This is the temperature difference in the current setpoint to activate the alarm (buzzer) for
LOW temperature.
Example: Setpoint =
[,,3.0]
,
[,f66]
=
[,,2.0]
. In this case, the alarm will only be
activated if the room temperature is lower than
[,,1.0]
(
[,,3.0]
-
[,,2.0]
).
This is the temperature difference in the current setpoint to activate the alarm (buzzer) for
HIGH temperature.
Example: Setpoint =
[,,3.0]
,
[,f67]
=
[,10.0]
. In this case, the alarm will only be
activated if the room temperature is higher than
[,13.0]
(
[,,3.0]
+
[,10.0]
).
When the door is opened, the
[OPEN]
message will appear on the display and the open
door timer starts. If this time is longer than the set time with this function, the audible alarm
(buzzer) will be activated.
0.1 (1)
50.0 (90)
ºC (ºF)
0.1 (1)
50.0 (90)
ºC (ºF)
[no,,]
999
Minimum room temperature alarm relative to the
setpoint
Maximum room temperature alarm relative to the
setpoint
Door opening time until the alarm is activated
10.0 (18)
50.0 (90)
min.
1
[,f75]
[no,,]
2
-
[no,,]
When control functions are shutdown, the controller starts to operate purely as a
temperature indicator, with all outputs deactivated. This function can operate in the
following ways:
[no,,]
Does not allow the control functions shutdown.
[,,,1]
Allows turning on and off of control functions only if the functions are unlocked.
[,,,2]
Allows turning on and off of control functions even if the functions are locked.
Note: To activate or deactivate the control, please refer to item 9.2
[,f70]
[,f71]
[,f72]
[,f74]
This function is used to stop the alarm for a certain period, due to a possible increase in
temperature
During the time set in this function, the alarm remains off, waiting for the system to start
working.
When defrost is concluded by time and not by temperature, the user is alerted by a blinking
dot on the lower right corner of the display (
[,,,,*]
).
With this function enabled, setups are protected against unauthorized changes, and are
available for viewing only. In this state, when trying to change these values, a
[LOC,,]
message will be displayed.
Note: To activate or deactivate the functions lock, please refer to item 9.3
[no,,]
999
min.
[no,,]
999
min.
[Off,]
[On,,]
-
15
60
sec.
[no,,]
[no,,]
[On,,]
15
Temperature alarm delay
Alarm delay when powering the controller
Indication to defrost terminated by time
Time for functions lock
Control functions shutdown
[,f73]
It allows and configures the functions lock; this function may operate in the following ways:
[no,,]
Does not allow functions lock
[,,,1]
Allows a partial lock, where the control functions will be locked but the change of
presets is allowed.
[,,,2]
Allows a full lock leaving only the access to the functions of the quick access menu
available.
Note: To activate or deactivate the functions lock, please refer to item 9.3
2
-
2
Functions Lock
[,f63]
[,f64]
If the room sensor (sensor S1) is disconnected or out of its measuring range, the
compressor will turn on and off according to the setup configured in these functions.
0
999
min.
20
0
999
min.
10
Compressor ON time in case of error on sensor S1
(room)
Compressor OFF time in case of error on sensor S1
(room)
When the instrument is switched on, the compressor will be kept off for some time, thus
delaying the beginning of the process. The purpose of this is to avoid peaks in electric power
demand when power returns after a power fault and many devices are connected to the
same mains. To do this, just set different times for each device.
[,f65]
[no,,]
999
min.
2
Compressor delay time when powering the
controller
[,f66]
This is the alarm that indicates when the compressor is active for longer than the configured
time set by this function, without reaching the setpoint.
[no,,]
999
H
[no,,]
Maximum time of compressor operation without
reaching the desired temperature (setpoint)
[,f58]
[,f59]
[,f60]
[,f61]
[,f62]
This setup defines when power-saving mode will be activated with the door closed. The light
output will be deactivated if it is ON and the operation setpoint will control the system
according to the power-saving setpoint
This allows you to set a maximum operating time for power-saving mode while the door is
closed. After this time, the setpoint returns to the normal operating mode. This time is
calculated in hours.
This function aims at preventing products from freeze after a period of closed door.
This is the minimum time the compressor will remain turned off, i.e. time between its last
deactivation and the next activation. It helps to relieve the discharge pressure and increase
the lifespan of the compressor.
This is the minimum time the compressor will remain on, i.e. time between the last activation
and the next deactivation. It helps to prevent high voltages within the power grid.
[no,,]
999
min./H
2
[no,,]
999
H
[no,,]
[no,,]
999
min./H
[no,,]
[no,,]
999
min.
[no,,]
[no,,]
999
min.
[no,,]
Time of door closed for activation of power-saving
mode
Maximum time on power-saving mode with the door
closed
Time of closed door for activation of antifreeze
safety differential temperature
Minimum time with compressor OFF
Minimum time with compressor ON
[,f57]
This setup defines when the light will be turned off with the door closed. It contributes
towards power saving.
[no,,]
999
min./H
2
Time of door closed for turning the ligths off
[no,,]
DESCRIPTION
FUN
MIN
MAX
UNIT.
DEFAULT
CELSIUS (FAHRENHEIT)
FUNCTION