11
13 mm x 4
x4
Manual
FUMEX FBE
1100
4.4.4 Vibration damper Kit FBV 750
Fig. 16
5 Commissioning
5.1 Start-up
Any faults must be rectified before turning
on the power.
1.
Start the fan.
If the machine’s overcurrent protection is
tripped, power consumption is too high.
Please contact Fumex.
2.
Check the fan motor’s direction of rotation. The fan
motor’s direction of rotation is checked by starting
the fan, then stopping the fan. As the speed decreases,
you can see which way the motor is rotating
through the cooling air intake (pos. 7,
Fig. 2
.) If the
direction of rotation is incorrect, the phase coupling
in the motor terminal block is reversed.
3.
Check the rotational direction again.
4.
Turn off the fan.
The fan is now ready for operation.
6 Operation
The fan motor generates heat and is equip-
ped with a cooling fan (pos 8,
Fig. 2
.) The
cooling fan inlet is located at the back of the
motor. Do not block the inlet.
Note that electric equipment is always
sensitive to static electricity, high humidity,
high temperature, and grid disruption.