MPI DC
16
All copying, even partial, of this manual is strictly forbidden.
RG66007970 - Rev 01
6 PeRFORManCeS
6.1
COOlInG CaPaCITIeS MPI DC-h
Tbs
1
Air inlet temperature (dry bulb)
Tw in/out
Water inlet/outlet temperature
PF
Cooling capacity
Pa
Total power input including pump
Tbs
1
20
25
30
35
40
45
Tw in
Tw out
PF
Pa
PF
Pa
PF
Pa
PF
Pa
PF
Pa
PF
Pa
[°C]
[°C]
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
MPI DC 014 h
Rated data at maximum frequency
10
5
15,40
4,10
14,70
4,44
14,00
4,83
13,20
5,26
12,30
5,75
11,30
6,26
11
6
15,90
4,11
15,20
4,46
14,40
4,85
13,60
5,29
12,70
5,77
11,70
6,30
12
7
16,40
4,11
15,70
4,48
14,90
4,87
14,00
5,31
13,10
5,81
12,00
6,33
13
8
16,90
4,12
16,20
4,48
15,40
4,90
14,40
5,34
13,50
5,84
12,50
6,36
14
9
17,50
4,12
16,70
4,50
15,80
4,92
14,90
5,36
13,90
5,86
12,80
6,41
15
10
18,00
4,13
17,20
4,52
16,30
4,93
15,30
5,39
14,30
5,90
13,20
6,43
16
11
18,60
4,14
17,70
4,53
16,80
4,95
15,80
5,42
14,80
5,93
13,70
6,47
17
12
19,20
4,14
18,30
4,54
17,30
4,97
16,30
5,45
15,20
5,95
14,10
6,51
MPI DC 014 h
Rated data at intermediate frequency
10
5
10,40
2,59
9,88
2,80
9,41
3,01
8,91
3,26
8,34
3,53
7,74
3,82
11
6
10,70
2,59
10,20
2,80
9,72
3,02
9,21
3,27
8,63
3,53
8,00
3,83
12
7
11,00
2,59
10,50
2,80
10,00
3,02
9,50
3,27
8,91
3,55
8,27
3,84
13
8
11,40
2,59
10,90
2,80
10,40
3,03
9,81
3,28
9,20
3,56
8,54
3,86
14
9
11,80
2,58
11,20
2,80
10,70
3,03
10,10
3,29
9,51
3,57
8,83
3,87
15
10
12,10
2,58
11,60
2,80
11,10
3,03
10,40
3,29
9,80
3,58
9,12
3,88
16
11
12,50
2,58
12,00
2,80
11,40
3,04
10,80
3,30
10,10
3,59
9,42
3,90
17
12
12,90
2,58
12,40
2,80
11,80
3,04
11,10
3,31
10,40
3,60
9,71
3,92
MPI DC 014 h
Rated data at minimum frequency
10
5
3,94
1,45
3,76
1,54
3,59
1,63
3,40
1,72
3,20
1,83
2,98
1,94
11
6
4,08
1,45
3,90
1,54
3,72
1,63
3,52
1,72
3,31
1,83
3,08
1,94
12
7
4,23
1,44
4,03
1,53
3,85
1,62
3,65
1,72
3,43
1,83
3,20
1,95
13
8
4,38
1,44
4,18
1,53
3,98
1,62
3,78
1,72
3,55
1,83
3,31
1,95
14
9
4,53
1,43
4,33
1,53
4,12
1,62
3,91
1,72
3,67
1,83
3,42
1,95
15
10
4,69
1,43
4,47
1,52
4,27
1,62
4,04
1,72
3,80
1,83
3,54
1,95
16
11
4,85
1,42
4,63
1,52
4,41
1,61
4,18
1,71
3,93
1,83
3,67
1,95
17
12
5,03
1,42
4,79
1,52
4,56
1,61
4,32
1,71
4,06
1,83
3,79
1,95
MPI DC 018 h
Rated data at maximum frequency
10
5
20,00
6,19
19,10
6,74
18,00
7,36
16,80
8,05
15,60
8,82
14,20
9,64
11
6
20,60
6,21
19,60
6,77
18,60
7,40
17,40
8,10
16,10
8,87
14,70
9,72
12
7
21,20
6,24
20,30
6,81
19,10
7,44
17,90
8,16
16,60
8,93
15,20
9,76
13
8
21,90
6,26
20,90
6,84
19,70
7,49
18,40
8,21
17,10
8,99
15,60
9,83
14
9
22,60
6,28
21,40
6,88
20,30
7,54
19,00
8,27
17,50
9,05
16,10
9,91
15
10
23,20
6,31
22,00
6,91
20,90
7,58
19,50
8,32
18,10
9,12
16,60
9,98
16
11
23,90
6,33
22,80
6,94
21,40
7,62
20,10
8,38
18,60
9,18
17,10
10,04
17
12
24,60
6,35
23,40
6,97
22,00
7,68
20,60
8,44
19,20
9,24
17,60
10,10
MPI DC 018 h
Rated data at intermediate frequency
10
5
13,00
3,36
12,50
3,61
11,90
3,91
11,20
4,24
10,50
4,61
9,69
5,01
11
6
13,40
3,36
12,90
3,62
12,30
3,92
11,60
4,26
10,80
4,63
10,00
5,03
12
7
13,90
3,35
13,30
3,62
12,70
3,93
11,90
4,27
11,20
4,65
10,30
5,06
13
8
14,30
3,35
13,70
3,62
13,10
3,94
12,30
4,28
11,50
4,67
10,70
5,08
14
9
14,80
3,34
14,20
3,63
13,50
3,94
12,70
4,30
11,90
4,69
11,00
5,10
15
10
15,30
3,33
14,60
3,63
13,90
3,96
13,10
4,32
12,20
4,70
11,30
5,13
16
11
15,80
3,32
15,10
3,63
14,30
3,96
13,50
4,33
12,60
4,72
11,70
5,15
17
12
16,30
3,31
15,50
3,62
14,70
3,97
13,90
4,34
13,00
4,74
12,10
5,18
MPI DC 018 h
Rated data at minimum frequency
10
5
3,91
1,45
3,73
1,53
3,56
1,62
3,37
1,72
3,18
1,82
2,96
1,93
11
6
4,05
1,44
3,87
1,53
3,69
1,62
3,49
1,71
3,29
1,82
3,06
1,93
12
7
4,20
1,43
4,01
1,53
3,80
1,62
3,62
1,71
3,40
1,82
3,17
1,94
13
8
4,36
1,42
4,15
1,52
3,96
1,61
3,74
1,71
3,52
1,82
3,28
1,94
14
9
4,52
1,41
4,31
1,51
4,09
1,61
3,87
1,71
3,64
1,82
3,39
1,94
15
10
4,69
1,40
4,46
1,50
4,24
1,60
4,01
1,70
3,76
1,82
3,50
1,94
16
11
4,87
1,39
4,63
1,49
4,39
1,59
4,14
1,70
3,88
1,82
3,62
1,94
17
12
5,06
1,37
4,80
1,48
4,54
1,59
4,28
1,70
4,01
1,82
3,74
1,94