6.3 DESCRIPTION OF PARAMETERS

[Code]

– Access code (123):

Required when you want to change the advanced configuration parameters. This code is not required 
to only view the set parameters.
 

[,F01]

 

– Thermostat control logic:

Sets the operating logic of the thermostat.

[Cool]

– Cooling.

[Heat]

– Heating.

 

[,F02]

 

– Thermostat temperature hysteresis (

[TEMP]

 parameter):

Temperature difference to turn on the thermostat. This function allows you to define a temperature 
range within which the output will remain off.

For example: If set to 

[temp]

=

[,45.0]

,

[,f02]

=

[,,2.0]

 and 

[,f01]

=

[heat]

 the thermostat 

output will be turned off when the T1 sensor temperature reaches 45.0 °C, and will only turn on when 
this falls below 43.0 °C (45.0-2.0=43.0).

 

[,F03]

 – Minimum allowable setting for the thermostat temperature:

[,F04]

 – Maximum allowable setting for the thermostat temperature:

These parameters serve as upper and lower limits for adjusting the 

[TEMP]

 parameter (thermostat 

heating temperature). They are used to block temperature adjustment so as to prevent an inappropriate 
configuration, for example. A high value could mean the thermostat output stays on for a long time, 
resulting in high power consumption.
 

[,F05]

 

– Thermostat manual override time:

Used when you wish to activate the output outside the hours set in the events schedule. When using 
manual override, the thermostat returns to AUT (automatic) mode after the time programmed in this 
parameter. To disable this function, move the setting to the minimum until

[,,No]

 appears.

 

[,F06]

 

– Events schedule operating mode:

Sets the operating mode of the events schedule:

[,1b1]

 – Weekly Programming – in this mode, the instrument can set up to 4 different 

events for each day of the week.

[,2t6]

 – Weekday Programming – in this mode, the instrument keeps events the same on 

weekdays (Monday to Friday) and allows you to program different events for Saturday and 
Sunday.

[,1t7]

 – Daily Programming – in this mode, the instrument keeps the events the same for 

every day of the week.

Note:

 When changing the mode of the events schedule, the controller loads the events with 

default values.

 

[,F07]

 

– Thermostat output linked to the events schedule:

This option lets you link the operation of the thermostat output to the events schedule.

[,OFF]

– the thermostat output is controlled only by temperature.

[,,ON]

– the thermostat output is controlled by temperature and by the events schedule.

Note:

 If set to OFF, the controller will indicate AUT for the thermostat mode.

 

[,F08]

 

– Thermostat temperature in economy mode:

Determines the temperature setpoint that the controller uses as a reference when in AUT mode and no 
event is active or when Holiday mode (OFF) is selected. This feature is preferably used for floor heating 
applications where, outside the ranges defined in the events schedule, the temperature control takes 
on a setpoint with a lower value in order to maintain the floors pre-heated and enable rapid heating of 
the environment when necessary. 
To  disable  this  function,  move  the  setting  to  the  minimum  until 

[,,No]

  appears,  turning  off  the 

temperature control in Holiday mode or when no event is active, a mode preferably used to heat thermal 
reservoirs.

[,f09]

 - Recirculation - Scan time (if F01 = Heat):

Time  during  which  the  controller  keeps  the  water  circulation  activated  to  equalize  the  water 
temperature in the keg.
This function can be switched off by setting it at the minimum value 0 

[no,,]

.

[,F10]

 - Interval between scans (if F01 = Heat):

It is the interval between the last and the next temperature scan.

NOTE:

 If the temperature to switch on the thermostat is reached the scan cycle is restarted.

[,F11]

 - Maximum time the thermostat output remains on without reaching the setpoint (if F01 

= Heat):

It is the maximum time the thermostat output will remain on without reaching the setpoint during the 
heating process. When this time is exceeded, the thermostat output is turned off according to the time 
set in 

[,f12]

. Functions 

[,F12]

 and 

[,F13]

 serves as protections for the gas-fired heater so that 

in  the  event  of  fault  (flame  out  for  instance),  the  water  circulation  is  interrupted  and  the  heater  is 
switched off to protect it.
This function can be switched off by setting it at the minimum value 0 

[no,,]

.

6.4 UNIT SELECTION

To define the temperature unit with which the instrument is going to operate you should 
access the 

[Code]

 function (see article 6.1 to find out how to access this function), insert 

the 231 code and press the key. The user may select the unit by pressing the keys      or    , 
where the messages 

[,=C,]

or

[,=F,]

are alternated. Press the 

SET

 key to confirm 

the  desired  unit.  Next  the  message

[----]

will  be  displayed  and  the

{

or 

}

icons 

corresponding to the unit will be turned on.

Obs.:

 While changing the unit, the controller carries the factory values in its parameters, 

[,FAC]

, being necessary to perform their setting.

 

7. SIGNALS

- Motive: 

Sensor 1 disconnected or out of the specified range.  

- Motive: 

Dis-programmed clock due to prolonged energy absence.

- Corrective measures: 

Check the connections and sensor operation.

- Corrective measures:

 Adjust time and day, see article 5.5.

am

- Motive: 

Manual

 

thermostat activation with parameter settings

[,F05]

=

[,,no]

.

- Corrective measures: 

Set parameter value F05 - Time of manual

thermostat activation.

- Motive: 

Attempted exchange the mode of thermostat with parameter 

adjustment

 

[,F07]

 = 

[,OFF]

.

- Corrective measures: 

Check parameter F07 – Thermostat output 

linked to the events schedule

6.2 TABLE OF PARAMETERS

Min

Max

Unit

Min

Max

Unit

Standard

CELSIUS

FAHRENHEIT

 Fun

[CoDE]
[,F01]
[,F02]
[,F03]
[,F04]
[,F05]
[,F06]
[,F07]
[,F08]
[,F09]
[,F10]
[,F11]
[,f12]
[,f13]
[,f14]
[,f15]

Standard

Description

Access code
Thermostat control logic
Thermostat temperature hysteresis
Minimum allowable setting for the thermostat temperature (TEMP parameter)
Maximum allowable setting for the thermostat temperature (TEMP parameter)
Thermostat manual override time
Events schedule operating mode
Thermostat output linked to the events schedule
Thermostat temperature in economy mode 
Recirculation - Scan time
Interval between scans
Maximum time the thermostat output remains on without reaching the setpoint
Thermostat output off time in state of alarm for not reaching the setpoint
T1 Sensor indication displacement (Offset)
Function lock time
Intensity of the display backlight

0

Cool

0.1
-50
-50

no (0)

1b1

Off

no (-11)

no (0)
no (0)
no (0)
no (0)

-5.0

no (3)

Eco (0)

999

Heat

20.0

105
105
600

1t7
On

30.0

999
999
120
120

5.0

30
10

-
-

ºC
ºC
ºC

min

-
-

ºC

min.
min.
min.
min.

ºC

s

-

0

Heat

2.0
0.0

50.0

120

1t7
On

no

no (0)
no (0)
no (0)
no (0)

0.0

10

Eco (0)

0

Cool

1

-58
-58

no (0)

1b1

Off

no (12)

no (0)
no (0)
no (0)
no (0)

-9

no (3)

Eco (0)

999

Heat

36

221
221
600

1t7
On

86

999
999
120
120

9

30
10

-
-

ºF
ºF
ºF

min

-
-

ºF

min.
min.
min.
min.

ºF

s

-

0

Heat

3

32

122
120

1t7
On

no

no (0)
no (0)
no (0)
no (0)

0

10

Eco (0)

- C

  orrective measures: 

Contact the technician responsible for 

installation.

[,F12]

 - Thermostat output off time in state of alarm for not reaching the setpoint (if F01 = 

Heat):

It allows adjusting the time for which the controller will keep the thermostat output off while in state of 
alarm for not reaching the setpoint. If the setpoint is reached during this time the alarm is switched off. If 
the setpoint is not reached after this time has elapsed, new checks are performed during the time 
defined in 

[,F11]

.

NOTE:

 This function takes precedence over the recirculation functions 

[,f09]

 and 

[,f10]

.

 

[,F13]

 

– T1 Sensor indication displacement (Offset):

Used to compensate for possible deviations in the sensor reading as a result of sensor replacement or 
changing the cable length.
 

[,F14]

 

– Function lock time:

Sets the time that the increment button must be pressed in order to lock/unlock parameter changes. For 
more  information  see  item  5.6  –  Function  Lock.  To  disable  this  function,  move  the  setting  to  the 
minimum until 

[,,No]

 appears.

 

[,F15]

– Intensity of the display backlight:

If the value adjusted in this function is the minimum 

[,ECO]

, the intensity of the backlight of the display 

will decrease to the minimum value (1) if no key is pressed for 5 seconds, If any key is pressed, the 
intensity will increase to (8).

Obs.: 

In the occurrence of any error information the controller signals the user, flashing the 

display's backlight shortly, in order to grab attention.

- C

  orrective measures: 

Contact the technician responsible for 

installation.