appliance circuits. Class A, Style Z
operation is accomplished by adding the Class A Option
to the (CAOM) Module. (See Figure 3.3.1)
Wiring Instructions
•
NAC 1 - TB1-1 (+), TB1-2 ( - )
•
NAC 2 - TB1-3 (+), TB1-4 ( - )
(Polarity markings indicate the polarity of the circuit in
alarm condition).
Use U.L. Listed End of Line Resistor EOL-N (47K),
P/N 4700-0512
Circuit Ratings
•
24 VDC regulated
•
Max. alarm load 1.5A/circuit
•
Ground fault test impedance: 20k Ohms
•
18 AWG minimum
•
If synchronization of strobes is required
Figure 3.3.1 Notification Appliance
Circuit Wiring
MDL-FC Synchronization Modules must be connected.
Class B, Style Y operation only
For a list of Gamewell-FCI Approved, UL Listed notification appliances, refer to the
Compatibility
Addendum for Gamewell-FCI Manuals, P/N 9000-0427.
•
Supervised
•
Power-limited
NOTE:
The CAOM module is furnished with the End of Line resistor installed.