6 Product Specifications
2022-06-25
56
Category
Specifications
⚫
Maximum change rate: 20%/h
Air volume
≥ 110 cubic feet per minute (CFM)
Operating altitude
≤3050m
⚫
When the server configuration complies with ASHRAE
Classes A1 and A2 and the altitude is above 900 m
(2952.76 ft), the highest operating temperature decreases by
1°C (1.8°F) for every increase of 300 m (984.25 ft).
⚫
HDDs cannot be used at an altitude of over 3050 m
(10006.44 ft).
Corrosive gaseous
contaminant
Maximum corrosion product thickness growth rate:
⚫
Copper corrosion rate test: 300 Å/month (meeting level G1
requirements of the ANSI/ISA-71.04-2013 standard on
gaseous corrosion)
⚫
Silver corrosion rate test: 200 Å/month
Particle contaminant
⚫
The equipment room environment meets the requirements
of ISO 14664-1 Class 8.
⚫
There is no explosive, conductive, magnetic, or corrosive
dust in the equipment room.
NOTE
It is recommended that the particulate pollution in the equipment room
be monitored by a professional agency.
Acoustic noise
The declared A-weighted sound power levels (LWAd) and
declared average bystander position A-weighted sound
pressure levels (LpAm) listed are measured at 23°C (73.4°F) in
accordance with ISO 7779 (ECMA 74) and reported in
accordance with ISO 9296 (ECMA 109).
⚫
Idle:
−
LWAd: 6.7 Bels
−
LpAm: 52.9 dBA
⚫
Operating:
−
LWAd: 6.9 Bels
−
LpAm: 55.6 dBA
NOTE
The noise generated during operation varies depending on the server
configuration, load, and ambient temperature.
SSDs and HDDs (including NL-SAS, SAS, and SATA) cannot be preserved for a long time in the
power-off state. Data may be lost or faults may occur if the preservation duration exceeds the specified
maximum duration. When drives are preserved under the storage temperature and humidity specified in
the preceding table, the following preservation time is recommended:
⚫
Maximum preservation duration of SSDs:
⚫
12 months in power-off state without data stored