Gallagher 3E3618 i Series Energizer User Manual
37
English
USING YOUR FENCE MONITOR
Con
fi
rm Fence Monitor is working by checking the zone indicator is displayed on the
Energizer Controller.
Note:
If the zone is not displayed on the Energizer Controller, refer to
Troubleshoo ng
(p. 42).
Viewing Zone Information
View the fence zone performance by pressing the naviga on bu ons (< or >) un l the
zone indica on arrow is highligh ng the desired fence zone (1 - 6). The fence zones
output voltage and alarm informa on is displayed in the same way as the Energizer
output voltage and alarm informa on.
Changing Zones
To change an exis ng fence zone number to another zone.
1.
Put the Energizer into Standby mode (
).
2.
Remove the cover.
3.
Set orange dial to the required zone.
4.
Replace the cover.
5.
Turn the Energizer on.
Both the old and new zone numbers will be displayed on the Energizer
Controller.
Important:
If you do not delete the old zone number, and subsequently try to display
the ac vity for this zone on your Energizer Controller, it will display Er 21.
Deleting an Unused Zone
To delete a zone from the Energizer Controller.
1.
Press the Se ngs bu on (
).
2.
Using the arrow keys, scroll to the unwanted zone number.
3.
Hold down the + and - bu ons for 6 seconds.
Zone 1 connected