Malfunction

Possible cause

Remedy

Fan not rotating.

a)   No power output present 

on the control unit.

b)  Main switch set to “0”.
c)   Motor cable not wired 

in the terminal box.

d)  Mains power not being supplied.
e)  Defective control fuse.
f)  Motor protection relay triggered.

• 

 Establish power output. 

• 

Set main switch correctly to “I”.

• 

 Connect motor cable. 
Check: 
Mains power, fuses, connections, motor 
temperature. Leave to cool 
if necessary (if the problem recurs, 
shut down the cause of overheating).

Motor protection trig-

gered.

Motor temperature too high.

Check motor for blocking, bearing 
damage, winding damage; check 
connections and power supply.

Impeller scraping.

a)   Deposits on impeller or 

nozzle.

b)   Relative positions of impeller 

and nozzle have 
changed.

Check impeller area for foreign 
bodies, check motor attachment. Release 
support, centre 
impeller/nozzle and retighten 
screws.

Fan rotates and 

does not convey any 

air or conveys too little 

air.

a)  Air flow interrupted.

b)   Fan rotating in incorrect 

direction.

c)   Non-uniform inflow to 

impeller.

Establish free air passage, clean impeller, 
check pipe system, check cover flaps.

Change direction of rotation by 
reversing polarity.

Lengthen the inlet-side straight connection 
pipe to at least three times the nominal 
value of the fan inlet. Mount non-return 
valves or butterfly valves at the earliest 
after three times the nominal value of the 
fan outlet.

Fan vibrates while 

running.

a)   Deposits have formed on the 

impeller vanes.

b)   Condensate outlet blocked, impel-

ler rotating in water.

Clean the impeller.

Clean the water drain.

The following table is intended to provide the service team with pointers to possible causes of malfunctions and a guide to 
rectifying them:

The warranty is rendered invalid if damage occurs due to a failure to conduct the regularly required 
inspections.

Summary of Contents for FRV 125

Page 1: ...diagrams 7 5 2 Cable connections 7 5 3 Thermal contact PTC thermistor for motor protection 7 5 4 Fluctuating power supply 7 5 5 Speed control via the frequency converter 7 5 6 Connection diagrams 8 6...

Page 2: ...ineering Industry Associ ation and EU Machinery Directive 2014 34 EU ATEX apply Ensure that no critical gas concentrations are present during repair maintenance and assembly tasks in explosion protec...

Page 3: ...ring transpor tation Pay attention to the centre of gravity approximately central and the weight see technical data Secure the fan using appropriate slings before transportation Ensure the stability o...

Page 4: ...red points in the base frame and anchored in the on site foundation If the fan is mounted outside a PE drive protection cover provided by the manufacturer must be attached A flame retardant PP rain co...

Page 5: ...or articles of loose clothing are sucked in 4 1 Safety inspections Conduct the following tests before commissioning After the fan has been positioned at its intended desti nation rotate the impeller...

Page 6: ...n be found on the plate on the motor cover and at other locations 5 2 Cable connections Cable routing is determined by local conditions and regula tions The type of cable and wire sizes are specified...

Page 7: ...reactivation before disconnecting the connecting cable of the drive motor To prevent the fan from being unintentionally reactivated via the control unit set the repair switch to 0 or disconnect and is...

Page 8: ...aware of contaminated components during cleaning maintenance and repair tasks 7 1 Standstill Standstill or temporary storage of the fan must be avoided If this is not avoidable in certain cases the f...

Page 9: ...aw it from the repair switch or terminal box Remove the supply air and exhaust system if present Release the frame from the vibration dampers 7 5 Maintenance tasks The FUNKEN radial fan is maintenance...

Page 10: ...are based on the respective operating conditions and must be specified by the operator Extracting heavily contaminated conveyed media can cause deposits to accrete on the fan impeller and the elastic...

Page 11: ...ease support centre impeller nozzle and retighten screws Fan rotates and does not convey any air or conveys too little air a Air flow interrupted b Fan rotating in incorrect direction c Non uniform in...

Page 12: ...law Any form of reproduction editing distribution and any form of exploitation outside that permitted by copyright law requires the written consent of the respective creator or author 9 EMERGENCIES In...

Page 13: ...rket They comply with the standards listed below Directive standard Title DIN EN ISO 12100 2011 Safety of machinery General principles for design Risk assessment and risk reduc tion DIN EN ISO 5801 20...

Page 14: ...rm which we have brought onto the market They comply with the standards listed below Directive standard Title DIN EN 1127 1 2011 10 Explosive atmospheres Explosion prevention and protection Part 1 Bas...

Page 15: ...16 SPACE FOR NOTES 16...

Page 16: ...17 17...

Page 17: ...EN 12 2019 FUNKEN Kunststoffanlagen GmbH Meysstrasse 1 53773 Hennef Germany Telephone 49 2242 92 09 0 Fax 49 2242 92 09 11 Email funken funken de www funken de K u n s t s t o f f a n l a g e n...

Reviews: