Page 13 of 35
Fig.6:
DACT Digital Alarm Communicator Transmitter Module
Fig.7:
PRM City Tie Module
6.4 DIGITIAL ALARM COMMUNICATOR MODULE (Model DACT)
P1
Cable to P8 on the Main Fire
Alarm Board.
Jumper
JW6
on the Main Fire Alarm
Module must be removed if a
DACT
is
installed.
Note that this module cannot be
installed if a
PRM
(Polarity
Reversal/City Tie Module) is used.
Please see the
DACT
Installation
instructions for more information.
6.5 POLARITY REVERSAL and CITY TIE MODULE (MODEL: PRM)
P1
Cable to P8 on the Main Fire
Alarm Module.
JW1
Cut this jumper for Trouble
transmission. When this jumper
is cut and a system trouble
occurs, the designated terminals
will transmit a "zero volts" or
"open" circuit. Please note that
at normal condition, the
terminals polarity is read exactly
as labelled on the circuit board.
Jumper
JW6
on the Main Fire Alarm
Module must be removed if a City Tie
Module is installed.
Note that this module cannot be
installed if a
DACT
module is used.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com