User's Manual
FDC-9200Self-Tune Fuzzy / PIDProcess Temperature Controller
Page 1: ...User s Manual FDC 9200 Self Tune Fuzzy PID Process Temperature Controller...
Page 2: ...although PID control has been used and proved to be an efficient controlling method by many industries yet the PID is difficult to deal with some sophisticated systems such as second order systems lon...
Page 3: ...Band Reset Integral Rate Derivative Ramp Rate Dwell ON OFF Cycle Time Control Action POWER Rating Consumption ENVIRONMENTAL PHYSICAL Safety Protection EMC Emmission EMC Immunity Operating Temperature...
Page 4: ...larity is observed throughout Joints in the cable should be avoided if possible The colour codes used on the thermocouple extension leads are shown in Table 4 1 4 4 5 Relay Output Direct Drive Figure...
Page 5: ...C 3 Silicon Rubber buttons For ease of control set up and setpoint adjustment Control Output Setpoint Value Alarm Outputs Process Value 3 5 7 4 6 8 or or Alarm 2 Control Output 2 Alarm1 Output Control...
Page 6: ...Hold Function Dwell Timer ON as Time Out No Special Function Alarm with Latch Function Alarm with Latch Hold Function Dwell Timer OFF as Time Out Deviation High Alarm Full Scale High Alarm Full Scale...
Page 7: ...compensatio Adjust the drift compensation code 6 6 6 6 count Select a proper status for Output 1 Output 1 ON Output 1 OFF Select Lock or F ree for the Security Level 0 Protect Lock all the Level 0 pa...
Page 8: ...be added to the process value so that the process value will be read with minimum error For those process with bad circulation may use this parameter to compensate the temperature difference between...
Page 9: ...r that parameter by using up key or down key Finally press and hold 3 2 seconds or longer now the new level value is entered If the level value is unchanged the above operation for entering can be omi...
Page 10: ...is set parameters TI TD and CCT will have no effect on the system nor can the manual mode and the auto tune program be executed PV Time D action Perfect TD too high TD too low SP PV Time Time P action...
Page 11: ...e to be used An error message will be shown in the display The manual control is used during Teaching the process The controller fails The manual control is an open loop control The process may rise t...
Page 12: ...enabled by configuring the alarm 1 to act as a dwell timer If A1SF is set to time out on the alarm 1 relay will now operate as a timer contact with the contact being opened on initial start up The ti...
Page 13: ...procedure connect a thermocouple to terminal 13 and 14 observing polarity and select a correct INPT for the thermocouple Switch the power on and let the controller to be powered for at least 30 minut...
Page 14: ...Control abnormal or operation incorrect Check and replace Read the operation procedure carefully Overflow error data out of range during execution of software program Wrong sensor or thermocouple typ...
Page 15: ...ermocouple type wrong input mode selected Analog portion of A D converter defective Check sensor or thermocouple type and if proper input mode was selected Replace related components or board Reversed...
Page 16: ...User s Manual FDC 9200 Process Temperature Controller 7524 West 98th Place Bridgeview IL 60455 Phone 888 751 5444 Fax 888 307 8014...