Full Gauge MT-512e Log Manual Download Page 3

8.3.8. Manual datalogger activation

The manual activation requires function F21 to be configured with the value 2. By holding down the keys 

 for 10 seconds, it is possible to activate or deactivate the operation of the internal record of 

temperature values and control outputs (datalogger). The message 

[dtL,]

will be shown followed by 

the message

[On,,]

when the datalogger is activated or 

[OFF,]

when it is deactivated. It is also 

possible to activate the datalogger manually through the quick access menu in option 

[dtl,]

.

8.3.9. 

<

 and 

>

Selection of temperature measurament units

To  select  the  temperature  measurament  units  the  system  will  use  to  operate, 
press

<

and

>

simultaneously  while  the  temperature  is  being  displayed,  enter  the  option 

[Code]

using the access code 

[,231]

 and then press

/

.Then select the desired unit 

[,=C,]

 or 

[,=F,]

using the keys

<

or

>

, and press 

/

 to confirm. 

NOTE: 

Whenever the units are changed, the configuration of the functions assume the factory default, 

so they need to be configured again.

8.4.4 Date and time adjustment

When the 

[ClO,]

menu is selected, if the access code 

[123,]

has been entered, the controller will 

enter the date and time adjustment mode. Use

<

or

>

 to change the value and press

/

 when ready 

to save the configured value. If the date entered is invalid, the message 

[ECLO] 

will be shown on the 

display.

Example 1 

(correct access code entered):

[,00d]

-

 

day  

[,00M]

-

 

month  

[,00Y]

-

 

year  

[00:00]

time

minute

flashing

IMPORTANT:

The controller has an auxiliary internal power supply to keep the clock running for at least 72 hours in 
case of a power failure. If the controller remains off for a long period of time, the message 

[ECLO]

may 

be displayed to indicate that the clock is not programmed. In this case, the date and time must be 
adjusted and the controller must be kept on for 10 hours to fully recharge the auxiliary power supply.

8.4. Advanced operations

8.4.1. Access to the main menu

The main menu can be accessed through the quick access menu

, option 

[Func]

or pressing 

and 

>

 simultaneously when the temperature is being displayed.

The following options will be displayed:

[Code]

Entry to the access code

[Func]

Change the advanced parameters

[ClO,]

Adjust or visualization of the date and time

 (

;



8.4.2. Access code

To allow changing the parameters or adjusting the clock, select the option 

[Code]

 by pressing 

/

 

(quick touch) and enter the access code 123 (one hundred and twenty-three) using the keys 

<

 or 

>

 , 

and confirm with

/

.

8.4.3. Changing the controller parameters

In the main menu (after entering the code 123) select the option 

[Func]

 and then the desired function 

using the keys

<

 and 

>

. Press 

/

 (quick touch) after selecting the function to view its value. 

8.4.5. Internal datalogger (internal memory)

When the datalogger is enabled (F21), it is possible to store records in the controller's internal memory. 
It can be configured to store records by time interval (F22), by temperature variation (F23), and/or by the 
variation of the state of the digital output or inputs (F24).

NOTE:

 The equipment records date, time, temperature, and events (sensor error, refrigeration/heating 

output state, defrost output state, and open door sensor).

Desired temperature (Setpoint)*

Sensor indication displacement (Offset)

Minimum setpoint allowed to the end user

Maximum setpoint allowed to the end user

Control differential (hysteresis)

Operating mode

Minimum output-on time

Minimum output-off time

Refrigeration time (interval between defrosts)

Defrosting time

Initial status when turning on the device

Temperature indication locked during defrosting

Delay in turning on device

Additional time to the end of the first cycle

Compressor state with a disconnected or faulty sensor

Compressor time on in case of error

Compressor time off in case of error

Digital filter intensity

Time for function lock

Control functions shutdown

Datalogger operating mode

Time between samples in the memory

Minimum temperature change to force data writing

Output change to force data writing

Overwrite memory?

Digital input operating mode

Address of the instrument in the RS-485 network

[,F01]

[,F02]

[,F03]

[,F04]

[,F05]

[,F06]

[,F07]

[,F08]

[,F09]

[,F10]

[,F11]

[,F12]

[,F13]

[,F14]

[,F15]

[,F16]

[,f17]

[,f18]

[,F19]

[,F20]

[,F21]

[,f22]

[,f23]

[,f24]

[,f25]

[,f26]

[,f27]

Description

Fun

Min

Max

Unit

200

5.0

200

200

20.0

1-heat.

999

999

999

999

1-defr.

yes

240

240

2

999

999

9

60

2

2

999

10.0

yes

yes

2

247

°C

°C

°C

°C

ºC

-

sec

sec

min

min

-

-

min

min

-

min

min

-

sec

-

-

sec

°C

-

-

-

-

CELSIUS

-58

-9

-58

-58

1

0-cool.

no

no

1

no

0-cool.

no

no

no

0

1

1

no

no

no

0

1

0

no

no

no

1

392

9

392

392

36

1-heat.

999

999

999

999

1-defr.

yes

240

240

2

999

999

9

60

2

2

999

18

yes

yes

2

247

°F

°F

°F

°F

°F

-

sec

sec

min

min

-

-

min

min

-

min

min

-

sec

-

-

sec

°F

-

-

-

-

FAHRENHEIT

Min

Max

Unit

Standard

-50

-5.0

-50

-50

0.1

0-cool.

no

no

1

no

0-cool.

no

no

no

0

1

1

no

no

no

0

1

0

no

no

no

1

39

0

-58

167

2

0-cool.

20

20

240

30

0-cool.

no

no

no

0

15

15

no

no

no

2

30

0

no

yes

no

1

4

0

-50

75

1.0

0-cool.

20

20

240

30

0-cool.

no

no

no

0

15

15

no

no

no

2

30

0

no

yes

no

1

8.5 Parameters table

Use

<

 or 

>

 to change the value and press

/

 when ready to save the configured value and return to 

the function menu. To leave the menu and return to the normal operating mode (temperature indication), 
hold down

/

 (long touch) until

[----]

appears.

NOTE: 

If the function lock is active, the controller will show the message 

[LOC,]

 , in the display upon 

pressing

<

 or 

>

 and will not allow the adjustment of the parameters.

Legend:

[yes,]

= yes

             

[no,,]

= no

*The minimum and maximum values depend on the values configured in 

[,F03]

and

[,F04]

.

F01 - Desired temperature (Setpoint):

The reference value for temperature control, that is, the temperature to be maintained in a controlled 
environment.

F02 - Sensor indication displacement (Offset):

Compensates for any deviations in temperature reading caused by sensor exchange or alterations in 
the cable length.

F03 - Minimum setpoint allowed to the end user:

A threshold aimed at preventing an exceedingly low temperature setpoint from being inadvertently 
adjusted. 

F04 - Maximum setpoint allowed to the end user:

A threshold aimed at preventing an exceedingly high temperature setpoint from being inadvertently 
adjusted.

F05 - Differential control (hysteresis):

The  difference  in  temperature  (hysteresis)  between  TURNING  ON  and  OFF  the  refrigeration  (or 
heating).

Example: 

One wants to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the 

refrigeration is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0), in the heating mode the 
output is switched off at 4° C is switched on again at 3° (4.0 - 1.0), as per the charts below:

8.5.1. Parameters description

Temperature [°C]

Refrigeration

Temperature [°C]

Heating

Setpoint

Se Hysteresis

Time [S]

Relay Off

Relay On

4°C

5°C

Setpoint

Setpoint - Hysteresis

Time [S]

3°C

4°C

Relay Off

Relay On

F06 - Operating mode:

Allows selecting the controller operation mode.

[,,,0]

- Refrigeration

[,,,1]

- Heating

NOTE: 

In the heating mode functions F09, F10, F11 and F12 are disregarded.

F07 - Minimum output-on time:

The minimum time the output will remain on, i.e. the length of time between the last start up and the next 
stop. It is aimed at avoiding high voltage surges in the power lines.

Standard

Reviews: