background image

A R - 1 2 2 0     A C   L I N E   V O L T A G E   R E G U L A T O R

the equipment, see fi gure 1.

The AR-1220 has twelve 20A outlets on the back, 

and two 15A outlets on the front. All are functionally 

interchangeable. The outlets are regulated, spike 

suppressed, and fi ltered against FIR with a 3 pole 

fi lter, making the unit a full function power condition-

er. There are no controls except an on off breaker 

switch. (The AR-1220J also has an output voltage 

selector switch.)

Limitations: These Line Voltage Regul ators are for 

use with AC voltage only. DC voltages should never 

be applied to them. Also, they do not change or 

regulate line frequency. The output frequency will 

always be the same as the incoming line frequency.

MAXIMUM LOAD

The AR 1220 can handle loads totalling up to 20 

amperes as long as the input voltage is equal to 

or above 124 volts. For voltages below that level, 

its capacity must be derated at approximately .10 

amperes per volt. See fi gure 2. As a practical mat-

ter, therefore, to cope successfully with worst case 

brownout condi-tions, you should plan your total 

load so that it does not exceed 16.5 amps, or 1980 

watts. Please note that this refers to the aggre-gate 

power requirement of all equipment plugged into the 

Voltage Regulator, not to each individual item.

EXTREME VOLTAGE PROTEC-

TION

The AR Series includes special circuitry to sense 

over  and un-der voltages and positively shut down 

the output before possible damage is done. For the 

AR-1220, overvoltages are those over 150V (135V 

in 100V mode). When the input voltage exceeds 

that limit, the power will cut off. It will come back on 

automatically when the overvoltage is removed as 

long as the voltage has not exceeded 300V. The red 

LED labelled EXTREME VOLTAGE SHUT-DOWN 

indicates the shutdown condition. The output is also 

shut down for extremely low input voltages (those 

below 75V, or 65V in 100V mode).

To provide protection against a catastrophic error in 

AC mains wiring, dangerously high voltages (those 

over approximately 300V) will cause an internal fuse 

to blow, but equipment plugged into the Voltage 

Regulator will not be damaged.

FUSES AND CIRCUIT BREAKERS

There are one circuit breaker and 8 internal fuses in 

the AR-1220.

1.  A fast blow 20 amp circuit breaker is used as the 

on/off switch. This breaker will trip if the unit’s 

20 amp capacity is exceed-ed at any time. If the 

circuit breaker is tripped, the on/off switch will 

switch off. To reset it, push the switch back to the 

on position.

2.  A fast blow 1/4 amp fuse is located inside the 

unit. This fuse will blow if the unit has been 

connected to a voltage that is above the range 

of the Extreme Voltage Shutdown circuitry (ap-

proximately 300V). To replace it, the unit must 

be completely disconnected from all power and 

removed from its rack. The six hex head screws 

and one Allen head screw holding the top cover 

must be removed.

NOTE: There are two different types of internal 

fuses. There are seven 30 amp fuses to protect 

the voltage switches against faults in the control 

circuits (see the section on Design), and the 1/4 

amp fuse mentioned above, to protect the small 

transformer against line voltages greater than 300V. 

For continued protection, replace fuses only with the 

exact same type and rating. The internal fuses are 

lo-cated on the main circuit board.

INPUT VOLTAGE MONITORING

The row of ten LED’s at the top left of the front panel 

make up a meter that indicates INPUT VOLTAGE. 

Only one LED will light up at a time. There are two 

red LED’s at the endpoints. When lit, they indicate 

that the input voltage may be above or below the 

point where it can be restored to the selected nomi-

2

Summary of Contents for AR-1220

Page 1: ...AR 1220 AC LINE VOLTAGE REGULATOR VOLTAGE REGULATORS...

Page 2: ...wo space rack unit weighs only 50 lbs 23 kg AR 1220J NOTE FIRST SELECT CORRECT VOLTAGE Before using your model AR 1220J Voltage Regu lator be sure that the output voltage switch on the rear panel is c...

Page 3: ...EME VOLTAGE SHUT DOWN indicates the shutdown condition The output is also shut down for extremely low input voltages those below 75V or 65V in 100V mode To provide protection against a catastrophic er...

Page 4: ...it is as close as possible to the nominal level SPIKE A pulse of energy on the power line Spikes can have voltages as high as 6000 volts Though they are usually of very short duration the energy they...

Page 5: ...d by a copy of the original purchase invoice showing the purchase date this is not necessary if the Warranty Reg istration was completed either via the mailed in warranty card or on line website regis...

Page 6: ...ng and use it to ship the product for servicing Also please enclose a note giving your name address phone number and a description of the problem NOTE All equipment being returned for repair must have...

Page 7: ...150V AR 1220J 100V mode Below 65V or above 135V Voltmeter Accuracy 5V Spike Protection Modes Line to neutral neutral to ground line to ground Spike Clamping Voltage Initial turn on at 200V TVSS ratin...

Page 8: ...Furman Sound Inc 1997 South McDowell Blvd Petaluma California 94954 6919 USA Phone 707 763 1010 Fax 707 763 1310 Web www furmansound com E mail info furmansound com Made in China 112103 A...

Reviews: