Reason:
Out of gas, the controller does not detect a flame.
Measure:
First check if there is gas available for the oven to operate.
Check the presence of flame and the distance between the flame sensor and the burner.
Other possibilities for this failure are: flame sensor disconnected or dirty / oxidized, damaged
ignition module or gas valve.
9.4 Other signaling
Controller in Economic mode. The controller was idle for the time adjusted in F22 - Economic
Mode. To leave this mode, press
or open the oven door.
dddd
Note:
This message is displayed alternately with the oven temperature.
Indicates that the oven door is open.
Note:
The message keeps flashing on the lower display.
Requests for the operator to close the oven door. Indicates that the
door remained open for the time configured in parameter F05. In
this mode the controller switches off the heating and activates the
audible alarm.
Note:
The message keeps flashing on the lower display.
SET
Reason:
Fan overheating, its temperature has exceeded the rated temperature of the termal
protection PTC sensor.
Measure:
Check the operation of the fan and respective temperature sensor.
Note:
If the thermal protection sensor is not used, connect terminals 3 and 4 with a
connection and / or deactivation parameter
[i08]
- Enable fan thermal protection.
Manual turbine shutdown not allowed.
The message will be displayed if turbine shutdown is attempted while the timer is active.
Indicates that the turbine of the oven is temporarily off. To restart
the turbine, press
<
for 4 seconds or activate the timer.
Note:
The message keeps flashing on the lower display.
10.1.2 Oven: gas
10.1.3 Oven: wood
PRECAUTIONS WHEN INSTALLING THE PRODUCT:
10.1.1 Oven: eletric
Before performing any procedure on this instrument, disconnect it from the power grid;
Ensure that it has adequate ventilation, avoid installation on control panels containing devices that could
cause it to operate outside its specified temperature range;
Install the product away from sources that may generate electromagnetic disturbances, such as:
motors, contactors, relays, solenoid valves, etc.
IMPORTANT:
It is crucial to install the ignition module next to the burner and as far as possible from the electronic
controller;
The ignition electrode must be installed at a distance of 5 mm from the burner;
The flame sensor must be installed at a distance of 5 mm from the burner and at least 5 mm from the
ignition electrode.
1 2 3 4
Fan
PTC
J or K
Thermocouple
E1:
Door micro switch input
B1:
External audible alarm (buzzer)
18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1
Check the controller model
RESIST
ANCE 2
FAN 2
FAN 1
LIGHTBULB
STEAM
E1
B1
RESIST
ANCE 1
*
Fan PTC:
R
TN
= 1000
Ω
R
TN
(T
N
- 5K) = max 550
Ω
R
TN
= Resistance at rated
temperature
P
+
12~24Vac / Vdc
-
85~240Vac
N
1 2 3 4
Fan
PTC
J or K
Thermocouple
E1:
Door micro switch input
E2:
Flame sensor
B1:
External audible alarm (buzzer)
Q:
Burner
18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1
GAS 2
FAN 2
FAN 1
LIGHTBULB
IGNITION
STEAM
GAS 1
E1
Q
E2
B1
Check the controller model
*
Fan PTC:
R
TN
= 1000
Ω
R
TN
(T
N
- 5K) = máx 550
Ω
R
TN
= Resistance at rated
temperature
+
12~24Vac / Vdc
-
P
85~240Vac
N
1 2 3 4
Fan
PTC
J or K
Thermocouple
18 17 16 15 14 13 12 11 10
9 8 7 6 5 4 3 2 1
AL
ARM 2
FAN 2
FAN 1
LIGHTBULB
STEAM
AL
ARM1
Check the controller model
*
Fan PTC:
R
TN
= 1000
Ω
R
TN
(T
N
- 5K) = máx 550
Ω
R
TN
= Resistance at rated
temperature
+
12~24Vac / Vdc
-
P
85~240Vac
N
E1
B1
E1:
Door micro switch input
B1:
External audible alarm (buzzer)
10. INSTALLATION
12. EasyProg* - version 02 or later
11. DIMENSIONS
10.1 Electrical connections
75,6
75,4
Panel openings
67,2 mm
67,2 mm
25 mm
10 mm
Packaging:
Materials used in the packaging of the Full Gauge products are 100% recyclable. Be sure to dispose of using specialized recycling
facilities.
Product:
The components used in the Full Gauge controllers may be recycled and reused if disassembled by specialized companies.
Disposal:
Do not incinerate or dispose of the controllers that reached the end of their service life in household waste. Be sure to comply with
the existing legislation in your area relating to disposal of electronic waste. In the event of doubt, please contact Full Gauge
Controls.
ENVIRONMENTAL INFORMATION
67
100,3
75
80
84,8
Side view
Front view
WARRANTY - FULL GAUGE CONTROLS
Products manufactured by Full Gauge Controls, as of May 2005, have a two (2) - year waranty directly with the factory and
one (1) year before the reseller network, counted as of the date of consigned sale as stated on the invoice. After this said year
before the reseller network, the warranty shall continue to be executed if the instrument is sent directly to Full Gauge Controls.
The products are warranted in case of defects in workmanship making them unsuitable or inadequate to the intended
applications. The warranty is limited to maintenance of instruments manufactured by Full Gauge Controls, disregarding other
kinds of expenses, such as indemnity for damages caused to other equipment.
EXCEPTIONS TO WARRANTY
The Warranty does not cover expenses incurred for freight and / or insurance for sending the products with signs of defect
or malfunctioning to the provider of technical support services. The following events are also excluded from warranty: natural
wear and tear of parts, external damages caused by falls or inadequate packaging of products.
INVALIDATION OF WARRANTY
The product warranty shall lose validity, automatically, if:
- The instructions for use and assembly contained in the technical description and the installation procedures described in
Standard NBR5410 are not followed;
- The product is submitted to conditions beyond the limits specified in its technical description;
- The product is violated or repaired by a person not integrating the technical team of Full Gauge;
- The damages are due to a fall, blow and / or impact, water damage, overload and / or atmospheric discharge.
USE OF WARRANTY
For use of the warranty, the customer should send the adequately packaged product, along with the respective Invoice to
Full Gauge Controls. The customer will bear the freight cost for sending of the products. Also, as much information as possible
with regard to the defect verified should be sent, in order to facilitate the analysis, the testing and the performance of the
service.
These processes and any product maintenance shall only be performed by the Technical Support Services of Full Gauge
Controls, at the Company headquarters - Street Júlio de Castilhos, 250 - CEP 92120-030 - Canoas - Rio Grande do Sul - Brazil.
Rev. 03
Copyright 2018
It is an accessory the main function of which is to store the parameters of
controllers. At any time you can load new parameters of a controller and unload
them on a production line (of the same controller), for example.
It is provided with three types of connections for loading or unloading the
parameters:
-
Serial RS-485:
It is connected via RS-485 network to the controller (only for those
controllers provided with RS-485).
- USB:
It is connected to the computer via USB port, using the Sitrad Preset Editor.
- Serial TTL:
The controller may be connected directly to EasyProg via Serial TTL
connection.
EASYPROG