635-SERIES HARDWARE M ANUAL
Chapter-Page
2-78
10.8 Field Wiring 635-DRM Remote Door Module to the 635 DSI Multidrop
Figure 60 – Wiring a 635-DRM (for Remote Door Modules) to a 635-DSI Board:
The DSI BOARD is shown
component-side up
(typically, it installs component-side down) – keep this in mind when
you are landing wires. When board is facing down, Terminal “A” is next to the LED. Section-1 is closest to the power
wiring harness in the controller. See Step-4 of this Chapter-2.
DSI to Relay Board (3-wire):
635-DSI
Relay Brd
A
TR +
B
TR -
GND
GND
Ground the shield at one
end of segment
Daisy-chain Relay Boards:
Relay Brd
Relay Brd
TR +
TR +
TR -
TR -
GND
GND
Ground the shield at one
end of segment
MAX DOORS VS. BOARDS:
Supports up to
16 DRM boards
per DSI Section
(up to 16 DOORS per section)
Note you can have 1 or 2 doors
attached to a DRM so this will
affect the number of DRMs you
need.
See instructions that come with
the Remote Door Module.