Installation and operation manual of the SG(B) buffers 

© All rights reserved - Galmet Sp. z o.o. Sp. K.

4

2. General operating rules

2. General operating rules

2.1. Installation 

-  Buffer tank should be installed in a dry room. The tank cannot be installed in rooms where the ambient temperature may fall below 0°C.
-  The tank should be connected by a qualified installer. Confirmation of installation in the warranty card is required.
-  Due to the design of the tank, it should only be installed in an upright position.
-  Buffer tanks are recommended to be installed close to the main heat source in order to avoid unnecessary heat loss.
-  Buffer tanks can be connected to open and closed systems. The heating system pressure (closed system) must not exceed the maximum operating pressure 

of the tank (0,3 MPa).

-  Buffer tanks used in an open installation should be connected to an open vessel protected in accordance with PN-B02413.
-  Buffer tanks used in closed systems should be protected by a properly selected safety valve with a pressure not higher than the maximum operating 

pressure of the tank (0,3 MPa). The installation should be additionally equipped with an expansion vessel of appropriate capacity.

2.2. Start-up

After connecting the entire central heating system you should:
1.  Fill the heating system with a heating factor.
2.  Check the hydraulic connections for any leaks.
3.  Insulate the pipelines and tank connections.
4.  Bleed the installation.

After completing all the steps, the central heating installation is ready to work. The first heating of the buffer tank should be carried out in the presence of 
the installer in order to correctly check the operation of the whole installation.

Before bleeding the buffer tank, make sure that the heating device is switched off and the heating system is not hot.

Before the first start-up or after a long break in operation, check whether the entire installation is filled with the heating medium.

2.3. Turning off the boiler

In the event of interruption in use and the risk of freezing of the heating medium in the tank, the tank and the entire heating system associated with it 
should be emptied.

Caution!
-  It is prohibited to start the heating circuit if the buffer tank is not filled with heating medium.
-  The buffer tank must not be used if a malfunction of the safety valve is found.
-  It is forbidden to install devices (e.g. shut-off valve, non-return valve, etc. between the tank and the safety valve, or an open expansion vessel (a tee is 

the only exception).

-  It is forbidden to make any unauthorized repairs to the tank.
-  It is not allowed to prevent the water leakage from the safety valve.

Summary of Contents for SG 40

Page 1: ...0 1500 2000 3000 4000 5000 One spiral coil Two spiral coils bivalent With the maximum size spiral coil Without spiral coils Detachable Nondetachable Without insulation Catalogue No Production date QC...

Page 2: ...e SG B 3000 4000 5000 without spiral coils 12 4 8 Technical parameters SG B 3000 4000 5000 without spiral coils 13 4 9 Scheme SG B 200 with one spiral coil 14 4 10 Technical parameters SG B 200 with o...

Page 3: ...out a properly functioning safety valve applies to closed system 3 The company is not responsible for safety valve malfunction caused by incorrect installation of the valve and installation errors 4 D...

Page 4: ...e entire central heating system you should 1 Fill the heating system with a heating factor 2 Check the hydraulic connections for any leaks 3 Insulate the pipelines and tank connections 4 Bleed the ins...

Page 5: ...of the SG B buffers 5 3 Exemplary scheme of the installation 3 Exemplary scheme of the installation ch boiler for solid fuels buffer fireplace open equalising tank floor heating radiator safety valve...

Page 6: ...manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 6 4 Technical specification 4 1 Scheme SG B 40 60 80 100 120 140 wall mounted without spiral coils 460 200 50 GS1 GS2 Gw 1 2 Gw 6 4...

Page 7: ...orking pressure bar 3 3 3 3 3 3 Dimensions CH boiler water connection height GS1 mm 175 175 175 175 175 175 CH boiler water connection height GS2 mm 305 505 690 840 940 1090 Height L mm 480 680 865 10...

Page 8: ...Installation and operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 8 4 Technical specification 4 3 Scheme SG B 200 without spiral coils...

Page 9: ...height GS3 mm 483 Sensorcoverorthermometerconnectionheight GS4 mm 603 CH boiler water connection height GS5 mm 785 Sensorcoverorthermometerconnectionheight GS6 mm 885 CH boiler water connection height...

Page 10: ...Installation and operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 10 4 Technical specification 4 5 Scheme SG B 300 400 500 800 1000 1500 2000 without spiral coils...

Page 11: ...rmometerconnectionheight GS5 mm 980 1015 1180 1020 1240 1640 1480 CH boiler water connection height GS6 mm 1170 1210 1410 1215 1485 1950 1755 Sensorcoverorthermometerconnectionheight GS7 mm 1355 1400...

Page 12: ...operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 12 4 Technical specification 4 7 Scheme SG B 3000 4000 5000 without spiral coils D d L GS11 GS10 GS7 GS6 GS5 0 0 GS8 GS9...

Page 13: ...CH boiler water connection height GS5 mm 425 445 445 Sensorcoverorthermometerconnectionheight GS6 mm 830 790 920 CH boiler water connection height GS7 mm 1045 910 1075 CH boiler water connection heig...

Page 14: ...d operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 14 4 Technical specification 4 9 Scheme SG B 200 with one spiral coil L 00 GS1 GS2 GS3 GS4 GS5 GS6 GS7 GS9 GS12 GS8 GS10...

Page 15: ...tionheight GS4 mm 603 CH boiler water connection height GS5 mm 785 Sensorcoverorthermometerconnectionheight GS6 mm 885 CH boiler water connection height GS7 mm 220 Coil return connection height GS8 mm...

Page 16: ...Installation and operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 16 3 Technical specification 4 11 Scheme SG B 300 400 500 800 1000 1500 2000 with one spiral coil...

Page 17: ...0 1640 1480 CH boiler water connection height GS6 mm 1170 1210 1410 1215 1485 1950 1755 Sensorcoverorthermometerconnectionheight GS7 mm 1355 1400 1640 1410 1730 2260 2025 CH boiler water connection he...

Page 18: ...of the SG B buffers All rights reserved Galmet Sp z o o Sp K 18 4 Technical specification 4 13 Scheme SG B 400 500 800 1000 1500 2000 with two spiral coils 0 GS10 GS13 GS15 L 0 GS1 GS2 GS3 GS4 GS5 GS7...

Page 19: ...mm 1150 1300 1150 1240 1715 1565 CH boiler water connection height GS7 mm 1210 1410 1215 1485 1950 1755 Upper coil feeding connection height GS8 mm 1420 1650 1420 1740 2260 2035 CH boiler water connec...

Page 20: ...d operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 20 4 Technical specification 4 15 Scheme SG B 300 with the maximum size spiral coil SPUST GS1 GS8 GS9 GS10 GS11 GS2 GS3...

Page 21: ...ght GS4 mm 785 Sensorcoverorthermometerconnectionheight GS5 mm 955 Coil feeding connection height GS6 mm 1040 CH boiler water connection height GS7 mm 1165 Heater connection height GS8 mm 310 CH boile...

Page 22: ...and operation manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 22 4 Technical specification 4 17 Scheme SG B 400 with the maximum size spiral coil GS1 GS2 GS3 GS4 GS5 GS6 SPUST GS7...

Page 23: ...ht GS4 mm 865 CH boiler water connection height GS5 mm 1270 Coil feeding connection height GS6 mm 1400 Heater connection height GS7 mm 340 CH boiler water connection height GS8 mm 660 CH boiler water...

Page 24: ...ration manual of the SG B buffers All rights reserved Galmet Sp z o o Sp K 24 4 Technical specification 4 19 Scheme SG B 500 with the maximum size spiral coil GS12 GS11 GS13 GS14 GS1 GS2 GS3 GS4 GS5 G...

Page 25: ...nection height GS6 mm 950 Sensorcoverorthermometerconnectionheight GS7 mm 1015 Sensorcoverorthermometerconnectionheight GS8 mm 1395 CH boiler water connection height GS9 mm 1405 Coil feeding connectio...

Page 26: ...ntifier SG B 200 polyurethane 1 coil SG B 300 polyurethane 1 coil SG B 400 polyurethane 1 coil SG B 500 polyurethane 1 coil SG B 800 detachable 1 coil SG B 1000 detachable 1 coil SG B 1500 detachable...

Page 27: ...irective PED 2014 68 UE The exchangers are intended for storage of neutral mediums demineralized boiler water glycol etc The wall thickness of the jackets and the bottoms as well as the material the e...

Page 28: ...rective PED 2014 68 UE The exchangers are intended for storage of neutral mediums demineralized boiler water glycol etc The wall thickness of the jackets and the bottoms as well as the material the ex...

Page 29: ...tweenthesafetyvalveandtheheater Itisonlyrecommended toassembleathree way adapterinordertoemptytheheater 9 Assembly and activation of the equipment constituting the subject of the guarantee have to be...

Page 30: ...tyofperiodicalcleaningofthetankfromtheaccumulateddeposits 18 15 replacementofconsumablefluids otherthanwater assemblyanddisassemblyofequipmentcoveredbytheherebyguarantee 19 Themethodforrepairshallbesp...

Page 31: ...f repair Service s seal Service s seal Service s seal Service s seal Owner s name and address Owner s name and address Owner s name and address Owner s name and address Owner s signature Owner s signa...

Page 32: ...ory no Date of sale Seller s stamp and signature Warranty coupon 1 Warranty coupon 2 Warranty coupon 3 Warranty coupon 4 Type Type Type Type Factory no Factory no Factory no Factory no Date of sale Da...

Reviews: