3E4237 Gallagher T15 Reader | Edition 1 | June 2016

 

Copyright © Gallagher Group Limited

Notes:

• 

Shielded cable may reduce the obtainable cable length.  Shielded cable should be 

grounded at the Controller end only.  

• 

If other cable types are used, operating distances and performance may be reduced 

depending on the cable quality.

• 

HBUS allows up to 20 readers to be connected to a single cable.  Each reader requires at 

least 9 Vdc to function correctly.  The cable length and the number of readers connected 

will have an impact on the voltage at each reader.

Distance between proximity readers

The distance separating any two proximity readers must not be less than 200 mm (8 in) in all directions.

200 mm

When mounting a proximity reader on an internal wall, check that any reader fixed to the other side of 

the wall is not less than 200 mm (8 inches) away.

   

200 mm

Summary of Contents for T15 Mifare Reader Black

Page 1: ...al Installation Note T15 Mifare Reader Black C300470 T15 Mifare Reader White C300471 T15 Multi Tech Reader Black C300480 T15 Multi Tech Reader White C300481 T15 PIV Mifare Reader Black C305470 T15 PIV...

Page 2: ...ss and it should not be relied on as such To the extent permitted by law all express or implied or other representations or warranties in relation to the information are expressly excluded Neither Gal...

Page 3: ...pyright Gallagher Group Limited Contents 1 Introduction 4 2 Before you begin 4 3 Distance between proximity readers 7 4 Installation 8 5 LED indications 10 6 Accessories 10 7 Technical specifications...

Page 4: ...are Classic and 125 KHz cards The reader can be connected as an HBUS Reader or Cardax IV Reader An HBUS Reader uses the HBUS communications protocol to communicate with the Gallagher Controller 6000 A...

Page 5: ...ltage at the reader should be approximately 12 Vdc HBUS cabling topology The HBUS communications protocol is based on the RS485 standard and allows the reader to communicate over a distance of up to 5...

Page 6: ...ble type Cable format HBUS single reader connected using data only in a single cable Cardax IV single reader connected using data only in a single cable HBUS Cardax IV single reader connected using po...

Page 7: ...US allows up to 20 readers to be connected to a single cable Each reader requires at least 9 Vdc to function correctly The cable length and the number of readers connected will have an impact on the v...

Page 8: ...d the two fixing holes 2 Run the building cabling out through the centre hole and through the reader base 3 Secure the base to the mounting surface using the two fixing screws provided It is important...

Page 9: ...Termination Orange HBUS A Green HBUS B Brown CDXIV TX White CDXIV RX Blue HBUS Reader Note To terminate an HBUS Reader connect the Orange HBUS Termination wire to the Green HBUS A wire Cardax IV Reade...

Page 10: ...red 1 Flash Amber Configured to a Controller but reader is not assigned to a door or elevator car On Green or Red Fully configured and functioning normally Green Access mode is Free Red Access mode is...

Page 11: ...Direct sunlight may increase the internal reader temperature above the ambient temperature level Humidity 0 95 non condensing 3 Environmental protection IP68 Impact rating IK07 Unit dimensions Height...

Page 12: ...reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with...

Page 13: ...ion 1 June 2016 Copyright Gallagher Group Limited 9 Mounting dimensions IMPORTANT This picture is not to scale therefore use the measurements provided 44 mm 1 73 139 mm 5 47 13 mm 1 2 diameter hole fo...

Reviews: