FUNKEN FRV 125 Manual Download Page 3

4

as they are usually connected to a larger system of ducts. 
The operator must install a protective grille on the outlet 
side in line with EN 292-1 to prevent injury and to prevent 
parts from falling in.

Ensure that the fan is suitable for use in explosion protection 
areas.

DANGER OF INJURY FROM ROTATING PARTS!

If installation makes it possible to accidentally reach into the 
rotating impeller, fit a suitable protective device (e.g. protec-
tive grille). Any different usage or use that goes beyond this 
scope is considered improper use. The manufacturer/supplier 
is not liable for resulting damage. The risk is borne solely by 
the user.

The user is responsible for proper use. Proper use also 
includes compliance with the operating instructions and ad-
herence to the mandatory inspection and service conditions.

1.5 Private use 

This fan has been developed, designed and built for industrial 
and commercial use. Use in the private sector is therefore 
prohibited. 

1.6 Danger zone

The danger zone extends around the entire fan during as-
sembly, maintenance and repair tasks. Keep the area around 
the fan free of objects.

2 TRANSPORTATION/STORAGE

2.1 Transportation

Transport fans carefully!

Improper transportation can cause damage. If damaged by 
impacts or dropping, carefully check that the fan is working 
correctly and that the current consumption of the fan is 
correct. Do not operate damaged fans.

The fan or the transport unit can tip over during transpor-
tation. Pay attention to the centre of gravity (approximately 
central) and the weight (see technical data). Secure the fan 
using appropriate slings before transportation. Ensure the 
stability of the unit, i.e. do not stack units.

2.2 Items delivered

Remove the packaging immediately on delivery. Check the 
radial fan for possible transportation damage (report to the 
forwarding agent immediately) and check that the delivery 
is complete and correct. To do this, compare the details on 
the fan identification plate with the details on the delivery 
note. The same applies to accessories. Incorrect quantities 
or transport damage can only be processed via the trans-
port insurance if the damage is confirmed by the forwarding 
agent’s driver.

2.3 Packaging

The fans can be delivered in robust and secure transport 
boxes and/or on pallets.

2.4 Temporary storage

Attention must be paid to the following points 
during temporary storage:

• 

Store the fan in the original packaging or supplement the 
original packaging depending on external influences.

• 

The storage site must be protected from weather, dry 
and free of dust and must not be subject to high humidity 
(max. 70%). The storage temperature must be between 
-25 °C and +60 °C.

• 

The fan must be protected against impacts, vibrations etc.

2.5 Transportation

Lift the fan carefully out of its packaging. The fan is fixed 

to a transport panel to protect it from 
damage. Remove this panel.

Radial fans must only be handled by the 
frame when being transported to the 
intended installation site.
Ensure that the mode of transport is 
selected to suit the fan weight. Ensure 
that the weight is evenly distributed.

Summary of Contents for FRV 125

Page 1: ...diagrams 7 5 2 Cable connections 7 5 3 Thermal contact PTC thermistor for motor protection 7 5 4 Fluctuating power supply 7 5 5 Speed control via the frequency converter 7 5 6 Connection diagrams 8 6...

Page 2: ...ineering Industry Associ ation and EU Machinery Directive 2014 34 EU ATEX apply Ensure that no critical gas concentrations are present during repair maintenance and assembly tasks in explosion protec...

Page 3: ...ring transpor tation Pay attention to the centre of gravity approximately central and the weight see technical data Secure the fan using appropriate slings before transportation Ensure the stability o...

Page 4: ...red points in the base frame and anchored in the on site foundation If the fan is mounted outside a PE drive protection cover provided by the manufacturer must be attached A flame retardant PP rain co...

Page 5: ...or articles of loose clothing are sucked in 4 1 Safety inspections Conduct the following tests before commissioning After the fan has been positioned at its intended desti nation rotate the impeller...

Page 6: ...n be found on the plate on the motor cover and at other locations 5 2 Cable connections Cable routing is determined by local conditions and regula tions The type of cable and wire sizes are specified...

Page 7: ...reactivation before disconnecting the connecting cable of the drive motor To prevent the fan from being unintentionally reactivated via the control unit set the repair switch to 0 or disconnect and is...

Page 8: ...aware of contaminated components during cleaning maintenance and repair tasks 7 1 Standstill Standstill or temporary storage of the fan must be avoided If this is not avoidable in certain cases the f...

Page 9: ...aw it from the repair switch or terminal box Remove the supply air and exhaust system if present Release the frame from the vibration dampers 7 5 Maintenance tasks The FUNKEN radial fan is maintenance...

Page 10: ...are based on the respective operating conditions and must be specified by the operator Extracting heavily contaminated conveyed media can cause deposits to accrete on the fan impeller and the elastic...

Page 11: ...ease support centre impeller nozzle and retighten screws Fan rotates and does not convey any air or conveys too little air a Air flow interrupted b Fan rotating in incorrect direction c Non uniform in...

Page 12: ...law Any form of reproduction editing distribution and any form of exploitation outside that permitted by copyright law requires the written consent of the respective creator or author 9 EMERGENCIES In...

Page 13: ...rket They comply with the standards listed below Directive standard Title DIN EN ISO 12100 2011 Safety of machinery General principles for design Risk assessment and risk reduc tion DIN EN ISO 5801 20...

Page 14: ...rm which we have brought onto the market They comply with the standards listed below Directive standard Title DIN EN 1127 1 2011 10 Explosive atmospheres Explosion prevention and protection Part 1 Bas...

Page 15: ...16 SPACE FOR NOTES 16...

Page 16: ...17 17...

Page 17: ...EN 12 2019 FUNKEN Kunststoffanlagen GmbH Meysstrasse 1 53773 Hennef Germany Telephone 49 2242 92 09 0 Fax 49 2242 92 09 11 Email funken funken de www funken de K u n s t s t o f f a n l a g e n...

Reviews: