F47 - Evaporator temperature (S2/S3) to start defrosting:

When the evaporator temperature is below the value configured in this function the controller will start the 
defrost. If sensor S3 is configured as the second evaporator sensor (F57), the controller will start the 
defrost as soon as one of the sensors, S2 or S3, meets this condition. This function is disregarded when the 
condition to start the defrost is time (F45).

F48 - Door open time to switch off the fan:

For safety reasons, after a time with the door open equal or longer than the one adjusted in this function has 
elapsed, the fan will be switched off in the refrigeration step. This function is disabled when configured 
with

[no,,]

 (-1).

F49 - Door open time to switch off the control outputs:

For safety reasons, after a time with the door open equal or longer than the time adjusted in this function 
has elapsed, the outputs will be switched off (compressor, fan, and defrost). This function is disabled when 
configured with 

[no,,]

 (0).

F50 - Maximum condenser temperature (S3) to switch off the control outputs:

Above this temperature, in addition to the indication of the visual and audible alarms (

[atC2]

) the loads 

activated by the outputs will be switched off. This alarm will be deactivated if the S3 input is configured 
(F57) for another function. This alarm is ignored until the controller reaches the control temperature for the 
first time.

F51 - Control differential for the maximum condenser temperature (hysteresis):

For the loads to be switched on again, the temperature in sensor S3 (condenser) must drop to the value 
adjusted in F50 minus the value configured in this parameter.

F52 - Compressor on time without reaching the setpoint to switch off the control outputs:

It is the maximum time the compressor will remain on without reaching the setpoint during the cooling 
process. If this time is exceeded, the outputs will be switched off (compressor, fan, and defrost), and the 
visual and audible alarms will be activated 

[ALrC]

. This function can be disabled by adjusting it to the 

minimum value

[no,,]

(0).

NOTE: 

In this condition the controller must be switched off and on again to resume normal operation.

F53 - Room temperature alarm delay:

When this configuration is active, the temperature must remain in the alarm condition for the time defined in 
this parameter so the alarm can be triggered.
It will avoid false alarms originating from punctual temperature variations, like after a defrost.

F54 - High condenser temperature alarm (S3):

It is the condenser temperature above which the controller will indicate the visual (

[atC1]

) and audible 

(F56) high temperature alarm. This alarm will be deactivated if the S3 input is configured (F57) for another 
function. This alarm is ignored until the instrument reaches the control temperature for the first time.

F55 - Open door time for the alarm to go on:

If the door is kept open for a time equal or longer than the one configured in this parameter the controller will 
activate a visual and audible (F56) door open alarm. The alarms are suspended when the door is closed. 
The visual alarm can be inhibited through the key 

>

(pressed for 2 seconds). For the door open alarm to 

work, one of the digital inputs must be configured as door contact (F57 and F58). This function is disabled 
when configured with 

[no,,]

  (0).

F56 - Enable buzzer:

Allows enabling and disabling the internal buzzer for alarm signaling.

F57 - Function of the digital input 1 / sensor S3:

[Off,]

Off

[,,,1]

Digital input: Activate economic setpoint (NO switch)

[,,,2]

Digital input: Force defrost (NO switch)

[,,,3]

Digital input: Force fast freezing (NO switch)

[,,,4]

Digital input: External alarm (NO)

[,,,5]

Digital input: Door contact (NO)

[,,,6]

Digital input: Activate economic setpoint (NC switch)

[,,,7]

Digital input: Force defrost (NF switch)

[,,,8]

Digital input: Force fast freezing (NC switch)

[,,,9]

Digital input: External alarm (NC)

[,,10]

Digital input: Door contact (NC)

[,,11]

Sensor S3: Temperature difference for economic setpoint (S3-S1)

[,,12]

Sensor S3: Condenser temperature control

[,,13]

Sensor S3: Second evaporator temperature control

[,,14]

Digital input: pressostat 1 status, contact NO

[,,15]

Digital input: pressostat 1 status, contact NC

[,,16]

Digital input: high pressure switch, contact NO

[,,17]

Digital input: high pressure switch, contact NC

F58 - Function of the digital input 2:

[Off,]

Off

[,,,1]

Digital input: Activate economic setpoint (NO switch)

[,,,2]

Digital input: Force defrost (NO switch)

[,,,3]

Digital input: Force fast freezing (NO switch)

[,,,4]

Digital input: External alarm (NO)

[,,,5]

Digital input: Door contact (NO)

[,,,6]

Digital input: Activate economic setpoint (NC switch)

[,,,7]

Digital input: Force defrost (NF switch)

[,,,8]

Digital input: Force fast freezing (NC switch)

[,,,9]

Digital input: External alarm (NC)

[,,10]

Digital input: Door contact (NC)

[,,11]

Digital input: pressostat 2 status, contact NO

[,,12]

Digital input: pressostat 2 status, contact NC

[,,13]

Digital input: low pressure switch, contact NO

[,,14]

Digital input: low pressure switch, contact NC

NOTE:

 When digital input is configurated as pressure switch, it allows turn off the compressor outputs, fans 

and defrost, displaying the associated alarm to this alarm origin. When there are no longer pressostat 
event, the controler returns to initial process configurated.

F59 - S2 Evaporator temperature indication offset:

It allows compensation for possible deviations in the evaporator temperature reading (S2) caused by the 
replacement of the sensor or changes in the cable length. Sensor S2 can be switched off by adjusting the 
function to the minimum value until the message

[,OFF]

is displayed. In this condition all the functions 

that rely on the reading of sensor S2 will be disabled.

F60 - S3 sensor temperature indication offset:

It  allows  compensation  for  possible  deviations  in  the  S3  sensor  temperature  reading  caused  by  the 
replacement of the sensor or changes in the cable length. Sensor S3 can be switched off by adjusting the 
function of the digital input 1 / Sensor S3 (F57) with the value 

[,OFF]

 (0) or making it to operate as a 

digital input.

F61 - Intensity of the digital filter applied to sensor 1 (0 - deactivated):

This filter aims at simulating an increase of thermal mass on the sensor, thus increasing its response 
time (thermal inertia). The higher the value adjusted in this function, the longer the response time of the 
sensor.

F62 - Function lock:

It allows and configures the function lock (see item 6.3.8).

[,,,0]

- Do not allow the function lock.

[,,,1]

- Allow a partial lock where the control functions will be locked but the adjustment of the 

setpoint is allowed.

[,,,2]

- Allow full locking.

NOTE: 

The defrost and view of the minimum and maximum temperature records will always be 

allowed.

F63 - Time for functions lockdown:

It configures the time in seconds for the command to activate the function lock.

[,,15]

-

[,,60]

 Time in seconds for the command to activate the lock.

F64 - Control functions shutdown:

Authorizes switching off the control functions (see item 6.3.9).

[no,,]

Disables the control functions shutdown.

[,,,1]

Enables activation/deactivation of the control functions only if the functions are unlocked.

[,,,2]

Enables activation/deactivation of the control functions even if the functions are locked.

[,,,3]

Enables activation/deactivation of the control functions only if the functions are unlocked.*

[,,,4]

Enables activation/deactivation of the control functions even if the functions are locked.*

* When F64 is configured as 3 or 4 and the control functions shutdown is activated, the controller will 
turn off the display, keeping only the indication     light on. If any key is touched the display turns on by 5 
seconds, turning off again until a new key is touched.

F65 - Operating mode of the room temperature alarms (S1):

Determines  whether  the  values  configured  for  the  high  room  temperature  (F07)  and  low  room 
temperature (F06) alarms are relative to the setpoint or absolute values.

[,,,0]

- The room temperature alarms F06 and F07 represent values relative to the setpoint.

Example:

Desired temperature 

[SP,,]

: - 5ºC

Low temperature alarm 

[,F06]

: 2ºC

High temperature alarm

[,F07]

: 2ºC

Limits: (

[SP,,]

[,F06]

 and 

[SP,,]

[,F07]

).

The low temperature alarm will be signaled at -7°C (-5-2) and the high temperature alarm at -3°C                           
(-5+2).

[,,,1]

- the room temperature alarms F06 and F07 are absolute values.

Example:

Low temperature alarm 

[,F06]

: -30ºC

High temperature alarm 

[,F07]

: 15ºC

The low temperature alarm will be signaled at -30 °C and the high temperature alarm at 15 °C.

F66 - Maximum operating time of the COMP output for maintenance:

Whenever the COMP output is activated the controller will count its operating time. When the counted 
time is equal or longer than the one set in this function, the display will show the message 

[Amai]

, and 

the audible warning will be activated if it is enabled (F56), meaning that the compressor must be 
serviced.

NOTE: 

The value adjusted in this parameter will be multiplied by ten.

Example: 

Value adjusted = 1, then 1*10 = 10 hours for the next service.

F67 - Time to confirm a low evaporator (S2 / S3) temperature to start defrosting (if F45=1):

When the evaporator temperature drops and then reaches the value set in F47, the controller starts 
counting the confirmation time to start defrosting. After the counting finishes, if the temperature is still 
below  the  value  configured  in  F47  the  defrost  is  started.  If  the  temperature  is  above  the  value 
configured in F47 during the counting, the system continues at the refrigeration stage and the count is 
reset to zero.

F68 - High pressure event validation time:

It is the minimum time that the pressure switch connected to the discharge line must remain activated in 
order to be validated this event. This time is used to avoid unnecessary triggering due to the pressure 
oscillation.

F69 - Low pressure event validation time:

It  is  the  minimum  time  that  the  pressure  switch  connected  to  the  suction  line  must  remain  on  for 
validated this event. This time is used to avoid unnecessary triggering due to oscillation of pressure.

F70 - Time to inhibit the reading of the low pressure when initializing:

Delay time that the suction line pressure switch takes to be within its ideal initialize the controller, 
avoiding unwanted alarms.

F71 - Time to wait for control return after high pressure event:

After the high pressure event, the controller uses this timeout to then regain control.

F72 - Delay time to return to control after a low pressure event:

After the low pressure event, the controller uses this timeout to then regain control.

F70

F68/F69

Reading validation of
the pressure switch

PRESSURE
SWITCH
ACTIVATED

Pressostat
event OFF

Pressostat
event ON

F71/F72

Control
released

PRESSURE
SWITCH
ACTIVATED

Control

deactivated

by pressure

switch

NOTE 1:

 For safety reasons, if controller registers 3 high pressure or 3 low pressure events in one hour 

period, three outputs of controller will be turned OFF: Compressor, Defrost & Fan display on controller 
will show alarm message 

[apHi]

 - High pressure alarm or 

[aplo]

 - Low pressure alarm. To reset 

[apHi]

 and 

[aplo]

 alarms a manual intervention is required. To manually reset: short press   key 

;

on controller to navigate 

[Hplp]

 option, short press   key, select the option ON and press   key.

/

/

NOTE 2:

 The values set in F57 and F58 must be properly configured for digital inputs of high/low 

pressure switches.

NOTE 3:

 The F71 and F72 times are independents of the time set in F10 - Minimum compressor time 

ON.

Summary of Contents for TC-900EL Log

Page 1: ...cess Short touch displays the maximum and minimum measurements recorded Hold down for 10 seconds manual datalogger activation Hold down for 2 seconds inhibits the audible alarm Hold down for 2 seconds...

Page 2: ...trolfunctionsandleavetheadjustmentofthesetpoint enabled F62 1 Toactivatethefunctionslock accessthe LOC optioninthequickaccessmenu 6 3 9 Control Functions Shutdown The shutdown of the control functions...

Page 3: ...ctive the controller will show the message LOC in the display uponpressing or andwillnotallowadjustingtheparameters 6 4 4 Date and time adjustment Select the option ClO in the main menu The controller...

Page 4: ...F min F F sec x10h min sec sec sec mim mim 58 0 NO 1 1 0 0 0 NO 0 0 NO 58 1 NO 0 NO 32 NO 1 0 NO 0 NO 32 0 NO 0 OFF 0 OFF 0 OFF 36 OFF 36 0 0 15 0 NO 0 0 NO 0 0 0 30 1 1 221 999 99 99 999 999 999 1 99...

Page 5: ...orator temperature does not reach the value adjusted in function F19 or if sensor S2 S3 isdisconnected thefanwillreturnafterthetimeadjustedinthisfunctionhaselapsed F21 Fanoperatingmodeduringrefrigerat...

Page 6: ...ons thatrelyonthereadingofsensorS2willbedisabled F60 S3sensortemperatureindicationoffset It allows compensation for possible deviations in the S3 sensor temperature reading caused by the replacement o...

Page 7: ...ls of eachinstrument Sold Separately CONV 32 or CONV 256 Keep Sitrad updated in website http www sitrad com Serial RS 485 It connects via RS 485 network to the controller only forcontrollersthathaveRS...

Page 8: ...the technical team of Full Gauge Controls Damage has been caused by a fall blow and or impact infiltration of water overload and or atmospheric discharge USE OF WARRANTY To make use of the warranty cu...

Reviews: