Version 1, 15 June 2020, 3 of 16
4.1
TECHNICAL DATA
MIXED OUTLET TEMPERATURE
Factory Preset Temperature
(°C)
43.5
Adjustable Temperature Range (°C)
35
– 48
INLET TEMPERATURES
Cold Supply (°C)
Min
5
Max
25
Hot Supply (°C)
Min
60
Max
90
Temperature Differential (between supply and the outlet) for Stable Operation (°C)
Min
10
Nominal Flow Rate (LPM) (Per Graph)
Min
6
DYNAMIC INLET PRESSURES
Hot and Cold Inlet Pressures
Min
20
Max
500
STATIC INLET PRESSURE
Hot and Cold Inlet Pressures (kPa)
Max
1000
INLET PRESSURE RATIO
Maximum Inlet Pressure Ratio for Stable Operation
(Either supply) (Hot ; Cold or Cold : Hot)
6:1
NOTE 1: for optimum operation it is recommended that the hot and cold water supply pressure be balanced to /- 10%
NOTE 2: Notwithstanding the above, compliance with AS/NZS3500 must be maintained.
4.2
FLOW SIZING GRAPH
The Galvin
Engineering CliniMix
®
Thermostatic Mixing Valve is suitable for many applications. The Head-loss
Characteristic for Mixed Outlet Flow rate versus Balanced Inlet Pressure is shown below in Graph below. It is important
that the valve is not oversized for its intended application.
GRAPH
– Head-loss Characteristics
NOTE: To ensure optimum performance the minimum
outlet flow of the TMV during operation should be at
least 6 litres/minute.
It is important that the valve is sized such that the flow
rates from the outlets are not less than those listed
AS/NZS 3500.1
The pipe-work between the TMV and the system must be
sized in accordance with AS/NZS 3500.1 to ensure the
water velocity in the pipe-work is within the allowed limit.
If the TMV is to be installed and operated under unequal
inlet pressures, the lower inlet pressure determines the
outlet flow rate. However, for optimum performance and
stability it is recommended that the TMV be installed
with balanced dynamic inlet pressures (+/- 10%).