![FUZRR ES3001 Manual Download Page 5](http://html1.mh-extra.com/html/fuzrr/es3001/es3001_manual_2352531005.webp)
- 4 -
Grounding
Voltage
AC 0.00
~
100.0V
±
2%rdg
±
3dgt
0.01V
Remark
:
1. Reference conditions: accuracy with Rh Rs < 100
Ω。
Working conditions:Rh max
=
3k
Ω
+100R
<
50k
Ω;
Rs max
=
3k
Ω
+100R
<
50k
Ω
2.Depends on the measurement accuracy of R,
π
=3.14, a:1 m
~
100m
;
IV
.
Technical Specifications
Function
Two three four-wire measure grounding resistance, soil
resistivity;
Ground voltage, AC voltage measurement
Ambient
temperature and
humidity
23
℃±
5
℃,
below 75%rh
Power
DC 6V 4.5Ah lead-acid battery lasts more than 100 hours
standby
Interference
voltage
<20V (should be avoided)
Interference
current
<2A (should be avoided)
Measure R
electrode
spacing
a
>
5d
Measured
electrode
spacing
a
>
20h
Auxiliary ground
resistance
Reference condition <100
Ω
, working condition <5k
Ω
Range
Grounding resistance: 0.00
Ω~
30.00k
Ω
Soil resistivity: 0.00
Ω
m
~
9999k
Ω
m
Grounding voltage: 0.00V
~
100.0V
measurement mode
Precise four-wire
、
three-wire measurement, simple
two-wire measurement
Measurement
methods
Grounding resistance: rated current change pole method
Soil resistivity: four-pole method
Ground Voltage: Average Rectification(between S-ES
interface)
Test frequency
128Hz
Short circuit
test current
> 20mA (Sine Wave)
Summary of Contents for ES3001