CENTRIC 3x480, User Guide, rel. 1.7
55
Register
Variable name
GET Values
Remarks
235 4x0235 Charger Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
236 4x0236 Charger Power Line 1
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
237 4x0237 Charger Apparent Power line 1
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
238 4x0238 Charger Power factor Line 1
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
239 4x0239 Charger Load level Line 1
%
240 4x0240 Charger Voltage Line 2
×10 V
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
241 4x0241 Charger Current Line 2
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
242 4x0242 Charger Power Line 2
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
243 4x0243 Charger Apparent Power line 2
×10 KVA
Divide the value by 10 for real measurement: 502/10=50.2 Hz
244 4x0244 Charger Power factor Line 2
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
245 4x0245 Charger Load level Line 2
%
246 4x0246 Charger Voltage Line 3
×10 V
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
247 4x0247 Charger Current Line 3
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
248 4x0248 Charger Power Line 3
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
249 4x0249 Charger Apparent Power line 3
×10 KVA
Divide the value by 10 for real measurement: 502/10=50.2 Hz
250 4x0250 Charger Power factor Line 3
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
251 4x0251 Charger Load level Line 3
%
252 4x0252 Output Source
0: Normal
1: On Battery
2: On Bypass
3: Unknown
Unknown state can be shown when the controller can't communicate with the ST/SW
module
253 4x0253 Output Frequency
×10 Hz
Divide the value by 10 for real measurement: 502/10=50.2 Hz
254 4x0254 Output Voltage Line 1
×10 Vac
Divide the value by 10 for real measurement: 2315/10=231.5 Vac
255 4x0255 Output Current Line 1
×10 A
Divide the value by 10 for real measurement: 21/10=2.1 A
256 4x0256 Output Power Line 1
×10 KW
Divide the value by 10 for real measurement: 453/10=45.3 KW
257 4x0257 Output Apparent Power Line 1
×10 KVA
Divide the value by 10 for real measurement: 769/10=76.9 KVA
258 4x0258 Output Power Factor Line 1
0 to 100
Divide the value by 100 for real measurement: 87/100 = 0.87 PF
259 4x0259 Output Load Line 1
%