F08 - Minimum output-off time:

The minimum time the output will remain off, i.e. the length of time between the last start up and the next 
stop. It relieves the discharge pressure and increases the service life of the compressor.

F09 - Refrigeration time (interval between defrosts):

Corresponds to the time in which the refrigeration function will operate via the controller. When this time 
is up the controller enters the defrost process.

F10 - Defrost time:

This is the defrost duration time. Within this period, the relay will remain off, and upon finishing, the 
controller will go back to the refrigeration state.

F11 - Initial status when turning on the device:

It allows defrosting when controller is turned on.

F12 - Temperature indication locked during defrost:

The real 

time temperature indication will only be released at the next refrigeration cycle after it reaches the 
“locked” temperature value again, or after 15 minutes in refrigeration (as a safety measure).

F13 - Delay in turning on device:

When the device is switched on its control output will remain disabled, delaying the beginning of the 
process. During this time the controller only works as a temperature indicator. The purpose is to avoid 
peaks of electric power demand after a power cut when many devices are connected to the mains. To do 
this, simply set different times for each device. This delay may be either for the compressor or the 
defrost (when the defrost is configured during the startup).

NOTE: 

At its end, the count of minimum time of output off is started, if there is any.

F14 - Additional time to the end of the first cycle:

Aimed at increasing the refrigeration time only in the first refrigeration cycle, increasing the efficiency.

F15 - Compressor state with a disconnected or faulty sensor:

If the room sensor is shorted, disconnected or out of range, the compressor will assume the state 
configured in this function.

[,,,0]

- Compressor off

[,,,1]

- Compressor on

[,,,2]

- Cycling according to times defined in 

[,F16]

 and 

[,F17]

NOTE: 

If the system is in both heating and error mode, the output will be switched off.

F16 - Compressor time on in case of error:

F17 - Compressor time off in case of error:

Sets the minimum time the compressor will remain on/off respectively when the sensor is disconnected 
or out of range.

F18 - Digital filter intensity:

This  filter  has  the  purpose  of  simulating  thermal  mass  increase  in  the  sensor,  thus  increasing  its 
response  time  (thermal  inertia).  The  greater  the  value  set  in  this  function,  the  greater  the  sensor 
response delay will be.

F19 - Time for function lock:

When this function is active, the setpoint and other parameters are protected from undue changes. 
When the controller is locked the user can only view the setpoint and parameters. To lock the functions, 
see item 8.3.3 - Basic Operations, item Function lock.

F20 - Control functions shutdown:

Allows the output to be switched off for maintenance purposes, see item 8.3.4 - Basic Operations, item 
Turning off the control functions.

F21 - Datalogger operating mode:

Indicates how to activate the device that records data in the internal memory:

[,,,0]

- Always off

[,,,1]

- Always on

[,,,2]

- Manual operation

F22 - Time between each sample in the memory:

The time in seconds that the controller takes to record samples of the temperature information and 
refrigeration output state.

F23 - Minimum temperature change to force the writing of data:

The temperature difference in relation to the last piece of data written in the datalogger for the data to be 
recorded in the memory regardless of the sampling time set in 

[,f22]

. To deactivate this function, just 

decrement the value until the message 

[no,,]

 is displayed.

F24 - Output change to force the writing of data:

Indicates  whether  the  change  in  the  control  output  will  force  the  recording  of  data  in  the  memory 
regardless of the sampling time set in 

[,f22]

.

F25 - Overwrite memory?:

This function indicates whether the controller should start writing new data at the beginning of the 
datalogger memory when the memory is full. This function prevents the last data calculated by the 
equipment from being lost.

F26 - Digital input operating mode:

Aims to program the controller with the type of door sensor used in the installation.

[,,,0]

- Off

[,,,1]

- NC door contact

[,,,2]

- NO door contact

F27 - Address of the instrument in the RS-485 network:

Equipment's network address for communicating with Sitrad software.

Note:

 Every single controller within the network must have different address.

This function is aimed at avoiding viewing the room temperature rise due to the defrost cycle. The last 
temperature measured in the refrigeration cycle will be locked in the display during the defrost. 

9. SIGNALS

Error in sensor: Sensor disconnected or damaged.

Control functions turned off.

Manual activation of defrost process.

Manual activation of the refrigeration process.

Function lock.

Function unlock.

[Err1]

[OFF,]

[Defr][On,,]

[defr][Off,]

[LOC,][On,,]

[LOC,][OFF,]

[Open]

[adfl]

[emem]

[ClO,]

[eClO]

[pppp]

[eCal]

Datalogger memory full.

Contact Full Gauge Controls.

Adjustment or visualization of the date and time.

Invalid date and/or time (adjust the clock).

Reconfigure the values of the functions.

Contact Full Gauge Controls.

10. 

INTEGRATING CONTROLLERS, RS-485 SERIAL INTERFACE 

AND COMPUTER

Open door indication.

11. GLOSSARY OF ACRONYMS

- °C: 

Temperature in Celsius degrees.

- °F:

 Temperature in Fahrenheit degrees.

- Refr: 

Refrigeration.

- Defr: 

Defrost.

-

 

Heat.: 

Heating.

- LOC:

 Blocked.

- No:

 No.

- OFF:

 Turned off/disabled.

- ON: 

Turned on, enabled.

- SET (as in "Setting")

 (setting or configuration).

- Vac:

 Electrical voltage (volts) of alternating current.

- Vdc:

 Electrical voltage (volts) of direct current.

- Yes:

 Yes.

12. OPTIONAL ITEMS - Sold Separately

Ecase protective cover

It is recommended for the Evolution line, keeps water from entering the back part of the instrument. It 
also protects the product when the installation site is washed.

ECASE PROTECTIVE COVER

Extended frame

It allows the installation of Evolution line controllers with sizes 76 x 34 x 77 mm in various situations, 
since it does not require precision in the notch of the instrument fitting panel. 
The frame integrates two switches of 10 Amperes that may be used to actuate interior light, air curtain, 
fan, and others.

CONTROLLER

EXTENDED 

FRAME

SWITCHES

A

B

MT-530

super

A

B

MT-530

super

A

A

B

B

A B

A

B

A

A

B

B

A B

A

A

B

B

A B

A

A

B

B

A B

*Connecting Block for Serial Communication

Used to connect more than one instrument to the Interface. The wire's connections must 
be made in agreement with the following rules: terminal 

A

 of the instrument connects to 

the terminal 

A

 of the c

, that must be connected with the terminal 

A

 of the 

Interface. Repeat the action for terminals 

B

 and  

  

, being  

 

 the cable shield.  

onnecting block

the terminal     of  onnecting block must be connected to the respective terminals     of 
each instrument.

c

*Sold Separately

CONV. 32 

or

CONV. 256

 Keep Sitrad updated in website: