30
•
Prior to installation, always follow the
instructions and warnings in the chapter
entitled ”Safety instructions”!
Exhaust-air mode
•
The exhaust air is conveyed upwards via a
ventilation shaft or directly through the outer
wall to the exterior.
Note: The exhaust air must not be conveyed into a
functioning smoke or exhaust gas flue or into a
shaft which is used to ventilate
installation rooms which contain heating
appliances.
•
Before conveying the exhaust air into a non-
functioning smoke or exhaust gas flue, obtain
the consent of the appropriate heating
engineer.
•
Discharge exhaust air in accordance with the
official and statutory regulations (e.g. regional
building laws).
•
If the exhaust air is conveyed through the outer
wall, a telescopic wall box should be used.
To ensure optimum performance, the extractor
hood requires:
–
a short, straight exhaust air pipe and
–
the largest possible pipe diameter.
•
If pipe bends cannot be avoided, ensure the
largest possible radii.
Note: If long, rough exhaust air pipes, a lot of pipe
bends or pipe diameters less than 150 mm are
used, the air capacity will be less than optimum and
there will be an increase in noise.
•
Use only pipes or hoses made of non-
combustible material for installation of the
exhaust air duct.
•
The manufacturer of the extractor hoods is not
responsible for complaints which can be
attributed to planning and design of the
pipework.
Connecting pipes
•
The diameter of the exhaust air pipes should
not be less than 150 mm.
•
Round pipes:
We recommend an inner diameter of 150 mm,
however at least 120 mm.
•
Flat ducts must have the same inner cross-
section as round pipes.
There should be no sharp bends.
Ø 150 mm approx. 177 cm
2
Ø 120 mm approx. 113 cm
2
•
If pipe diameters differ:
Use sealing strips.
Connection of 150 mm ø exhaust air pipe
(recommended size)
•
Attach exhaust air pipe
directly to the air-pipe
connector and seal
appropriately. If using an
aluminium pipe, smooth the
connection area beforehand.
Connection of 120 mm ø exhaust air pipe
•
Attach reducing connector
directly to the air-pipe
connector.
•
Attach exhaust air pipe to the
reducing connector.
•
Seal both joints appropriately.
Installation instructions
Summary of Contents for AW 221190CN
Page 1: ...AW 221190CN Gaggenau zh en Operating and installation instructions...
Page 2: ...2 1 Fig 1 GAS 1 ELECTRO zh 03 18 en page 19 34...
Page 3: ...3 4 4 4 5 5 5 6 7 7 8 8 8 9 11 12 12 12 13 14 14 15 16 16 17 18...
Page 4: ...4 2002 96 EC WEEE F 1 E FD...
Page 5: ...5...
Page 6: ...6 4 Pa 0 04 mbar Technische Regeln Gasinstallation TRGI 50 mm 2 15 1 5 kW 2...
Page 7: ...7 550 mm 1 650 mm 1...
Page 8: ...8 min 126 mm min 580 mm max 1 445 mm min 170 mm 170 mm...
Page 9: ...9 1 2 3 Int 0 Int 2 1 2 3 Int 2 2 0 0 0...
Page 10: ...10 Int 1 2 3 3 4 2 Int 2 1 2 3 Int 10 10 5 0 1 2 3 0 F 30 F F...
Page 11: ...11 1 2...
Page 12: ...12 1 2 3 1 2 2 1 2 3 4...
Page 13: ...13 1 2 3 4 1 2 3 4 5...
Page 14: ...14 150 mm 150 mm 150 mm 120 mm 150 mm 177 cm2 120 mm 113 cm2 150 mm 120 mm...
Page 15: ...15 3 mm LS 1 30 m EC...
Page 16: ...16 Poroton 40 kg 1 2 3 2x 8 mm 2x 8 mm 4 5 3 Nm...
Page 17: ...17 1 1 2 2 3 3 1 2 3 4 5...
Page 18: ...GB 29539 2013...
Page 34: ...GB 29539 2013...
Page 35: ...35 AD220182 AD220110 AD220312 AD220322 AD221312 AD221322...