7
DIP 1, 2, & 3 and the Delay Adjustment
DIP Switch positions 1, 2 and 3 are used to define the time delay or
“dwell” time that is imposed between activating/deactivating consecu-
tive devices within a chain of sequencers. Miniports will activate their
outlet as soon as an activation message or signal has been received, but
impose a delay (defined by the settings of DIP 1, 2 & 3) when forwarding
the activation message to the next downstream device. When activating,
the delay countdown starts after the outlet has been activated. When
deactivating, the delay occurs prior to deactivating the outlet.
DIP 1
= ON adds 1 to the minute maximum time delay
DIP 2
= ON adds 2 minutes
DIP 3
= ON adds 4 minutes.
Note: The DIP switch settings are cumulative, thus if all three DIP
switches are in the ON position, the maximum allowable time delay will
be 7 minutes, i.e. 1min+2min+4min=7min. The factory default setting
is DIP 1 ON or UP, and DIP 2 and 3 are OFF or DOWN. You can set these
switches in any position you like to achieve your preferred time delay
1 2 3 4 5 6 7 8 9
ON
DLY
ADJ
ON
OFF
DIP SWITCH DEFAULT SETTING
-
Switches are factory pre-set as shown
below. Switches
1, 4, 8
, and
9
are up
(ON) position.
NOTE:
The DIP switch
ON / OFF settings are
indicated as shown
below throughout
this manual.
1 2 3 4 5 6 7 8 9
C US
BYPASS
DLY
ADJ
GND
ON
MOM
MNT
PRI
SEC
EVS ON
EVS OFF
6
7
8
9
1M
2M
4M
N.O.
N.C.
12V ON
12V OFF
1 2
3
4
5
Bypass Switch
The BYPASS push button switch is located on the side panel to the right
of the DIP Switch. A hole in the security cover provides access to the
BYPASS switch even when the security cover is installed.
The BYPASS switch has a dual purpose:
The BYPASS switch is provided to allow a layperson to activate the outlets
if the external control system is either inaccessible or commanding the
outputs to an OFF state. It should be noted that the FORCE OFF and EVS
conditions have priority over the BYPASS switch and if either of these
conditions are true, the outlets will be deactivated regardless of the posi-
tion of the BYPASS switch. The BYPASS switch operates in a push on/
push off mode and latches either on or off. If the switch is pushed on,
the outlet will remain powered until the switch is pressed a second time
and latches in the off state.
The BYPASS switch is also used to clear the FORCE OFF error. If the unit
is in FORCE OFF mode, and the conditions at the FORCE OFF inputs that
spawned the FORCE OFF error have been removed, the user can use
the BYPASS switch to clear the FORCE OFF error by quickly toggling the
BYPASS switch ON/OFF.
DIP Switch and Delay Adjustment
The DIP Switch is found near the center of the side panel, under the
Security Cover. You can access the DIP switch by removing the security
cover screw using a small Philips screwdriver. The DIP Switch is used to
set various options. It is also used in combination with the DLY ADJ pot to
the ON/OFF delay.
Side Panel Overview
Potentiometer
DIP Switches
Bypass Switch
1,
2,
3
1M
1 2 3
4 5
2M 4M
N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7 8 9
1 2 3
4 5 6 7 8 9
4
1M
1 2 3
4
5
2M 4M
N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7 8 9
1 2 3
4
5 6 7 8 9
5,
6
1M
1 2 3
4
5
2M 4M N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6
7 8 9
1 2 3
4
5 6
7 8 9
7
1M
1 2 3
4 5
2M 4M N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6
7
8 9
1 2 3
4 5 6
7
8 9
8
1M
1 2 3
4 5
2M 4M N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7
8
9
1 2 3 4 5 6 7
8
9
9
1M
1 2 3
4 5
2M 4M N.O.
N.C.
12V ON
12V OFF
GND
ON
MOM
MNT
PRI
SEC
EVS AUTO
MANUAL
6 7 8
9
1 2 3
4 5 6
7 8
9
FACTORY DEFAULT SETTING
DIP 1
DIP 2
DIP 3
Maximum Time Delay
OFF
OFF
OFF
10 Seconds
ON
OFF
OFF
1 Minute
OFF
ON
ON
2 Minute
ON
ON
OFF
3 Minute
OFF
OFF
ON
4 Minute
ON
OFF
ON
5 Minute
OFF
ON
ON
6 Minute
ON
ON
ON
7 Minute
Default DIP Switch Settings