Futek TFF Series Manual Download Page 10

TFF Torque Sensor Family Manual

10

Sensor Solution Source

Load · Torque · Pressure · Multi-Axis · Calibration · Instruments · Software

www.futek.com

Troubleshooting

When troubleshooting, we recommend that the sensor be removed from any fixtures . In order to confirm that that sensor 
is operating correctly, we suggest placing the sensor on a firm surface, and to apply a known load .  

We also recommend using a volt meter with a clean power supply to confirm the sensor is operating correctly .

SYMPTOM

POSSIBLE CAUSE

CHECK

REPAIRABILITY

High zero output   

•  Sensor is under preload

•  Sensor has been overloaded from too 

much load, off axis load, or moment .   

•  Fixtures or bolting stress for causes of 

pre-load .

•  Loading and support placement for off 

axis loads .

•  Avoid excessive moments during 

installation .

•  Overload shift would not be repairable . 

•  If zero offset is stable it may be 

possible to use sensor by use of Tare 
or subtracting zero from sequential 
readings .   

Non-responsive 
zero output   

•  Sensor or instrument is not powered .

•  Sensor is not properly connected .

•  Load is not displaced properly onto 

sensor .

•  Sensor is not supported correctly and 

not allowing deflection to occur to 
measure load .

•  Internal disconnect or short .

•  Power and wiring to sensor and instru-

ment .

•  Sensor bridge resistance for possible 

opens or shorts .

•  Perform continuity test on cable .

•  Load is placed correctly on sensor 

loading surface .

•  Sensor loading surface is not obstruct-

ed or supported and able to flex under 
load .

•  Sensor support is not giving while 

sensor is loaded .   

•  Internal disconnections or shorts would 

not be available for repair .

•  Sensor cable repair may be available 

if disconnect or short is not too close 
to sensor .   

Non-responsive 
high output   

•  Sensor is disconnected from  

instrument .

•  An opening has occurred in sensor or 

cable connection .

•  Sensor has been overloaded and de-

formed causing permanent high stress 
on internal gauges .

•  Fixture, applied load, or mounting is 

causing a high pre-load on sensor .   

•  Power and wiring to sensor and instru-

ment .

•  Sensor bridge resistance for possible 

opens or shorts .

•  Perform continuity check on cable .

•  Sensor zero output to see if sensor 

returns to zero or has a high zero load 
output due to overloading .

•  Remove load and loosen mounting 

bolts or fixtures to check if sensor is 
being preloaded .

•  Overload shift would not be repairable .

•  Internal disconnections or shorts would 

not be available for repair .

•  Sensor cable repair may be available 

if disconnect or short is not too close 
to sensor .   

Incorrect output for 
applied load   

•  Load is not applied correctly to sensor 

loading surface or is off axis .

•  Fixtures are not secure or obstruct 

loading .

•  Sensor loading surface is not able to 

deflect with applied load .

•  Sensor support is not ridged and firm .

•  Incorrect sensor output is utilized .   

•  Placement of load on sensor .

•  Fixtures are not impeding ability to 

load .

•  Support surface is not giving with 

applied load .

•  Calibration verified outputs are being 

used .   

•  Recalibration is available for confirma-

tion of sensor performance .   

Summary of Contents for TFF Series

Page 1: ...Sensor Solutions Source Load Torque Pressure Multi Axis Calibration Instruments Software www futek com TFF Series Torque Sensor Family Manual...

Page 2: ...on Instruments Software www futek com Table of Contents Key Features 3 Mechanical Installation 4 Mounting and Installation 5 Maximum Installation Torque 6 Cable Care and Routing 7 Electrical Installat...

Page 3: ...00 to 500 in lb capacities The standard TFF line can be modified or customized to meet your requirements Contact FUTEK s application team for further information The TFF series features a through hole...

Page 4: ...th overload protection wire cut gaps if exposed should be regularly cleaned to maintain proper deflection path 1 Do not pull on or carry sensor by cable 2 Monitor sensor output for effects on zero out...

Page 5: ...d Installation Refer to the sensor spec sheet for information on proper torque sensor orientation for best performance and to limit cable influence Measurements are called out on the sensor spec sheet...

Page 6: ...n oz 15 20 100 in lb 25 30 200 in lb 25 30 500 in lb 25 30 TFF500 100 in lb 5 10 TFF600 2000 in lb 150 200 10000 in lb 150 200 Maximum moments and off axis loading Use extraneous load information to d...

Page 7: ...iption page 1 Avoid stress and movement on cable to avoid damage 2 Properly secure sensor cable to limit cable movement influence 3 Avoid bending the strain relief Bends in the cable should not exceed...

Page 8: ...XXX Excitation Red Signal Black Signal Green Voltage Output Green Excitation White WC3 Bridge Sensor XXX WC6 Bridge Sensor XXX Power Supply Red Current Output Green Power Supply Red Ground Black WC5 B...

Page 9: ...futek com calibrationData aspx SHUNT A shunt is an external resistance applied across two points on the load cell s Wheatstone bridge to generate a known fixed output from the sensor Shunt results can...

Page 10: ...face is not obstruct ed or supported and able to flex under load Sensor support is not giving while sensor is loaded Internal disconnections or shorts would not be available for repair Sensor cable re...

Page 11: ...able or noisy Sensor is exposed to temperature change Sensor support is not rigid and firm Sensor exposed to liquid or humidity Stability of power supply and noise levels Fixtures for stability For te...

Page 12: ...usage Calibration data may be available online at http www futek com calibrationData aspx To send in your sensor or system for recalibration visit our FUTEK calibration web page at http www futek com...

Reviews: