Fan Relay ON

Fan Relay ON

Fan Relay ON

Fan Relay ON

Fan Relay ON

Fan Relay ON

Fan Relay ON

Fan Relay ON

Mode

Comp. Relay ON

Fan Relay CYCLING

Fan Relay CYCLING

Fan Relay CYCLING

Fan Relay ON

Fan Relay ON

Fan Relay ON

Fan Relay OFF

Fan Relay OFF

Comp. Relay off with

Normal or FF* SP*

Comp. Relay off with

Economic SP*

Fan Relay CYCLING

Fan Relay ON

Fan Relay OFF

Fan Relay CYCLING

Fan Relay ON

Fan Relay OFF

Fan Relay CYCLING

Fan Relay OFF

*LEGEND:
SP: Setpoint
FF: Fast Freezing

F22 - Fan stop due to high temperature in the evaporator:

This  aims  at  switching  off  the  evaporator  fan  until  the  evaporator  temperature  approaches  the 
temperature provided in the project design, thus avoiding high suction pressures and temperatures that 
could damage the compressor.
During the refrigeration process if the evaporator temperature exceeds the adjusted value, the fan is 
switched off, being switched on again with a fixed hysteresis of 0.1 °C / 1 °F. It is a valuable resource 
when, for example, a cold storage installation is started up after several days of inactivity, or when a 
walk-in chamber or display is replenished with goods.

F08 - Time in refrigeration (interval between defrosts):

When the defrost is configured to start by time (F45), this function establishes the maximum time 
duration of the cooling process.In this case, the defrost will be started whenever the time elapsed during 
the cooling mode reaches the value configured in this function. If the condition to start the defrost is the 
evaporator temperature and the controller is not indicating a reading error for this sensor, the time in 
refrigeration will not be considered.

F09 - Minimum compressor on time:

It is the minimum time for which the compressor remains switched on, i.e. the length of time between the 
last start up and the next stop. It is aimed at avoiding high voltage surges in the power lines, potentially 
extending lifespam of compressor.

F10 - Minimum compressor off time:

It is the minimum time the compressor will remain off, i.e. the length of time between the last stop and the 
next  start  up.  It  is  aimed  at  relieving  the  discharge  pressure  and  increase  the  service  life  of  the 
compressor.

F11 - Compressor state with a disconnected or faulty room sensor (S1):

If the room sensor (S1) is shorted, disconnected, or out of range, the compressor will assume the state 
configured in this function.

[,,,0]

- Compressor off

[,,,1]

- Compressor on

[,,,2]

- Cycling according to the times defined in F42 and F43.

F12 - Defrost at instrument startup:

It allows performing a defrost when the controller is powered on, for example when the electric power 
returns (in case of power failure).

F13 - Evaporator temperature (S2 / S3) to determine the end of defrost:

The defrost will be ended when the evaporator temperature reaches a value equal or higher than the 
value configured in this function. If sensor S3 is configured as the second evaporator sensor (F57), the 
controller will switch off the defrost outputs individually and the defrost process will be ended when both 
are off.

F14 - Maximum defrost time:

This parameter defines the maximum defrost time. If the defrost is not ended by temperature when this 
time has elapsed, a dot will keep flashing in the lower right corner of the display. If sensor 2 is switched 
off, the defrost process end will be always defined by time, thus no warning signal is required. If the 
maximum defrost time is configured as 0 (

[no,,]

), the defrost process will not be performed.

F15 - Fan on during defrost:

It defines whether the fan will remain on during the defrost. The cases of natural defrost and defrost by 
finned resistances installed outside of the evaporator are examples of the usage of the fan on.

F16 - Defrost type:

[,,,0]

 - Electric defrost (by resistance), where only the defrost output is activated

[,,,1]

 - Defrost by hot gas, where the compressor output and defrost output are activated

F17 - Temperature indication (S1) locked during defrost:

This function is aimed at avoiding viewing the room temperature rise due to the defrost cycle. The last 
temperature measured in the refrigeration cycle will be locked in the display during the defrost. The 
indication will be unlocked when this temperature is reached again or when the time configured in this 
function is exceeded after the start of the following refrigeration cycle (whichever comes first). This 
function may be disabled if configured with 

[no,,]

 (-1).

F18 - Draining time (defrost water dripping):

Time required for dripping, i.e. to drain the last drops of the evaporator. During this period, all outputs 
remain turned off. If you do not want this stage, adjust this time to 

[no,,]

.

F19 - Evaporator temperature (S2 / S3) for the fan to return after draining:

The  fan-delay  cycle  is  started  after  the  draining  phase.  The  compressor  is  activated  immediately 
because the evaporator temperature is high but the fan is activated only after the temperature on the 
evaporator drops below the adjusted value. This process is required to remove the heat that already 
exists on the evaporator as a result of the defrost to avoid transferring it to the environment.

F20 - Maximum time for the fan to return after draining (fan-delay):

For safety reasons, if the evaporator temperature does not reach the value adjusted in function F19 or if 
sensor (S2 / S3) is disconnected, the fan will return after the time adjusted in this function has elapsed.

F21 - Fan operating mode during refrigeration:

This parameter allows configuring how the fan output will behave during the refrigeration cycle. In this 
case, the working options take into account the state of the compressor output and the setpoint with 
which the instrument is operating. When configured to cycle, the on and off times are defined by F40 and 
F41.

F23 - Room temperature indication offset S1:

It  allows  compensating  possible  deviations  in  the  room  temperature  reading  (S1)  caused  by  the 
replacement of the sensor or changes in the cable length.

F24 - Address of the instrument in the RS-485 network:

Equipment's network address for communicating with Sitrad software.

NOTE: 

Every single controller within the network must have different address.

F25 - Number of defrosts per day (Monday to Friday):

The defrost cycles are evenly distributed in accordance with the number of defrosts set per day, always 
considering the preferred time. The values can be adjusted to 1, 2, 3, 4, 6, 8, or 12. This function works 
with the Monday to Friday operation schedule.

F26 - Preferred time to start defrosting (Monday to Friday):

A preferred time (reference time) for the daily defrost to be performed must be set. This function works 
with the Monday to Friday operation schedule.

F27 - Number of defrosts per day (Saturday):

The defrost cycles are evenly distributed in accordance with the number of defrosts set per day, always 
considering the preferred time. The values can be adjusted to 1, 2, 3, 4, 6, 8, or 12. This function works 
with the Saturday operation schedule.

F28 - Preferred time to start defrosting (Saturday):

A preferred time (reference time) for the daily defrost to be performed must be set. This function works 
with the Saturday operation schedule.

F29 - Number of defrosts per day (Sunday):

The defrost cycles are evenly distributed in accordance with the number of defrosts set per day, always 
considering the preferred time. The value can be adjusted to 1, 2, 3, 4, 6, 8, or 12. This function works 
with the Sunday operation schedule.

F30 - Preferred time to start defrosting (Sunday):

A preferred time (reference time) for the daily defrost to be performed must be set. This function works 
with the Sunday operation schedule.

F31 - Normal setpoint:

It is the desired room temperature. It is the reference value for the temperature control.

F32 - Economic setpoint (SPE):

It is the desired room temperature when the instrument is operating in economy mode.

F33 - Economic setpoint control differential (hysteresis):

It is the temperature difference (hysteresis) between switching ON and OFF the refrigeration control 
output in the economy mode.

F34 - Door closed time for activating the economy mode:

If the door is kept closed for a time equal or greater than the one configured in this function and the 
normal setpoint is or has been reached, the controller will activate the economy mode. After that the 
controller will operate with the economic setpoint until any condition to deactivate it is met (see 6.3.3). 
This function is disabled when configured with

[no,,]

(0).

F35 - Temperature difference (S3-S1) below which the economic setpoint is activated:

When the temperature difference between sensor 3 and sensor 1 is below the value adjusted in this 
parameter, the controller starts to operate in the economy mode.

F36 - Temperature difference (S3-S1) above which the normal setpoint is activated:

When the temperature difference between sensor 3 and sensor 1 is above the value adjusted in this 
parameter, the controller starts to operate with the normal setpoint.

F37 - Maximum time on power-saving mode:

It allows configuring the maximum time in economy mode. After this time the setpoint returns to the 
normal operation setpoint. This time is disregarded if configured as 

[tOFF]

 .

F38 - Temperature limit for Fast Freezing:

It is the minimum temperature that the instrument can reach during the fast freezing process.

F39 - Maximum Fast Freezing time:

It is the time duration of the fast freezing process.

F40 - Fan on time:
F41 - Fan off time:

They define the time for which the fan is kept on and off when operating in the cyclic mode.

F42 - Compressor on time in case of S1 fault:
F43 - Compressor off time in case of S1 fault:

They define the compressor on and off times when it is operated in the cyclic mode. This condition 
happens  when  sensor  S1  is  disconnected  (or  faulty)  and  when  parameter  F11  is  configured  as 

[,,,2]

.

F44 -Time to collect the gas before starting the defrost:

When starting the defrost the controller will keep only the fan on during this time to take advantage of 
the residual energy of the gas. This time will be disregarded in case of defrost at power up.

F45 - Condition to start the defrost (0 - time / 1 - temperature):

It defines the condition to start the defrost:

[,,,0]

- Time

[,,,1]

- Temperature

Before starting the defrost process the controller will observe the minimum time of compressor on or off 
(F09 and F10) and the gas collection stage (F44).

NOTE: 

This function is ignored when the defrost schedule is enabled (F01 = 1 or F01 = 2).

F46 - Maximum open door time for instantaneous defrost:

During the cooling step, if the door is kept open for a time longer than the one defined in this function, the 
instantaneous defrost will take place. If the door is open at the beginning of the refrigeration process, 
the counting of this time is reset. This function is disabled when configured with 

[no,,]

 (0).

Summary of Contents for TC-900EL Log

Page 1: ...cess Short touch displays the maximum and minimum measurements recorded Hold down for 10 seconds manual datalogger activation Hold down for 2 seconds inhibits the audible alarm Hold down for 2 seconds...

Page 2: ...trolfunctionsandleavetheadjustmentofthesetpoint enabled F62 1 Toactivatethefunctionslock accessthe LOC optioninthequickaccessmenu 6 3 9 Control Functions Shutdown The shutdown of the control functions...

Page 3: ...ctive the controller will show the message LOC in the display uponpressing or andwillnotallowadjustingtheparameters 6 4 4 Date and time adjustment Select the option ClO in the main menu The controller...

Page 4: ...F min F F sec x10h min sec sec sec mim mim 58 0 NO 1 1 0 0 0 NO 0 0 NO 58 1 NO 0 NO 32 NO 1 0 NO 0 NO 32 0 NO 0 OFF 0 OFF 0 OFF 36 OFF 36 0 0 15 0 NO 0 0 NO 0 0 0 30 1 1 221 999 99 99 999 999 999 1 99...

Page 5: ...orator temperature does not reach the value adjusted in function F19 or if sensor S2 S3 isdisconnected thefanwillreturnafterthetimeadjustedinthisfunctionhaselapsed F21 Fanoperatingmodeduringrefrigerat...

Page 6: ...ons thatrelyonthereadingofsensorS2willbedisabled F60 S3sensortemperatureindicationoffset It allows compensation for possible deviations in the S3 sensor temperature reading caused by the replacement o...

Page 7: ...ls of eachinstrument Sold Separately CONV 32 or CONV 256 Keep Sitrad updated in website http www sitrad com Serial RS 485 It connects via RS 485 network to the controller only forcontrollersthathaveRS...

Page 8: ...the technical team of Full Gauge Controls Damage has been caused by a fall blow and or impact infiltration of water overload and or atmospheric discharge USE OF WARRANTY To make use of the warranty cu...

Reviews: