10. INTERCONNECTING CONTROLLERS AND SITRAD INBOX
10.1 FOR A ROBUST ELECTRICAL INSTALLATION, OBSERVE THE FOLLOWING RECOMMENDATIONS:
- Use a 2-way cable, minimum 24 AWG;
- Preferably, use cables with mesh shielding to protect the communication line from outside interference;
- Avoid splicing the cable;
- Use terminal blocks to connect controllers. Besides facilitating the connection, they have a protection feature;
- Avoid connections longer than 2 meters between the connection block and the controller;
- Use a maximum of
32 devices
connected to each Interface.
32 controllers
32 controllers
MT-530
super
MT-530
super
MT-530
super
MT-530
super
CONVERTER
RS-485
POWER
STATUS
TX
RX
CONVERTER
RS-485
POWER
STATUS
TX
RX
- Size networks with maximum length of
1000 meters
between the Interface and the last controller.
Maximum cable distance = 1000 m
MT-530
super
MT-530
super
CONVERTER
RS-485
POWER
STATUS
TX
RX
- Connect a 120 ohm terminating resistor between terminals
A
and
B
of the terminal block at the end of the line when using a cable length greater than
100
meters
.
MT-530
super
!
Merely illustrative images