User’s manual 

- 8 - 

FUM – 2410/15/20CBP 

 

K.  Specifications 

 
Model 

FUM – 2410CBP 

FUM – 2415CBP 

FUM – 2420CBP 

Output 

Absorption charge voltage selections 

Gel: 28.2V / AGM: 28.6V / Wet: 28.8V / Calcium-Calcium: 31.1V 

Absortion charge timer 

Limited not over 4 hours. 

Float charge voltage selections 

26.4V       27.0V       27.6V 

Battery charger / power supply selections  

Yes 

Maximum output charging current 
(continuous) 

15A 

20A 

25A 

Recommended battery capacity range 

50~150 Ah 

70~200 Ah 

80~250 Ah 

Soft start bulk charge 
Battery voltage to trigger (cut-in) soft start 
bulk charge mode 

< 18V 

Soft start bulk charge current (current limit) 

7.5A 

10A 

10A 

 
Line regulation (90~260V) for charging 
current 

< 0.5% 

Ripple and noise (peak to peak) 

< 250mV 

< 250mV 

< 250mV 

Efficiency at maximum power (100/230VAC) 

> 86/90% 

> 86/90% 

> 86/90% 

 
Dual bank charging (battery must be of same 
type) 

Yes 

Input 

AC voltage range 

100~260 VAC 50Hz 

AC current at full load (100/230VAC) 

5.6/2.4A 

7.4/3.2A 

9.3/3.9A 

Protection 

Overload 

90~110% rated output current or 50% rated output current (soft 
charge). 
Protection type: constant current limiting, recovers automatically 
after fault condition is removed. 

Short circuit 

Recovers automatically after fault condition is removed. 

Reverse polarity 

Car blade fuse. 

Over temperature 

Protecction type: shut down. 

OVP output over voltage 

Yes 

Cooling 

Cooling method 

Thermostatic, Variable speed fan. 

Indicators 

3 stage battery charger / power supply mode 

Yes 

Charge phase bulk / absortion / float 

Yes 

Fault mode 

Yes 

AC power 

Yes 

Fuses 

AC fuses at IEC AC power socket 

T6.3A 

T8A 

T10A 

DC car blade fuse at front panel 

25A x 1 

15A x 2 

20A x 2 

Accesories 

Cable & spare fuses 

Yes 

Remote temperatura sensor 

Optional 

Approvals 

Safety: EN 60335 

Yes 

EMC: EN 55014 

Yes 

Others 

Dimensions and weight 

220 x 80 x 200mm; 

2.4Kg 

220 x 80 x 250mm; 

2.8Kg 

220 x 80 x 261mm; 

3.2Kg 

Remarks 

All values are based on the standard ambient temperature 25°C and pressure 0.1Mpa 

 
 
 
 
 
 
 
 

OR: 7673-2200-0012 Rev. 3.0    08/2009 

TR: 24XX-CBP-BIG Rev. 3.0    08/2009

 

Summary of Contents for FUM-2410CBP

Page 1: ...f the charger there is no user serviceable parts inside Do not charge the battery on boats Remove the battery and charge on shore Never attempt to charge a frozen battery Never attempt to charge a damaged battery Wear protective goggles and turn your face away when connecting or disconnecting the battery Never place the charger on top of a battery Never smoke use an open flame or create sparks nea...

Page 2: ... See section G 2 Battery type selection Slide switch to set charger for AGM gel wet and calcium calcium type battery 3 Float voltage selection Slide switch to set float charge voltage to 26 4 27 0V 27 6V 4 Charge status LED display Charger ON LED Green 3 stage charger mode Red Power supply mode BULK LED Red Bulk charging with constant max current ABSORPTION LED Orange Absorption charging with pres...

Page 3: ... Ah C Battery charger installation and connection Observe the warnings safety precautions before rushing to install and operate the charger Check battery condition fill up cells for wet battery clean battery poles Secure the battery charger in a well ventilated place make sure the mounting surface is flat and without soft covering material or loose paper sheet The air intake is at the bottom and a...

Page 4: ...dependently by user according to the type of battery such that battery can be connected permanently to the charger when it is not in use E Manual equalization charging for wet type battery only Wet lead acid battery requires periodic high voltage charging about 10 overcharge absorption voltage to balance the voltage of each cell reverse the high concentration of electrolyte at the bottom and clear...

Page 5: ... voltage However a 2 stage charger cannot completely charge the battery when the charger switches from bulk mode to float mode After switching to float mode the battery will in most cases be about 80 recharged The battery receives the remaining recharge while in float mode over several days It is highly recommended to switch back to the 3 stage charger mode periodically when the external load is d...

Page 6: ...perature control function never plug in the charger during charging I Cable size selection Wire size AWG Area mm Maximum one way distancie for 2 voltage loss 24V 15A Maximum one way distancie for 2 voltage loss 24V 20A Maximum one way distancie for 2 voltage loss 24V 25A 10 5 26 4 65 m 15 3 feet 3 50 m 11 5 feet 2 80 m 9 2 feet 8 8 37 7 31 m 24 feet 5 48 m 18 feet 4 39 m 14 4 feet 6 13 3 11 58 m 3...

Page 7: ...on even after 20 hours charging time Absorption light remains on all the time Wrong battery type selection eg charge gel battery with Calcium Calcium or wet type selection Check charged battery label and change battery type selection to correct setting Total battery capacity is too high for dual charging Check battery capacity or charge battery separately Battery temperature too high Use temperatu...

Page 8: ...ll load 100 230VAC 5 6 2 4A 7 4 3 2A 9 3 3 9A Protection Overload 90 110 rated output current or 50 rated output current soft charge Protection type constant current limiting recovers automatically after fault condition is removed Short circuit Recovers automatically after fault condition is removed Reverse polarity Car blade fuse Over temperature Protecction type shut down OVP output over voltage...

Reviews: