15
All copying, even partial, of this manual is strictly forbidden
RG66012163 - Rev 00
5
TECHNICAL CHARACTERISTICS
5.1
RATED TECHNICAL DATA OF WATER CHILLERS
- Cooling capacity: outdoor air temperature 35°C, water temperature 12°C / 7°C
- Sound power level measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure level measured at a distance of 10 m and a height of 1�5 m above the ground in a free field (fan side)�
- The maximum electrical input is the mains electricity that must be available in order for the unit to work�
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit� It is the maximum current allowed in the unit� This value may never be exceeded; it must
be used as a reference for determining the size of the power supply line and the related safety devices (refer to the wiring diagram supplied with the units)�
MPED-C
007 M 008 M
008
010 M
010
013
015
018
020
024
027
028
Power supply
V-ph-Hz
230-1-50
400-3-50 230-1-50
400-3-50
Cooling capacity (UNI EN 14511)
kW
6,66
8,35
8,48
9,17
9,18
12,8
14,9
17,5
19,9
24,2
27,9
27,9
Total power input (UNI EN 14511)
kW
2,40
3,51
3,24
3,75
3,81
4,61
5,56
7,01
7,87
8,55
9,37
9,73
EER (UNI EN 14511)
2,78
2,38
2,62
2,45
2,41
2,78
2,68
2,50
2,53
2,83
2,98
2,87
ESEER
2,96
2,87
3,05
2,92
2,93
3,36
3,29
2,92
2,89
3,15
3,16
3,45
Maximum power input
kW
3,32
5,28
5,28
7,26
7,81
9,46
11,0
13,7
13,8
13,5
14,4
15,3
Maximum current absorption
A
17
11
26
18
33
21
24
26
26
26
28
37
Starting absorbed current
A
63
49
98
48
97
63
66
76
105
145
145
145
n° of compressors / circuits
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Refrigerant charge
kg
2,0
2,1
2,1
2,9
2,9
4,0
4,1
3,7
4,2
5,8
6,0
7,5
Low/high pressure switch
bar
2 / 42 2 / 42 2 / 42
2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42 2 / 42
n° of axial fan
1
1
1
1
1
1
1
1
1
1
1
2
Air flow
m
3
/h
3533
3533
3533
7666
7666
7192
7192
13384 13384 12191 12191 16276
Fan maximum head
Pa
157
157
157
320
320
386
386
311
311
430
430
240
Fan net available head
Pa
75
75
75
120
120
120
120
180
180
180
180
180
Water flow
l/h
1148
1438
1461
1591
1592
2224
2584
3033
3444
4200
4832
4823
Diameter of hydrualic connections
"
1
1
1
1
1
1
1
1,25
1,25
1,25
1,25
1,25
Water side pressure drop
kPa
6
6
6
34
34
61
38
53
53
51
37
40
Available pressure head
kPa
69
67
67
115
115
80
101
126
120
108
116
141
Water content escluding optionals
dm
3
1,5
1,5
1,5
3,0
3,0
3,0
3,0
4,0
4,0
4,0
4,0
5,5
Buffer tank
dm
3
20
20
20
30
30
30
30
50
50
50
50
125
Expansion tank
dm
3
1
1
1
5
5
5
5
5
5
5
5
8
Height
mm
966
966
966
1247
1247
1247
1247
1565
1565
1565
1565
1988
Length
mm
751
751
751
1012
1012
1012
1012
1131
1131
1131
1131
951
Depth
mm
758
758
758
1224
1224
1224
1224
1274
1274
1274
1274
1823
Inlet + radiated sound power level
dB(A)
74
73
73
75
75
74
74
79
79
78
78
80
Outlet sound power level
dB(A)
75
75
75
82
82
81
81
84
84
81
81
89
Inlet + radiated sound power level
(LOW NOISE)
dB(A)
70
70
70
70
70
71
71
76
76
75
75
77
Inlet + radiated sound pressure level dB(A)
46
45
45
47
47
46
46
51
51
50
50
52
Outlet sound pressure level
dB(A)
47
47
47
54
54
53
53
56
56
53
53
61
Unit with pump and tank
transport weight
kg
123
127
127
211
211
216
219
265
281
297
313
427
Unit with pump and full tank
operating weight
kg
132
136
136
227
227
232
236
301
317
333
350
534