PSB / PSC Series Installation Instructions
Application
These general-purpose power supplies can be used to
fulfill all the 120 Vac and 24 Vac
*
(Class 2) power require-
ments needed inside a building automation (BAS) panel,
industrial enclosure, or other general purpose electrical
enclosure, in addition to on/off control, equipment over-
current protection, power indication, high/low voltage
separation, and convenience receptacles. They are also
useful for many applications outside of BAS.
Installation
When installing this product...
1. Read these instructions carefully. Failure to follow them
could damage the product or cause a hazardous condition.
2. Check the product ratings and ensure that the product is
suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, perform a voltage check as
provided in these instructions.
CAUTION
RISK OF ELECTRICAL SHOCK - MORE THAN ONE DISCONNECT MAY BE
REQUIRED TO DE-ENERGIZE THE DEVICE BEFORE SERVICING.
CAUTION
REMOVAL OF COVER OR ACCESS PLATE (IF PRESENT) EXPOSES
HIGH VOLTAGE.
PSB / PSC Series Selection Guide
Model Number *
VA Rating
Panel
Mount
Enclosed
120 Vac
Receptacles
Aux Output
Main Breaker on
Input Power
Secondary
Configuration
PSC100AB10
100 VA
•
•
•
10 Amp Switch / Breaker
Terminal Strip
PSB100AB10
100 VA
•
•
•
10 Amp Switch / Breaker
Terminal Strip
PSC40AB10
40 VA
•
•
•
10 Amp Switch / Breaker
Terminal Strip
PSB40AB10
40 VA
•
•
•
10 Amp Switch / Breaker
Terminal Strip
RESET
OFF
ON
OFF
Com
24 Vac
120 Vac
Neutral
Ground
120 Vac Aux. Output
120 Vac Convenience Outlet
*
10 Amp Main
Breaker/Switch
24 Vac ON/OFF
LED Indicator
5.620˝
2.245˝
3.900˝
5.620˝
6.250˝
4.500˝
Removable Access Plate
4.500˝
4.610˝
To remove cover
4 Mounting Screw Holes
Hole diameter .203"
* All models may be followed by –IC.
Functional Devices, Inc.
• p: 800.888.5538 • f: 765.883.7505 • www.functionaldevices.com • [email protected]
Bulletin B1450