Full Gauge TC-900EL Log Manual Download Page 1

DIGITAL CONTROLLER FOR FREEZING SYSTEMS

WITH DEFROST SCHEDULING AND INTERNAL  

DATALOGGER

4. INDICATIONS AND KEYS

6. OPERATIONS

6.1 Quick Access Menu Map

To access or navigate the quick access menu using the 

;

(short press) key while the controller is 

displaying the temperature. For every touch, the next function in the list is displayed. To confirm, use the 

/

(short press) key.

1. DESCRIPTION

Designed to better safeguard frozen products. 

TC-900

e

 

Log

 is equipped with 3 relays (Comp, 

Defrost & Fan), 2 temperature sensors, 2 digital inputs, real-time clock, data logger and light intensity 
sensor. A  third  temperature  sensor  can  be  connected  to  one  of  it’s  digital  input  for  either  defrost 
management of second evaporator; condenser temperature control or to activate economic set point. 
Other salient features include hour-meter to clock the working hours of compressor for preventive 
maintenance, internal buzzer, IP65 frontal, min-max temperature record, temperature sensor response 
time control, fast freezing mode, tamper-proof function, control functions shutdown and RS485 serial 
communication port for Sitrad real-time monitoring and management.
Product conforming to UL Inc. (United States and Canada) and NSF (United States).

2. APPLICATION

• Walk-in freezers
• Display freezers
• Upright freezers

evolution

 

 

V

er

.03

TC-900

e

 

Log

5. INSTALLATION - ASSEMBLING AND ELECTRICAL
CONNECTIONS

Control 

functions

shutdown

Functions

lockdown

Serial

programming

Protection

level

IP 65

FRONT

Fast 

Freezing

Datalogger

LOG

Supervisory 

system

3. TECHNICAL SPECIFICATIONS

Power supply

Control temperature

Operating humidity

Dimensions (mm)

76 x 34 x 77 mm (WxHxD)

Dimensions of the clipping for fixing
of the instrument

 

71 ± 0,5 x 29 ± 0,5 mm (see item 5)

TC-900E Log:

 115 or 230Vac  ±10% (50/60Hz)

TC-900EL Log:

 12 or 24Vac/dc +10%

 

 

-50°C to 105°C  /  -58°F to 221°F

 

Operating temperature

0 to 50°C  /  32 to 122°F

Load current (outputs)

COMP: 

12(8)A  / 240Vac 1HP

DEFR:

 10A  / 240Vac 2400W

FANS: 

5(3)A  / 240Vac

10 to 85 %RH (without condensation)

Defrost indication LED

Temperature unit indication LED

Control functions shutdown indication LED

TC-900

e

 

Log

Upper key

Lower key

Set key

Quick Access
Menu Key

Functions lockdown indication LED

Compressor output

indication LED

Fan indication LED

6.2 Quick access keys map

When the controller is on temperature display, the following keys serve as a shortcut for the following 
functions:

/

<

<

<

<

Hold down for 2 seconds: setpoint adjustment.

Short touch: displays the current process.

Short touch: displays the maximum and minimum measurements recorded.

Hold down for 10 seconds: manual datalogger activation.

<

Hold down for 2 seconds: inhibits the audible alarm.

<

Hold down for 2 seconds: clears history when records are displayed.

;

Short touch: enter the quick access menu.

and

<

Hold down for 4 seconds: carries out manual defrost.

/

Short touch: the current day, month, year, day of the week, hour, and 

                      minute will be shown in sequence on the display.

<

<

Short touch: Go to menu selection.

and

71 

 mm

± 0,5

29 

 mm

± 0,5 

Panel (Front View)

Panel

(Side View)

Dimension of the clipping

for fixing of the

instrument in panel

ATTENTION

FOR INSTALLATIONS WHERE A SEALING IS REQUIRED TO AVOID LIQUID CONTACT, THE CUT FOR THE CONTROLLER MUST BE OF 
70,5X29mm MAXIMUM. THE SIDE LOCKS MUST BE FIXED SO IT PRESSES THE RUBBER SEALING AVOIDING
INFILTRATION BETWEEN THE CUT AND THE CONTROLLER.

IMPORTANT

SCREWDRIVER SLOT 3/32''(2.4mm) FOR ADJUSTMENTS IN THE SIGNAL TERMINALS;
SCREWDRIVER PHILLIPS #1 FOR ADJUSTMENTS IN THE POWER TERMINALS;

THE USE OF APPROPRIATE TOOLS IS ESSENTIAL TO AVOID DAMAGE IN THE CONNECTION AT INSTRUMENT TERMINALS:

<

Hold down for 2 seconds: resets the counter when the hour meter is being 

                                             displayed.

Maximum consumption of device

1.5 VA

Luminosity 

sensor

Hourmeter

TC-900

Log

TC-900

Log

Connection 115 Vac

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

 S1

D2

 S2

C

O

M

P

D

E

FR

115 Vac

FA

N

S / 

D

E

FR 2

A

B

SITRAD

D1/S3

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

230 Vac

C

O

M

P

D

E

FR

FA

N

S / 

D

E

FR 2

Connection 230 Vac

D2

A

B

SITRAD

 S1

 S2

D1/S3

The 

sensor S1

 

(black)

 must be in the ambient.

The 

sensor S2

 

(gray)

 must be placed in the evaporator 

through metallic cramp.

LEGEND:

 

To the terminal     of 
the connecting block

Connection 12 Vac/dc

1

5 6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

C

O

M

P

D

E

FR

FA

N

S / 

D

E

FR 2

12 Vac/dc

D2

A

B

SITRAD

Loads supply

 S1

 S2

D1/S3

1

5

Connection 24 Vac/dc

6 7 8

2 3 4

9

10 11 12 13 14 15 16 17

C

O

M

P

D

E

FR

FA

N

S / 

D

E

FR 2

24 Vac/dc

D2

A

B

SITRAD

 S1

 S2

D1/S3

Loads supply

E251415

COMPONENT

Have this manual in the palm of 

your hand by

 FG Finder

 application.

TC900ELOGV03-01T

-16578

Pressed for 5 seconds: turn on/turn off the control functions.

;

FAST FREEZING (ON/OFF)

;

TC-900

e

 

Log

 

;

ECONOMIC SETPOINT (ON/OFF)

TC-900

e

 

Log

 

;

DEFROST (ON/OFF)

TC-900

e

 

Log

  

;

FUNCTIONS LOCKDOWN

TC-900

e

 

Log

 

;

CONTROL FUNCTIONS
SHUTDOWN (ON/OFF)

TC-900

e

 

Log

 

NORMAL SETPOINT

;

TC-900

e

 

Log

 

ERASE MIN. AND MAX.
VALUES

;

TC-900

e

 

Log

   

EXIT FUNCTION

;

TC-900

e

 

Log

 

ECONOMIC SETPOINT

;

TC-900

e

 

Log

 

FUNCTION SELECTION

;

TC-900

e

 

Log

 

MIN. AND MAX. 
TEMPERATURE RECORD

;

TC-900

e

 

Log

 

DISPLAY TIME AND DATE

TC-900

e

 

Log

 

;

ON/OFF DATA LOGGER
(MANUAL MODE)

TC-900

e

 

Log

 

;

;

TC-900

e

 

Log

 

DISPLAY HOURMETER

RESET HIGH AND LOW
PRESSURE ALARMS

;

TC-900

e

 

Log

 

Summary of Contents for TC-900EL Log

Page 1: ...cess Short touch displays the maximum and minimum measurements recorded Hold down for 10 seconds manual datalogger activation Hold down for 2 seconds inhibits the audible alarm Hold down for 2 seconds...

Page 2: ...trolfunctionsandleavetheadjustmentofthesetpoint enabled F62 1 Toactivatethefunctionslock accessthe LOC optioninthequickaccessmenu 6 3 9 Control Functions Shutdown The shutdown of the control functions...

Page 3: ...ctive the controller will show the message LOC in the display uponpressing or andwillnotallowadjustingtheparameters 6 4 4 Date and time adjustment Select the option ClO in the main menu The controller...

Page 4: ...F min F F sec x10h min sec sec sec mim mim 58 0 NO 1 1 0 0 0 NO 0 0 NO 58 1 NO 0 NO 32 NO 1 0 NO 0 NO 32 0 NO 0 OFF 0 OFF 0 OFF 36 OFF 36 0 0 15 0 NO 0 0 NO 0 0 0 30 1 1 221 999 99 99 999 999 999 1 99...

Page 5: ...orator temperature does not reach the value adjusted in function F19 or if sensor S2 S3 isdisconnected thefanwillreturnafterthetimeadjustedinthisfunctionhaselapsed F21 Fanoperatingmodeduringrefrigerat...

Page 6: ...ons thatrelyonthereadingofsensorS2willbedisabled F60 S3sensortemperatureindicationoffset It allows compensation for possible deviations in the S3 sensor temperature reading caused by the replacement o...

Page 7: ...ls of eachinstrument Sold Separately CONV 32 or CONV 256 Keep Sitrad updated in website http www sitrad com Serial RS 485 It connects via RS 485 network to the controller only forcontrollersthathaveRS...

Page 8: ...the technical team of Full Gauge Controls Damage has been caused by a fall blow and or impact infiltration of water overload and or atmospheric discharge USE OF WARRANTY To make use of the warranty cu...

Reviews: