Full Gauge Controls MT-514 E Faston Quick Start Manual Download Page 4

F24 - Low temperature alarm:

It is the temperature below that which the instrument will visually display the low temperature alarm 

[atlo]

 as well as the audible alarm (Buzzer). The differential for switching off the alarm is fixed at 

0.1°C / 1°F. This alarm considers the temperature shown on the display, thus being influenced by the 
temperature indication that was locked during the defrost 

[,f18]

. To disable this alarm, simply set this 

function to the minimum value until 

[,,no] 

is displayed.

F25 - High temperature alarm :

It is the temperature above that which the instrument will visually display the high temperature alarm

  

[athi]

 as well as the audible alarm (Buzzer). The differential for switching off the alarm is fixed at 

0.1°C / 1°F. This alarm considers the temperature shown on the display, thus being influenced by the 
temperature indication that was locked during the defrost 

[,f18]

. To disable this alarm, simply set this 

function to the maximum vale until 

[,,no]

 is displayed.

Note:

 For safety, output OUT1 is switched off if the controller is configured for heating and a high 

temperature  alarm 

[athi]

  occurs,  or  if  it  is  configured  for  cooling  and  a  low  temperature  alarm 

[atlo]

 occurs, therefore, you must set the alarm limits above (if heating) or below (if cooling) the 

desired temperature (setpoint of output OUT1).

F26

 

- Output OUT2 operation mode :

Select the operating mode of the OUT2 output.

[,,,1]

- Extra alarm-absolute range

: It considers the values defined in

[,F24]

 and 

[,F25]

as 

minimum and maximum values to trigger the alarm output.

[,,,2]

- Extra alarm-setpoint range: 

It considers the active receipt setpoint 

[Rc1,]

 or 

[Rc2,]

 

and the absolute values defined in

[,F24]

 and 

[,F25]

, that is, the positive value of these functions 

as minimum and maximum values to trigger the alarm output.

For example:

Desired temperature

 [SP,,]

: - 5ºC

Low temperature alarm 

[,F24]

: 2ºC

High temperature alarm 

[,F25]

: 2ºC

City Limits: (

[SP,,]

-

 [,F24]

 and 

[SP,,]

[,F25]

).

The low temperature alarm will go off at -7°C (-5-2) and the high temperature alarm at -3°C (-5+2).

[,,,3]

- Electric defrost (using resistances): 

Where only the OUT2 output is activated during the 

defrost process.

[,,,4]

- Hot gas defrost 

: Where the compressor outputs OUT1 and OUT2 are activated during the 

defrost process.

[,,,5]

- Output OUT2 as NF

 

of output OUT1

: In this option, the OUT2 output is activated when the 

OUT1 output is deactivated, regardless of the state (cooling / heating or defrost), except when the 
sensor is in error 

[,F20]

.

[,,,6]

- OUT2 output as ventilation

: While the controller is cooling, the output reamins in operation 

accodingly to the configuration selected in function 

[,f27]

 - Fan operation mode during cooling and 

remains on during the defrost duration time. 

[,,,7]

- OUT2 output as an auxiliary compressor

: The output is used to start a second compressor. 

Output OUT2 is activated immediately after output OUT1 is activated or according to

 [,F31]

 - Time 

delay between compressors activations.

Note 1:

 

If the OUT2 output is configured to work different than an alarm, the absolute alarm indications 

are still visual (messages on the display) and audible (if the buzzer is enabled)

Note 2:

 If the OUT2 output is configured for defrost (electric or hot gas), after the defrost time has 

elapsed, a fixed time of 2 minutes is counted for drainage. During this dripping time, outputs OUT1 and 
OUT2 remain off.

Note 3:

 If output OUT2 is configured for ventilation, and if a sensor error occurs, output OUT2 will be 

activated  and  deactivated  together  with  output  OUT1,  that  is,  if  OUT1  is  activated  OUT2  remains 
activated,  and  will  continue  to  work  together  according  to  the  configuration  selected  in  function 

[,F20]

 - Compressor status with the sensor disconnected.

Note 4:

 If OUT2 output is configured as ventilation and function

 [F35]

 (Digital input operating mode) 

is configured as 1 or 2 (door open), OUT2 output will be turned off whenever the door is opened and 
turned back on when closing the door. If the door remains open for the time defined in 

[F38]

 (Door 

open time to issue alarm), the OUT1 and OUT2 outputs will remain off while the door is open and will be 
turned back.

F27 - Fan operation mode during cooling:

Selects the operating mode of the OUT2 output when 

[,F26]

 = 6.

[,,,0]

 - OUT2 output remains activated as long as OUT1 output (compressor) is activated. When the 

compressor  is  off  by  setpoint,  the  OUT2  output  cycles  according  to  the  values  configured  in  the 
functions 

[,F28]

 - Fan Time On and 

[,F29]

 - Fan Time Off;

[,,,1]

 - OUT2 output remains on regardless of output OUT1;

[,,,2]

 - OUT2 output remains on as long as OUT1 output is on and off when OUT1 output is turned 

off.

F28 - Fan On Time:
F29 - Fan Off Time:

Define fan on time 

[,F28]

 and fan off time

[,F29]

 during the off-cycle when 

[,f04] 

= 0, 

[,f26]

 

= 6 and 

[,F27] 

= 0

F30 - Fan Delay:

Defines the time (delay) before activating the OUT2 output (if configured as fan 

[,F26]

 = 6) after the 

start of a new refrigeration cycle.

F31 -Time delay between compressors activations:

Defines  the  time  (delay)  before  activating  the  OUT2  output  (if  configured  as  auxiliary  compressor 

[,F26]

 = 7). Every time the OUT1 output is activated, the time configured in this function will elapse 

before activating the OUT2 output.

F32 - Alarm inhibition time when powering up the controller:

 

This is the time during which the alarm remains off even under conditions of alarm during the instrument 
start-up. This time will be counted after elapsing of the time configured in 

[,F19]

. This function can be 

switched off by setting it at the minimum value 0 

[no,,]

.

F33 - Alarm inhibition time by room temperature:

 

With this configuration active, the temperature will need to remain in the alarm condition during the 
inhibition time set, for the alarm to be indicated. That way one can prevent alerts resulting from specific 
temperature variations, and after defrost.

F34 - Enable buzzer (0-Disabled/1-Enabled):

Allows enabling and disabling of the internal buzzer for alarm signaling.

F35 - Digital input operation mode: 

Select the operatiing mode of the digital input.

[no,,]

- Disabled 

[,,,1]

- Digital input: Door open (active when closing contact)

[,,,2]

- Digital input: Door open (active when opening contact)

[,,,3]

- Digital input: External alarm / power failure (active when closing contact)

[,,,4]

- Digital input: External alarm / power failure (active when opening contact)

[,,,5]

- Digital input: Door open and power failure (active when closing contact)

[,,,6]

- Digital input: Door open and power failure (active when opening contact)

[,,,7]

- Digital input: Push-button type switch (button) to manually start/stop defrost

[,,,8]

- Digital input: Push-button type switch (button) to switch the control functions off or on

F36 - Output on time in OUT2 alarm status:
F37 - Output off time in OUT2 alarm status:

Selects the cycling time in seconds of the alarm output when it is active. If any of those functions are set 
with a value of 

[,,,0]

 the output will be permanently active.

 

F38 - Door open time to trigger alarm:

 

If the door remains open for a time equal to, or greater than, the one configured in this parameter, the 
controller will set off a visual open door alarm

 

[AOPn]

 and the audible alarm (Buzzer).

The alarms are suspended upon the door closing. The audible alarm may be inhibited through the 

>

 

key (pressed for 2s). This function can be switched off by setting it at the minimum value 0 

[no,,]

.

Note 1:

 In order for the open door alarm to operate, the function “Digital input operating mode” 

[,F35]

 

must be configured as open door contact.
The audible alarm is activated only if the buzzer is enabled in the function “Enable Buzzer (0-Disabled 
/1-Enabled)” 

[,F34]

.

Note 2:

 If the function “Digital input operating mode” 

[,F35]

 is configured as open door contact, the 

open door indication 

[OPEn]

 will be displayed every time the door is open, except for the cases of 

alarm.

F39 - Sensor digital filter intensity:

[,,,0]

- The filter acts both on the rise as on the decrease temperature.

[,,,1]

- The filter acts only in the temperature rise ramp. When the temperature falls, your response 

will be immediate.

F40 -Intensity of the digital filter applied to the sensors:

This filter has the purpose of simulating increase in thermal mass at the sensor thereby increasing its 
response time (thermal inertia). The higher the value set in this function, the more time the sensor takes 
to respond.
This function can be switched off by setting it at the minimum value 0

[no,,]

.

F35 =

[,,,3]

1

5 6

2 3 4

SENSOR

NC

NC

Vca

A1

A2

F35 =

[,,,4]

1

5 6

2 3 4

SENSOR

NO

NO

Vca

A1

A2

Examples of connection for detecting open door alarm:

This configuration may be used for the

 

MT-514

e

 Faston

 

to detect whether the door has been left 

open for a time above the value set up in “

[,F33]

 - Time with open door to trigger alarm”. In this 

configuration, the message 

[AOPn]

 is displayed when an open door alarm is detected. To that end, the 

user may use the NO or NC pushbuttons (not supplied) connected to the digital input, as shown in 
examples below:

F35 =

[,,,1]

1

5 6

2 3 4

SENSOR

NC

Door contact

F35 =

[,,,2]

1

5 6

2 3 4

SENSOR

NO

Door contact

Examples of connection for power outage detection:

This configuration may be used when 

MT-514

e

 Faston

 is being energized by a 12/24 V DC 

battery (common in vaccine refrigerators) and one wants to detect when a power outage occurred 
(115/230 V AC). In this configuration, the message

[AVoL]

 is displayed when alarm is detected for 

power outage. To that end, the user may utilize a contactor or auxiliary contact (not supplied), where NC 
(

[,F30]

=

[,,,3]

)  or  NO  (

[,F30]

=

[,,,4]

)  contacts  are  connected  to  the  digital  input  and 

contacts A1 and A2 (contactor coil) are connected to the power system, as shown in examples below:

Example of connections for detecting open door and power outage:

This configuration may be used to detect power outage alarm (115/230 V AC) and also to detect that the 
door has been left open (either one event).
In those configurations, the messages 

[AVoL]

 and 

[AOPn]

are displayed alternately when alarm 

event is detected (power outage or open door alarm).
For this purpose, the user may use the pushbuttons (not supplied) and a contactor or auxiliary contact 
(not supplied) connected in series or in parallel, as shown in examples below:

F35 =

[,,,6]

Serial connection

1

5 6

2 3 4

SENSOR

NO

NO

Vca

A1

A2

NO

Door contact

F35 =

[,,,5]

Parallel connection

1

5 6

2 3 4

SENSOR

NC

NC

Vca

A1

A2

NC

Door contact

Reviews: