LCA
RG66000986 – Rev.00
20
ANTI-RECYCLE TIMER
The function of the timer is to prevent excessively frequent compressor starts and stops.
This device is a function included in the microprocessor control.
It imposes a minimum time lapse of 300 seconds between two successive starts.
Never attempt to change the delay set in the factory: wrong settings could cause serious
damage to the unit.
OIL DIFFERENTIAL PRESSURE SWITCH
LCA units are equipped with spinning scroll compressors; these compressors do not have a lubricant
pump and therefore no oil differential pressure switch is provided.