FHSAC1-230-45CE
INSTALLATION INSTRUCTIONS
®
Page
7
of
8
Fulham extends a limited warranty to the original purchaser or first user for a period of 5 years from the date of manufacture when properly installed
and operated under normal conditions of use. For complete terms and conditions, please refer to the Warranty Center at www.fulham.
Specifications subject to change without notice.
com.
2017-718-7 Rev A
0-10VDC
Pulse
DIM
02
EL-T
Self-Diagnostic tests to insure the unit is properly functional . It will test the following parameters:
*Battery-Checks to insure battery is properly connected and has sufficient capacity for 180
minutes when set to 1-3W or 90 minutes when set to 4W-6W
*LED load-Insures LED load is connected properly and functional.
*Charging circuit-Insures unit charging circuit is functioning properly.
Any errors will be shown via the indicator light as per the table below:
LED indicators on TEST SW
System Status
Permanent green
System OK
Slow flashing green
(1 sec on – 1 sec off)
Self-Diagnostic process underway
Flashing Red
(4 sec on – 1 sec off)
Battery not connected, check BAT pack
Solid Red
Load failure, check EM LED load.
Slow flashing red
(1 sec on – 1 sec off)
Battery failure, replace BAT pack.
Fast flashing red
(0,5 sec on – 0,5 sec off)
Charge circuit error, replace EM Driver.
Both Green & Red off
EM Mode
TEST SWITCH OPERATIONS:
Emergency Test Mode
1.
Press and Hold Test Button to test Emergency Mode.
This can be done in all normal AC powered situations including dimmed to off and switched off.
Manual Self-Diagnostic
1.
Quickly Press Test Button 3 times within 3 seconds to manually activate Self-Diagnostic cycle.
This will test the unit for 180 minutes when EM power set for 1W to 3W or for 90 minutes when
EM power is set for 4W or 6W.
2.
To Exit the Self-Diagnostic cycle, Press and Hold Test Button for 5 seconds
Enable / Disable Auto Self-Diagnostic
1.
Press and Hold Test Button for 3 seconds
2.
Release and Quickly Press Test Button 2 times
3.
Press and Hold Test Button again for 3 seconds
4.
Green Indicator on Test Button will flash for 5 seconds indicating the Enabled or Disabled
Status
:
Short off / Long on = Enabled
Long off / short on = Disabled