GAI-Tronics DEX-103 Manual Download Page 8

 

Pub.: 42004-692L2C 

M

ODEL 

DEX-103

 AND 

DEX-203

 

D

RILLER

I

NTERCOM 

S

TATIONS

 

Page 7 of 13 

f:\standard ioms - current release\42004 instr. manuals\42004-692l2c.doc 
11/10

 

Power 

A separate power feed is recommended for stations in Div. 1 areas so that the stations can be de-energized 
for maintenance without disrupting the power supply to the other equipment in the Div. 1 area.  Refer to 
Figure 4 and Figure 5 for wiring details.  Remove the termination enclosure cover and pull all wiring into 
the termination enclosure.  Terminal block TB2 is provided for connection of power to the station.  
Terminate all conductor ends using #6-32 screws lugs. 

Model DEX-203 

Terminate the 120–240 V ac 50/60 Hz feed on TB2.  This terminal block can also be used to connect 
120–240 V ac 50/60 Hz to the next station.  The maximum current of the ac feed shall not exceed 20 
amperes.  Refer to Figure 5 for more details. 

Model DEX-103 

Refer to Figure 4.  Terminate the 24 V dc feed on TB2.  This terminal block can also be used to connect 
24 V dc to the next station.  The maximum current of the dc feed shall not exceed 20 amperes.  Power 
must be supplied by an isolated 24 V dc power source.  Additional power feeds may be required to 
increase the system distance and/or the number of stations. 

N

OTE

:

  Isolated dc power sources must be used for this installation.  The 24 V dc source should be 

located as close to the system center as possible. 

Grounding the negative side of the power source at one point is recommended to ensure hum and noise-
free operation.  Noise present on dc power lines can negatively affect station operation.  Therefore, noise 
should be limited to 10 mV or less. 

When installing this equipment, the power cable length is an important consideration.  Refer to Table 1 
for the recommended wire sizing details and the maximum cable lengths.  This table is a guideline that is 
useful in most applications; however, the installer must take into consideration any parameters specific to 
their application. 

Table 1. Maximum Distance between 

Driller’s Intercom Stations (in meters)* (DC) 

# of 

Wire Size (mm

2

Stations 

4.0 

2.5 

1.5 

1.0 

276.15 173.74 109.12  68.58 

92.05 57.91 36.27 22.86 

46.02 28.96 17.98 11.28 

27.43 17.37 10.67 ------- 

18.29 11.58 ------- ------- 

13.11 8.23 ------- ------- 

9.75  ------- ------- ------- 

7.62  ------- ------- ------- 

*This chart is based on the following 
parameters: 

1.

 

V(max) = 27 V 

2.

 

V(min) = 21 V 

3.

 

Cable temperature rating = 90º C 

4.

 

The American Wire Gauge 
resistance table 

For V(max) of 24 V, multiply the 
distance shown by a factor of 0.47. 

Summary of Contents for DEX-103

Page 1: ...N T E N T S Confidentiality Notice 1 General Information 1 Product Overview 1 System Requirements and Limitations 1 Features and Functions 2 Available Models 2 Description of Major Components 2 Insta...

Page 2: ...ing platforms especially in hazardous areas It provides all call group call and point to point communications and is available in digital and analog versions The enclosure is rated IP56 and is factory...

Page 3: ...ac ATEX Description of Major Components The Driller s Intercom stations consist of a factory sealed enclosure top and a termination enclosure bottom Refer to Figure 1 for details The factory sealed co...

Page 4: ...e applying power verify that the bolts on the factory sealed section of the station are set at 30 ft lbs This station has a highly sensitive microphone that allows the user to communicate at a distanc...

Page 5: ...Pub 42004 692L2C MODEL DEX 103 AND DEX 203 DRILLER S INTERCOM STATIONS Page 4 of 13 f standard ioms current release 42004 instr manuals 42004 692l2c doc 11 10 Figure 2 Driller s Intercom Outline...

Page 6: ...Securely fasten the factory sealed and termination enclosures to the mounting location using steel mounting bolts and washers or washer head bolts hardware not included Conduit Installation Install t...

Page 7: ...nclosure Make all connections as described below NOTE All field wiring is to be completed in the termination enclosure bottom enclosure only NOTE Consult the National Electrical Codes and local codes...

Page 8: ...ated 24 V dc power source Additional power feeds may be required to increase the system distance and or the number of stations NOTE Isolated dc power sources must be used for this installation The 24...

Page 9: ...mination of a 2 conductor twisted pair cable on system terminals A and B only Analog stations require termination of a 4 conductor twisted pair cable A B twist C D twist on system terminals A D Refer...

Page 10: ...rd ioms current release 42004 instr manuals 42004 692l2c doc 11 10 System Interconnection Refer to Figure 6 for a typical system wiring diagram Consult the central switch manual for further details on...

Page 11: ...can be activated for a variety of conditions Refer to the Attendant Contacts section of the Central Switch manual for details 3 Depress and hold the T button or the footswitch and speak into the micro...

Page 12: ...decreased Increase the volume by simultaneously depressing the V and B buttons Decrease the volume by simultaneously depressing the V and C buttons The volume level setting range is between 0 and 9 an...

Page 13: ...ion Refer to the Volume Configuration section of the Central Manual for details High speaker volume Decrease the actual and or maximum volume settings in the configuration Refer to the Volume Configur...

Page 14: ...amplifier Frequency response 200 4 000 Hz 3 dB ref 1 kHz Speaker amplifier Output Class AB 18 watts min into 8 ohms with nominal supply voltage Frequency response 200 10 000 Hz 3 dB ref 1 kHz Distort...

Page 15: ...of the Contractor s personnel from the work site Re performance of services shall be Buyer s sole and exclusive remedy and in no event shall GAI Tronics warranty obligations with respect to services e...

Reviews: