Gallagher SMB T11 Installation Notes Download Page 2

Introduction

The Gallagher SMB T11 Reader can be configured as an arming reader or access reader.  
The reader allows users to arm, disarm, or request access at a locked door with a smartphone 
(via Bluetooth

®

 or NFC) or a Gallagher SMB Key Tag.

Connections

The HBUS communications protocol allows a single reader to communicate over a distance 
of up to 500 m (1640 ft) from the controller, when using data only in a single CAT5E cable. 
Cabling should be a minimum size of 0.2 mm

2

 (24 AWG). The cabling between HBUS devices 

should be done in a “daisy chain” topology, (i.e. a "T" or "Star" topology should not be used 
between devices).

Connect the reader tail to the building cable. If the reader is the last device on the run, 
terminate the reader by connecting the Orange wire to the Green wire.

A
B
-
+

Controller

HBUS A
HBUS B
Negative
Positive
HBUS Termination

Not used
Not used

Green

Brown

Black

Red

Orange

White

Blue

Reader tail

Building 

cable

RS485 

2

Distance between readers

The distance separating any two readers must not be less than 200 mm (8 inches) in all 
directions. When mounting the reader on an internal wall, check that any reader fixed to the 
other side of the wall is not less than 200 mm (8 inches) away.

200 mm