background image

15

All copying, even partial, of this manual is strictly forbidden

 RG66012163 - Rev 00

TECHNICAL CHARACTERISTICS

5.1 

RATED TECHNICAL DATA OF WATER CHILLERS

-   Cooling capacity: outdoor air temperature 35°C, water temperature 12°C / 7°C
-   Sound power level measured according to standards ISO 3741 -  ISO 3744 and EN 29614-1
-   Sound pressure level measured at a distance of 10 m and a height of 1�5 m above the ground in a free field (fan side)�
-   The maximum electrical input is the mains electricity that must be available in order for the unit to work�
-   The maximum current absorption refers to the current that will trigger the internal safety devices of the unit� It is the maximum current allowed in the unit� This value may never be exceeded; it must 

be used as a reference for determining the size of the power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�

 MPED-C

007 M 008 M

008

010 M

010

013

015

018

020

024

027 

028 

 Power supply

V-ph-Hz

230-1-50

400-3-50 230-1-50

400-3-50

 Cooling capacity (UNI EN 14511)

kW

6,66

8,35

8,48

9,17

9,18

12,8

14,9

17,5

19,9

24,2

27,9

27,9

 Total power input (UNI EN 14511)

kW

2,40

3,51

3,24

3,75

3,81

4,61

5,56

7,01

7,87

8,55

9,37

9,73

 EER (UNI EN 14511)

2,78

2,38

2,62

2,45

2,41

2,78

2,68

2,50

2,53

2,83

2,98

2,87

 ESEER 

2,96

2,87

3,05

2,92

2,93

3,36

3,29

2,92

2,89

3,15

3,16

3,45

 Maximum power input

kW

3,32

5,28

5,28

7,26

7,81

9,46

11,0

13,7

13,8

13,5

14,4

15,3

 Maximum current absorption 

A

17

11

26

18

33

21

24

26

26

26

28

37

 Starting absorbed current

A

63

49

98

48

97

63

66

76

105

145

145

145

 n° of compressors / circuits 

1/1

1/1

1/1

1/1

1/1

1/1

1/1

1/1

1/1

1/1

1/1

1/1

 Refrigerant charge 

kg

2,0

2,1

2,1

2,9

2,9

4,0

4,1

3,7

4,2

5,8

6,0

7,5

 Low/high pressure switch

bar

2  /  42 2  /  42 2  /  42

2  /  42 2  /  42 2  /  42 2  /  42 2  /  42 2  /  42 2  /  42 2  /  42 2  /  42

 n° of axial fan

1

1

1

1

1

1

1

1

1

1

1

2

 Air flow

m

3

/h

3533

3533

3533

7666

7666

7192

7192

13384 13384 12191 12191 16276

 Fan maximum head

Pa

157

157

157

320

320

386

386

311

311

430

430

240

 Fan net available head

Pa

75

75

75

120

120

120

120

180

180

180

180

180

 Water flow

l/h

1148

1438

1461

1591

1592

2224

2584

3033

3444

4200

4832

4823

 Diameter of hydrualic connections

"

1

1

1

1

1

1

1

1,25

1,25

1,25

1,25

1,25

 Water side pressure drop

kPa

6

6

6

34

34

61

38

53

53

51

37

40

 Available pressure head

kPa

69

67

67

115

115

80

101

126

120

108

116

141

 Water content escluding optionals

dm

3

1,5

1,5

1,5

3,0

3,0

3,0

3,0

4,0

4,0

4,0

4,0

5,5

 Buffer tank

dm

3

20

20

20

30

30

30

30

50

50

50

50

125

 Expansion tank

dm

3

1

1

1

5

5

5

5

5

5

5

5

8

 Height

mm

966

966

966

1247

1247

1247

1247

1565

1565

1565

1565

1988

 Length 

mm

751

751

751

1012

1012

1012

1012

1131

1131

1131

1131

951

 Depth 

mm

758

758

758

1224

1224

1224

1224

1274

1274

1274

1274

1823

 

Inlet + radiated sound power level

dB(A)

74

73

73

75

75

74

74

79

79

78

78

80

 Outlet sound power level

dB(A)

75

75

75

82

82

81

81

84

84

81

81

89

 Inlet + radiated sound power level 
 (LOW NOISE)

dB(A)

70

70

70

70

70

71

71

76

76

75

75

77

 

Inlet + radiated sound pressure level dB(A)

46

45

45

47

47

46

46

51

51

50

50

52

 Outlet sound pressure level

dB(A)

47

47

47

54

54

53

53

56

56

53

53

61

Unit with pump and tank 
transport weight

kg

123

127

127

211

211

216

219

265

281

297

313

427

Unit with pump and full tank 
operating weight

kg

132

136

136

227

227

232

236

301

317

333

350

534

Summary of Contents for PERFORMA MPE Series

Page 1: ...MPE D 7 kW 76 kW R410A eco TECHNICAL MANUAL FOR CHILLERS AND HEAT PUMPS EN Air condensed duct water chillers and heat pumps PERFORMA MPE series DUCTABLE VERSION...

Page 2: ...Performance 20 6 1 Integrated capacities 21 7 Sound level 21 8 Operating limits 22 8 1 Cooling mode 22 8 2 Heating mode 22 8 3 Thermal carrier fluid 22 9 Calculation factor 23 9 1 Change in operating...

Page 3: ...OWS THE FOLLOWING DATA Series and size of the unit Date of manufacture Main technical data Manufacturer The label is applied on the unit usually on the enclosing panels beside the condenser coil IMPOR...

Page 4: ...IE T54 T61 T69 T76 SELF ADAPTIVE The electronic control system allows the setpoint to be adjusted automatically according to the outdoor temperature in order to reduce consumption and broaden the work...

Page 5: ...lly removable fan considerably reduce maintenance work The use of finned block heat exchangers with 8mm diameter pipes reduces pressure drops on the air side thus significantly improving the noise lev...

Page 6: ...hanger 3 Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 9 4 way valve MPED H 10 Thermostatic valve 11 Water saf...

Page 7: ...Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 9 4 way valve MPED H 10 Thermostatic valve 11 Water safety valve...

Page 8: ...3 Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 9 4 way valve MPED H 10 Thermostatic valve 11 Water safety va...

Page 9: ...Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 9 4 way valve MPED H 10 Thermostatic valve 11 Water safety valve...

Page 10: ...3 Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 9 4 way valve MPED H 10 Thermostatic valve 11 Water safety va...

Page 11: ...Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 9 4 way valve MPED H 10 Thermostatic valve 11 Water safety valv...

Page 12: ...er 3 Fans 4 Water differential pressure switch fan housing 5 Automatic air purge valve 6 Expansion vessel fan housing 7 Water tank accessory 8 4 way valve MPED H 9 Thermostatic valve 10 Water safety v...

Page 13: ...tandard initial A Ducted with radial fans D Expansion valve 0 Traditional 0 Electronic A Pump and accessories 0 Absent 0 Pump expansion tank filling tap 1 Dual pump expansion tank filling tap 2 Inerti...

Page 14: ...ement chiller coil wire PDC 4 Control microprocessor 1 BASE microprocessor 1 ADVANCED microprocessor 2 Advanced microprocessor kit GSM 3 Advanced microprocessor clock card 4 ACCESSORIES O Horizontal a...

Page 15: ...76 105 145 145 145 n of compressors circuits 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Refrigerant charge kg 2 0 2 1 2 1 2 9 2 9 4 0 4 1 3 7 4 2 5 8 6 0 7 5 Low high pressure switch bar 2 42 2...

Page 16: ...1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1 Refrigerant charge kg 7 5 7 8 10 8 13 0 15 0 7 8 7 8 10 9 10 9 11 0 11 0 16 0 16 0 Low high pressure switch bar 2 42 2 42 2 42 2 42 2 42 2 42 2 42 2 42 2 42 2 42 2 42...

Page 17: ...2 5 28 5 28 7 26 7 81 9 46 11 0 13 7 13 8 13 5 14 4 15 3 Maximum current absorption A 17 11 26 18 33 21 24 26 26 26 28 37 Starting absorbed current A 63 49 98 48 97 63 66 76 105 145 145 145 n of compr...

Page 18: ...ption A 41 43 47 55 66 50 55 55 58 57 61 69 76 Starting absorbed current A 166 161 183 221 266 103 115 146 156 177 187 202 229 n of compressors circuits 1 1 1 1 1 1 1 1 1 1 2 1 2 1 2 1 2 1 2 1 2 1 2 1...

Page 19: ...condensation and evaporation control which will correspond to the nominal air flow rate BASE CONTROLLER The installer will vary the fan speed in order to measure using a differential pressure gauge be...

Page 20: ...rature Inlet water temperature Outlet water temperature Ethylene glycol percentage default 0 Directivity factor and distance Output data Cooling heating capacity Water flow rate on user side Water pre...

Page 21: ...71 0 77 0 79 5 80 8 78 0 79 1 69 9 86 84 58 56 MPED 010 71 0 77 0 79 5 80 8 78 0 79 1 69 9 86 84 58 56 MPED 013 69 6 75 6 78 1 79 4 76 6 77 7 68 5 85 83 57 55 MPED 015 69 6 75 6 78 1 79 4 76 6 77 7 68...

Page 22: ...series can work with mixtures of water and up to 35 ethylene glycol 8 OPERATING LIMITS The graphs below illustrate the operating limits of MPED in the case of continuous operation in relation to the...

Page 23: ...heating capacity CPA Correction coefficient of electrical input CQw Correction coefficient of water flow rate C pw1 Correction coefficient of pressure drop 9 2 WATER AND GLYCOL MIXTURE Based on the mi...

Page 24: ...12000 p KPa Qw l h MPE 010 013 MPE 015 018 MPE 020 MPE 024 MPE 027 032 MPE 030T 034T 035 MPE 040 040T 045T All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 10 PRESSURE D...

Page 25: ...KPa Qw l h MPE 054 MPE 066 All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 10 PRESSURE DROPS 10 1 PRESSURE DROPS ON THE WATER SIDE The diagram shows the evaporator pres...

Page 26: ...50 00 200 00 250 00 0 60 2 60 4 60 6 60 8 60 10 60 12 60 14 60 16 60 18 60 20 60 MPED 61 T All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 10 PRESSURE DROPS 10 1 PRESSU...

Page 27: ...120 00 140 00 160 00 180 00 200 00 0 60 5 60 10 60 15 60 20 60 25 60 MPED 76 T All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 10 PRESSURE DROPS 10 1 PRESSURE DROPS ON...

Page 28: ...0 8000 10000 12000 p kPa Qw l h MPE 010 028 MPE 032 066 MPE T30 T76 All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 10 PRESSURE DROPS 10 2 PRESSURE DROPS OF Y FILTER Th...

Page 29: ...13 MPE 015 MPE 020 MPE 024 MPE 027 028 032 MPE 030T 034T 035 MPE 040 040T 045T MPE 018 All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 11 AVAILABLE HEAD OF THE UNIT The...

Page 30: ...60 4 60 6 60 8 60 10 60 12 60 14 60 16 60 18 60 MPED 54 T All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 11 AVAILABLE HEAD OF THE UNIT The diagram below shows the ava...

Page 31: ...00 13 00 15 00 17 00 19 00 MPED 69 T All copying even partial of this manual is strictly forbidden RG66012163 Rev 00 11 AVAILABLE HEAD OF THE UNIT The diagram below shows the available head Pu of the...

Page 32: ...en partial of this manual is strictly forbidden RG66012163 Rev 00 11 AVAILABLE HEAD OF THE UNIT The diagram below shows the available head Pu of the unit as a function of the water flow rate Qw assumi...

Page 33: ...ncoming water supply is hooked up to the connection marked Water Inlet Otherwise the evaporator would be exposed to the risk of freezing since the antifreeze thermostat would not be able to perform it...

Page 34: ...ER CIRCUIT MPED EVAPORATOR AND PUMP MPED EVAPORATOR OPTIONAL OPTIONAL LEGEND VS Safety valve EV Evaporator PD Water differential pressure switch MA Water gauge VAS Air bleed hole OPTIONAL ONLY FOR MPE...

Page 35: ...ER TANK OPTIONAL OPTIONAL OPTIONAL ONLY FOR MPED 28 66 30 45T 54 76T RANGE ONLY FOR MPED 10 27 RANGE ONLY FOR MPED 10 27 RANGE NOT AVAILABLE FOR MPED 07 08 NOT AVAILABLE FOR MPED 07 08 LEGEND VS Safet...

Page 36: ...ump on the expansion valve with the ensuing risk of the safety devices being triggered 1 Utility side 2 Storage tank 3 Mixing valve 4 Circulation pump 5 On board de superheater The bulb of the 3 way m...

Page 37: ...r IL A 007M 008 M 008 010 M 010 013 015 018 020 024 027 028 032 3 32 5 28 5 28 7 26 7 81 9 46 11 0 13 7 13 8 13 5 14 4 15 3 17 3 17 0 26 0 11 0 32 9 17 9 21 0 23 6 25 8 25 8 26 1 27 7 37 4 40 7 63 98...

Page 38: ...PED AND PCDS PCD REMOTE CONTROL PANEL NOTE On the terminal block of the electric control panel a voltage of 24V will be present at the 50 24V terminals in the event of an alarm if it is desired to int...

Page 39: ...L DIMENSIONS LEGEND 1 Water in 1 female 2 Water out 1 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply 1 2 male optional tap 5 Drain manifold 1 2 female 6 Power s...

Page 40: ...ALL DIMENSIONS LEGEND 1 Water in 1 female 2 Water out 1 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply 1 2 male optional tap 5 Drain manifold 1 2 female 6 Power...

Page 41: ...ENSIONS LEGEND 1 Water in 1 1 4 female 2 Water out 1 1 4 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply 1 2 male optional tap 5 Drain manifold 1 2 female 6 Powe...

Page 42: ...NK MPED 30 45 T 14 OVERALL DIMENSIONS LEGEND 1 Water in 1 1 4 female 2 Water out 1 1 4 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply 1 2 male optional tap 5 Dr...

Page 43: ...1 Water inlet 2 female 2 Water outlet 2 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply male 5 Water drainage female 6 Power supply 7 Electric control board 8 Fa...

Page 44: ...trictly forbidden RG66012163 Rev 00 14 OVERALL DIMENSIONS LEGEND 1 Water inlet 2 female 2 Water outlet 2 female 3 Safety valve discharge outlet provided with rubber ring holder 4 Water supply male 5 W...

Page 45: ...respectively in the top and front views of the dimensional diagrams The isometric view shows for example the case of ducting on the side panel DUCT DIMENSIONS A mm B mm DUCT DIMENSIONS A mm B mm 007M...

Page 46: ...ondensation while operating in the heating mode MPED water chillers and heat pumps are air cooled units suitable for indoor installation It is necessary to install air intake and outlet ducts that mus...

Page 47: ...RICAL BOX EXCHANGER SIDE HEAT EXCHANGER WATER CONNECTION SIDE EXCHANGER SIDE ELECTRICAL BOX MPED N DAMPERS 04 08 4 10 15 4 18 27 4 28 66 6 30 45 T 6 54 76 T 6 15 1 DAMPERS SITING DAMPERS MPED 54 76T S...

Page 48: ...www galletti it 40010 Bentivoglio BO Via Romagnoli 12 a Tel 051 8908111 Fax 051 8908122 Company UNI EN ISO 9001 and OHSAS 18001 certified...

Reviews: